8. 2.  Operation method

Depending on your installation, choose from the following:

 

By the wireless remote controller (with [TEST RUN] button) 

•  To start test run, press the [START/STOP] button and the [TEST RUN] button on the 

remote controller. 

•  To end test run, press the remote controller [START/STOP] button. 

 

By the IR receiver unit 

•  To start test run, press the [MANUAL AUTO] button of the IR receiver for more than 10 

seconds (forced cooling).

•  To end test run, press the [MANUAL AUTO] button for more than 3 seconds or press 

the remote controller [START/STOP] button. 

•  The Operation indicator lamp and Timer indicator lamp will simultaneously 

fl

 ash during 

the test run mode. 

 

By the wired remote controller

•  For the operation method, refer to the installation manual and the operating manual of 

the wired remote controller. 

Heating test run will begin in a few minutes when HEAT is selected by the remote controller 
[reverse cycle model only].

9. FINISHING

Install the heat insulation material after performing a refrigerant leak check (see the 
installation manual for the outdoor unit for details).

Coupler heat insulation

No gaps

Indoor unit side

Cable ties (large)
(Accessory)

Pipes

(Gas and liquid pipes)

Coupler heat insulation 
(Accessory)

Be sure to overlap 
the insulation.

 CAUTION

There should be no gaps between the insulation and the product.

 CAUTION

• After connecting the piping, check the all joints for gas leakage with gas leak detector.
• Once the pressure checking has been completed using nitrogen, please refer to the 

outdoor unit installation manual to complete the evacuation process.

• Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to 

do so may cause water leaks.

10. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:
(1)  Starting and stopping method, operation switching, temperature adjustment, timer, and 

other remote controller operations.

(2)  Cleaning and maintenance of the product, and other items such as air 

fi

 lters and air 

louvers if applicable.

(3) Give the operating and installation manuals to the customer.
(4)  If the indoor unit custom code is changed, and the installation includes a wireless 

remote controller, inform the customer the changed code. (On some wireless remote 
controllers, the custom code may return to A when batteries are replaced.)

11. ERROR CODES

If you use a wired type remote controller, error codes will appear on the remote control-
ler display. If you use a wireless remote controller, the lamps on the IR receiver unit will 
output error codes by way of blinking patterns. See the lamp blinking patterns and error 
codes in the table below. An error display is displayed only during operation.
For more details, refer to the installation manual of the remote controller.

Error display

Wired 

remote 

controller 

Error code

Description

OPERATION 
lamp (green)

TIMER 

lamp 

(orange)

ECONOMY 

lamp 

(green)

(1)

(1)

Serial communication error

(1)

(2)

Wired remote controller 
communication error

(1)

(5)

Check run un

fi

 nished

Automatic air

fl

 ow adjustment error

(1)

(6)

Peripheral unit transmission PCB 
connection error

(1)

(8)

External communication error

(2)

(1)

Unit number or Refrigerant circuit 
address setting error 
[Simultaneous Multi]

(2)

(2)

Indoor unit capacity error

(2)

(3)

Combination error

(2)

(4)

• Connection unit number 

error (indoor secondary unit) 
[Simultaneous Multi]

• Connection unit number error 

(indoor unit or branch unit) 
[Flexible Multi]

(2)

(6)

Indoor unit address setting error

(2)

(7)

Primary unit, secondary unit setup 
error [Simultaneous Multi]

(2)

(9)

Connection unit number error in 
wired remote controller system

(3)

(1)

Power supply interruption error

(3)

(2)

Indoor unit PCB model 
information error

(3)

(3)

Indoor unit motor electricity 
consumption detection error

(3)

(5)

Manual auto switch error

(3)

(9)

Indoor unit power supply error for 
fan motor 

(3)

(10)

Indoor unit communication circuit 
(wired remote controller) error

(4)

(1)

Room temp. sensor error 

(4)

(2)

Indoor unit heat ex. middle temp. 
sensor error

(4)

(4)

Human sensor error

(5)

(1)

Indoor unit fan motor error

9381386246_IM.indb   14

9381386246_IM.indb   14

12/18/2018   4:09:49 PM

12/18/2018   4:09:49 PM

Содержание ARU30RGLX

Страница 1: ... in this system Carefully refer to the wir ing diagram and these instructions when wiring Improper connections and inadequate earthing grounding can cause accidental injury or death Earth Ground the unit following local electrical codes Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard When Transporting Be careful when picking up and movi...

Страница 2: ...erienced service technicians for repairing When moving or relocating the air conditioner consult experienced service technicians for disconnection and reinstallation of the product Do not touch the aluminum fins of heat exchanger built in the indoor or outdoor unit to avoid personal injury when you install or maintain the unit Do not place any other electrical products or household belongings unde...

Страница 3: ...rs pressure higher than when using conventional R22 refrigerant it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are available on the market Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter in mm Thickness in mm 1 4 6 35 0 032 0 80 3 8 9 52...

Страница 4: ...than 40 in 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the unit where ambient temperature does not reach 140 F 60 C or more Take a measure such as ventilation for an environment in which heat is retained 1 The inlet and outlet ports should not be obstruc...

Страница 5: ... and B so that the unit does not fall 3 3 3 Leveling Base vertical direction leveling on the unit right and left Right side Level AIR AIR Base horizontal direction leveling on top of the unit Drain hose 0 to 3 16 in 0 to 5 mm Level Give a slight tilt to the side to which the drain hose is connected The tilt should be in the range of 0 to 3 16 in 0 to 5 mm 3 4 Intake duct connection Follow the proc...

Страница 6: ...s given in the following figure Unit in mm 11 280 1 9 16 40 11 13 16 300 5 1 16 128 2 9 16 65 5 11 16 145 9 1 8 232 1 1 8 29 Drain pipe O D Ø1 1 4 32 Drain pipe O D Ø1 1 4 32 Right side 3 5 1 Installing the drain hose 1 Install the drain hose accessory to the drain port of the indoor unit Attach the hose band around the hose within the dimension shown Secure firmly with the hose band 2 Attach the ...

Страница 7: ...nd perform the flare processing with a flare tool Use the special R410A flare tool or the conventional flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes Check if L is flared uniformly and is not cracked or scratched Pipe Die B A L Pipe outside diameter in mm Dimension A i...

Страница 8: ... the allowable cur rent can cause electric shock or fire Match the terminal board numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a ...

Страница 9: ...ally purchased Lock nut Locally purchased Attach the conduit connector on the wiring connecting port The grommet edging and the connection cable clamp are not used Connection cable Control line Conduit connector Power line Outdoor unit Earth ground Remote controller cable 2 wire type White Red Remote controller cable Remote controller Earth Ground the remote controller if it has a earth ground wir...

Страница 10: ...mode Input signal Command OFF ON Forced stop ON OFF Normal When the forced stop is triggered indoor unit stops and Operation Stop operation by a remote controller is restricted Connected device Terminal When function setting is Operation Stop mode 2 Input signal Command OFF ON Operation ON OFF Stop R C disabled 4 2 2 External output A twisted pair cable 22AWG should be used Maximum length of cable...

Страница 11: ...e them If configuring manually it is necessary to configure both the indoor unit and the remote controller For details please refer to the remote controller installation manual Setting Setting range Switch 100 Remote controller address 00 to 15 Setting example 00 1 2 3 4 ON RC AD Example If 4 indoor units are connected RC AD SW 00 RC AD SW 01 RC AD SW 02 RC AD SW 03 Indoor unit 1 Remote controller...

Страница 12: ...ncy function such as for power outage etc Do not attempt to use this function in normal operation Be sure to operate the unit by remote controller or external device Room temperature sensor switching Only for wireless remote controller When using the Wired remote controller temperature sensor change the setting to Both 01 Factory setting Function Number Setting Value Setting Description 42 00 Indo...

Страница 13: ... to incorrect adjustments Check if the electrical wirings and duct installations are complete If there is a damper installed in the system make sure the damper is open Check if the air filter optional is attached If there are several inlet outlet ports make sure the airflow rates of each port match the designed airflow rate by adjusting the throttles Automatic airflow adjustment is possible by the...

Страница 14: ...f the product and other items such as air filters and air louvers if applicable 3 Give the operating and installation manuals to the customer 4 If the indoor unit custom code is changed and the installation includes a wireless remote controller inform the customer the changed code On some wireless remote controllers the custom code may return to A when batteries are replaced 11 ERROR CODES If you ...

Страница 15: ...4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor error Sub cool Heat Ex gas outlet temp sensor error 8 3 Liquid pipe temp sensor error 8 4 Current sensor error Error display Wired remote controller Error code Description OPERATION lamp green TIMER ...

Отзывы: