En-10

4. OPTIONAL INSTALLATION WORK

4. 1.  Optional kit installation

 WARNING

Regulation of cable differs from each locality, refer in accordance with local rules.

Y1

Y2

Y3

1

2

Y1

Y2

Y3

1

2

 Terminal

(External in)

CN8 (Remote sensor)

 CN48 

(IR receiver)

  CN65

(External in/out PCB)

 CN47

(External out)

This air conditioner can be connected with the following optional kits.
For details on how to install optional parts, refer to the installation manual included in each 
item.

Connector No.

Option type

CN48

IR receiver (UTY-LBTUM)

CN8

Remote sensor (UTY-XSZX)

CN47*1

Connect wire (UTY-XWZXZG)

CN65*2

External input and output PCB (UTY-XCSX)

*1: For external output terminal setting, refer to Function No.60 in “6. FUNCTION SETTING”.
*2: Other options (WLAN adapter, converters, etc.) may be available by using the optional 

External input and output PCB.

4. 2.  External input and output

4. 2. 1.  External input

•  Indoor unit functions such as Operation/Stop or Forced stop can be 

done by using indoor unit terminals.

•  “Operation/Stop” mode or “Forced stop” mode can be selected with 

function setting of indoor unit.

•  A twisted pair cable (22 AWG) should be used. Maximum length of 

cable is 492 ft. (150 m).

•  Use an external input and output cable with appropriate external 

dimension, depending on the number of cables to be installed.

•  The wire connection should be separate from the power cable line.

 Dry contact terminal

When a power supply is unnecessary at the input device you want to connect, use the Dry 
contact terminal.

*1

PCB

Terminal
(External in)

Connected device

*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.

 

Operation behavior

 Input signal type

Edge

ON

OFF

When function setting is “Operation/Stop” mode 1.

Input signal

Command

OFF 

 ON

Operation

ON 

 OFF

Stop

When function setting is “Forced stop” mode.

Input signal

Command

OFF 

 ON

Forced stop

ON 

 OFF

Normal

*  When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a 

remote controller is restricted.

Connected device

Terminal 

When function setting is "Operation/Stop" mode 2.

Input signal

Command

OFF 

 ON

Operation

ON 

 OFF

Stop (R.C. disabled)

4. 2. 2.  External output

•  A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft. (25 m).
•  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

•  Output voltage: Hi DC12V±2V, Lo 0V.
•  Permissible current: 50mA

 

Output select

 When interlocking with external device

CN47

PCB

Connected 

device

Relay (locally purchased)

or

 When displaying "Operation/Stop"

CN47

PCB

Connected device

Resistor

LED

 

Operation behavior

*If function setting "60" is set to "00"

Function setting

Status

Output voltage

60

00

Stop

0 V

Operation

DC 12 V

01 - 05

OFF

0 V

ON

DC 12 V

06

Stop

0 V

Operation

DC 12 V

07 - 08

OFF

0 V

ON

DC 12 V

09

Normal

0 V

Error

DC 12 V

10

Indoor unit fan stop

0 V

Indoor unit fan operation

DC 12 V

11

External heater OFF

0 V

External heater ON

DC 12 V

4. 2. 3.  Connection methods

 

Wire modi

fi

 cation

•  Remove insulation from wire attached to wire kit connector.
•  Remove insulation from locally purchased cable. Use crimp type insulated butt 

connector to join 

fi

 eld cable and wire kit wire.

•  Connect the wire with connecting wire with solder.

IMPORTANT:

 Be sure to insulate the connection between the wires.

Locally purchased

Option parts 

External output wire

Solder and insulate the connected parts.

• Connecting wires to the terminals. 

Use ring terminals with insulating sleeves to connect to the terminal block.

• Connection terminals and wiring arrangement

In following 

fi

 gure, all the possible connections are done for description.

In actual installation, connections will differ according to each installation requirements.

9381386246_IM.indb   10

9381386246_IM.indb   10

12/18/2018   4:09:45 PM

12/18/2018   4:09:45 PM

Содержание ARU30RGLX

Страница 1: ... in this system Carefully refer to the wir ing diagram and these instructions when wiring Improper connections and inadequate earthing grounding can cause accidental injury or death Earth Ground the unit following local electrical codes Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard When Transporting Be careful when picking up and movi...

Страница 2: ...erienced service technicians for repairing When moving or relocating the air conditioner consult experienced service technicians for disconnection and reinstallation of the product Do not touch the aluminum fins of heat exchanger built in the indoor or outdoor unit to avoid personal injury when you install or maintain the unit Do not place any other electrical products or household belongings unde...

Страница 3: ...rs pressure higher than when using conventional R22 refrigerant it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are available on the market Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter in mm Thickness in mm 1 4 6 35 0 032 0 80 3 8 9 52...

Страница 4: ...than 40 in 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the unit where ambient temperature does not reach 140 F 60 C or more Take a measure such as ventilation for an environment in which heat is retained 1 The inlet and outlet ports should not be obstruc...

Страница 5: ... and B so that the unit does not fall 3 3 3 Leveling Base vertical direction leveling on the unit right and left Right side Level AIR AIR Base horizontal direction leveling on top of the unit Drain hose 0 to 3 16 in 0 to 5 mm Level Give a slight tilt to the side to which the drain hose is connected The tilt should be in the range of 0 to 3 16 in 0 to 5 mm 3 4 Intake duct connection Follow the proc...

Страница 6: ...s given in the following figure Unit in mm 11 280 1 9 16 40 11 13 16 300 5 1 16 128 2 9 16 65 5 11 16 145 9 1 8 232 1 1 8 29 Drain pipe O D Ø1 1 4 32 Drain pipe O D Ø1 1 4 32 Right side 3 5 1 Installing the drain hose 1 Install the drain hose accessory to the drain port of the indoor unit Attach the hose band around the hose within the dimension shown Secure firmly with the hose band 2 Attach the ...

Страница 7: ...nd perform the flare processing with a flare tool Use the special R410A flare tool or the conventional flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes Check if L is flared uniformly and is not cracked or scratched Pipe Die B A L Pipe outside diameter in mm Dimension A i...

Страница 8: ... the allowable cur rent can cause electric shock or fire Match the terminal board numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a ...

Страница 9: ...ally purchased Lock nut Locally purchased Attach the conduit connector on the wiring connecting port The grommet edging and the connection cable clamp are not used Connection cable Control line Conduit connector Power line Outdoor unit Earth ground Remote controller cable 2 wire type White Red Remote controller cable Remote controller Earth Ground the remote controller if it has a earth ground wir...

Страница 10: ...mode Input signal Command OFF ON Forced stop ON OFF Normal When the forced stop is triggered indoor unit stops and Operation Stop operation by a remote controller is restricted Connected device Terminal When function setting is Operation Stop mode 2 Input signal Command OFF ON Operation ON OFF Stop R C disabled 4 2 2 External output A twisted pair cable 22AWG should be used Maximum length of cable...

Страница 11: ...e them If configuring manually it is necessary to configure both the indoor unit and the remote controller For details please refer to the remote controller installation manual Setting Setting range Switch 100 Remote controller address 00 to 15 Setting example 00 1 2 3 4 ON RC AD Example If 4 indoor units are connected RC AD SW 00 RC AD SW 01 RC AD SW 02 RC AD SW 03 Indoor unit 1 Remote controller...

Страница 12: ...ncy function such as for power outage etc Do not attempt to use this function in normal operation Be sure to operate the unit by remote controller or external device Room temperature sensor switching Only for wireless remote controller When using the Wired remote controller temperature sensor change the setting to Both 01 Factory setting Function Number Setting Value Setting Description 42 00 Indo...

Страница 13: ... to incorrect adjustments Check if the electrical wirings and duct installations are complete If there is a damper installed in the system make sure the damper is open Check if the air filter optional is attached If there are several inlet outlet ports make sure the airflow rates of each port match the designed airflow rate by adjusting the throttles Automatic airflow adjustment is possible by the...

Страница 14: ...f the product and other items such as air filters and air louvers if applicable 3 Give the operating and installation manuals to the customer 4 If the indoor unit custom code is changed and the installation includes a wireless remote controller inform the customer the changed code On some wireless remote controllers the custom code may return to A when batteries are replaced 11 ERROR CODES If you ...

Страница 15: ...4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor error Sub cool Heat Ex gas outlet temp sensor error 8 3 Liquid pipe temp sensor error 8 4 Current sensor error Error display Wired remote controller Error code Description OPERATION lamp green TIMER ...

Отзывы: