En-20
10.3.1. Function Details
Filter sign
Select appropriate intervals for displaying the
fi
lter sign on the
indoor unit according to the estimated amount of dust in the
air of the room.
If the indication is not required, select "No indication" (03).
(
♦
... Factory setting)
Function
Number
Setting
Value
Setting Description
11
00
Standard (400 hours)
01
Long interval (1000 hours)
02
Short interval (200 hours)
03
No indication
♦
Static pressure
Select the appropriate static pressure according to the instal-
lation conditions.
(
♦
... Factory setting)
Function
Number
Setting
Value
Setting Description
26
00
0 in. WG (0 Pa)
01
0.04 in. WG (10 Pa)
02
0.08 in. WG (20 Pa)
03
0.12 in. WG (30 Pa)
04
0.16 in. WG (40 Pa)
05
0.20 in. WG (50 Pa)
06
0.24 in. WG (60 Pa)
07
0.28 in. WG (70 Pa)
08
0.32 in. WG (80 Pa)
09
0.36 in. WG (90 Pa)
31
0.1 in. WG (25 Pa)
[Standard]
♦
Range of static pressure is different by model.
Model Name
Range of Static Pressure
ARU7RLF
0 to 0.36 in. WG (0 to 90 Pa)
ARU9RLF
ARU12RLF
ARU18RLF
ARU24RLF
0 to 0.2 in. WG (0 to 50 Pa)
Auto restart
Enable or disable automatic restart after a power interruption.
(
♦
... Factory setting)
Function
Number
Setting
Value
Setting Description
40
00
Enable
♦
01
Disable
* Auto restart is an emergency function such as for power
outage etc. Do not attempt to use this function in normal
operation. Be sure to operate the unit by remote controller or
external device.
Room temperature sensor switching
(Only for Wired remote controller)
When using the Wired remote controller temperature sensor,
change the setting to "Both" (01).
(
♦
... Factory setting)
Function
Number
Setting
Value
Setting Description
42
00
Indoor unit
♦
01
Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller
are active.
* Remote controller sensor must be turned on by using the
remote controller
Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
(
♦
... Factory setting)
Function
Number
Setting
Value
Setting Description
44
00
A
♦
01
B
02
C
03
D
External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
♦
... Factory setting)
Function
Number
Setting
Value
Setting Description
46
00
Operation/Stop mode
♦
01
(Setting prohibited)
02
Forced stop mode
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller
only, change the setting to "Wired remote controller" (01). This
function will only work if the function setting 42 is set at "Both"
(01)
(
♦
... Factory setting)
Function
Number
Setting
Value
Setting Description
48
00
Both
01
Wired remote controller
♦
Setting record
Record any changes to the settings in the following table.
Setting
Setting Value
Filter sign
Static pressure
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
After completing the Function Setting, be sure to turn off the
power and turn it on again.