En-10
4. OPTIONAL INSTALLATION WORK
4. 1. Optional kit installation
WARNING
Regulation of cable differs from each locality, refer in accordance with local rules.
Y1
Y2
Y3
1
2
Y1
Y2
Y3
1
2
Terminal
(External in)
CN8 (Remote sensor)
CN48
(IR receiver)
CN65
(External in/out PCB)
CN47
(External out)
This air conditioner can be connected with the following optional kits.
For details on how to install optional parts, refer to the installation manual included in each
item.
Connector No.
Option type
CN48
IR receiver (UTY-LBTUM)
CN8
Remote sensor (UTY-XSZX)
CN47*1
Connect wire (UTY-XWZXZG)
CN65*2
External input and output PCB (UTY-XCSX)
*1: For external output terminal setting, refer to Function No.60 in “6. FUNCTION SETTING”.
*2: Other options (WLAN adapter, converters, etc.) may be available by using the optional
External input and output PCB.
4. 2. External input and output
4. 2. 1. External input
• Indoor unit functions such as Operation/Stop or Forced stop can be
done by using indoor unit terminals.
• “Operation/Stop” mode or “Forced stop” mode can be selected with
function setting of indoor unit.
• A twisted pair cable (22 AWG) should be used. Maximum length of
cable is 492 ft. (150 m).
• Use an external input and output cable with appropriate external
dimension, depending on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
●
Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal.
*1
PCB
Terminal
(External in)
Connected device
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
■
Operation behavior
●
Input signal type
Edge
ON
OFF
When function setting is “Operation/Stop” mode 1.
Input signal
Command
OFF
→
ON
Operation
ON
→
OFF
Stop
When function setting is “Forced stop” mode.
Input signal
Command
OFF
→
ON
Forced stop
ON
→
OFF
Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
Connected device
Terminal
When function setting is "Operation/Stop" mode 2.
Input signal
Command
OFF
→
ON
Operation
ON
→
OFF
Stop (R.C. disabled)
4. 2. 2. External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft. (25 m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
■
Output select
●
When interlocking with external device
CN47
PCB
Connected
device
Relay (locally purchased)
or
●
When displaying "Operation/Stop"
CN47
PCB
Connected device
Resistor
LED
■
Operation behavior
*If function setting "60" is set to "00"
Function setting
Status
Output voltage
60
00
Stop
0 V
Operation
DC 12 V
01 - 05
OFF
0 V
ON
DC 12 V
06
Stop
0 V
Operation
DC 12 V
07 - 08
OFF
0 V
ON
DC 12 V
09
Normal
0 V
Error
DC 12 V
10
Indoor unit fan stop
0 V
Indoor unit fan operation
DC 12 V
11
External heater OFF
0 V
External heater ON
DC 12 V
4. 2. 3. Connection methods
■
Wire modi
fi
cation
• Remove insulation from wire attached to wire kit connector.
• Remove insulation from locally purchased cable. Use crimp type insulated butt
connector to join
fi
eld cable and wire kit wire.
• Connect the wire with connecting wire with solder.
IMPORTANT:
Be sure to insulate the connection between the wires.
Locally purchased
Option parts
External output wire
Solder and insulate the connected parts.
• Connecting wires to the terminals.
Use ring terminals with insulating sleeves to connect to the terminal block.