En-14
8. 2. Operation method
Depending on your installation, choose from the following:
■
By the wireless remote controller (with [TEST RUN] button)
• To start test run, press the [START/STOP] button and the [TEST RUN] button on the
remote controller.
• To end test run, press the remote controller [START/STOP] button.
■
By the IR receiver unit
• To start test run, press the [MANUAL AUTO] button of the IR receiver for more than 10
seconds (forced cooling).
• To end test run, press the [MANUAL AUTO] button for more than 3 seconds or press
the remote controller [START/STOP] button.
• The Operation indicator lamp and Timer indicator lamp will simultaneously
fl
ash during
the test run mode.
■
By the wired remote controller
• For the operation method, refer to the installation manual and the operating manual of
the wired remote controller.
Heating test run will begin in a few minutes when HEAT is selected by the remote controller
[reverse cycle model only].
9. FINISHING
Install the heat insulation material after performing a refrigerant leak check (see the
installation manual for the outdoor unit for details).
Coupler heat insulation
No gaps
Indoor unit side
Cable ties (large)
(Accessory)
Pipes
(Gas and liquid pipes)
Coupler heat insulation
(Accessory)
Be sure to overlap
the insulation.
CAUTION
There should be no gaps between the insulation and the product.
CAUTION
• After connecting the piping, check the all joints for gas leakage with gas leak detector.
• Once the pressure checking has been completed using nitrogen, please refer to the
outdoor unit installation manual to complete the evacuation process.
• Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to
do so may cause water leaks.
10. CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, and
other remote controller operations.
(2) Cleaning and maintenance of the product, and other items such as air
fi
lters and air
louvers if applicable.
(3) Give the operating and installation manuals to the customer.
(4) If the indoor unit custom code is changed, and the installation includes a wireless
remote controller, inform the customer the changed code. (On some wireless remote
controllers, the custom code may return to A when batteries are replaced.)
11. ERROR CODES
If you use a wired type remote controller, error codes will appear on the remote control-
ler display. If you use a wireless remote controller, the lamps on the IR receiver unit will
output error codes by way of blinking patterns. See the lamp blinking patterns and error
codes in the table below. An error display is displayed only during operation.
For more details, refer to the installation manual of the remote controller.
Error display
Wired
remote
controller
Error code
Description
OPERATION
lamp (green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
(1)
(1)
Serial communication error
(1)
(2)
Wired remote controller
communication error
(1)
(5)
Check run un
fi
nished
Automatic air
fl
ow adjustment error
(1)
(6)
Peripheral unit transmission PCB
connection error
(1)
(8)
External communication error
(2)
(1)
Unit number or Refrigerant circuit
address setting error
[Simultaneous Multi]
(2)
(2)
Indoor unit capacity error
(2)
(3)
Combination error
(2)
(4)
• Connection unit number
error (indoor secondary unit)
[Simultaneous Multi]
• Connection unit number error
(indoor unit or branch unit)
[Flexible Multi]
(2)
(6)
Indoor unit address setting error
(2)
(7)
Primary unit, secondary unit setup
error [Simultaneous Multi]
(2)
(9)
Connection unit number error in
wired remote controller system
(3)
(1)
Power supply interruption error
(3)
(2)
Indoor unit PCB model
information error
(3)
(3)
Indoor unit motor electricity
consumption detection error
(3)
(5)
Manual auto switch error
(3)
(9)
Indoor unit power supply error for
fan motor
(3)
(10)
Indoor unit communication circuit
(wired remote controller) error
(4)
(1)
Room temp. sensor error
(4)
(2)
Indoor unit heat ex. middle temp.
sensor error
(4)
(4)
Human sensor error
(5)
(1)
Indoor unit fan motor error