En-4

3.3.2. Multiple outdoor unit installation

Provide at least 15 mm of space between the outdoor units if multiple units are 

• 

installed.
When routing the piping from the side of an outdoor unit, provide space for the piping.

• 

No more than 3 units must be installed side by side. 

• 

When 3 units or more are arranged in a line, provide the space as shown in the 
following example when an obstruction is present also in the upward area.

When the upward area is open 

(Unit : mm)

(1)  Obstacles at rear only

(2)  Obstacles at front only

 

  

  

  

 

1500 or more

300

(3)  Obstacles at front and rear only

500

1500 or more

When an obstruction is present also in the upward area 

(Unit : mm)

Obstacles at rear and above only

• 

1500

500

Max. 300

1500

3.3.3. Outdoor units installation in multi row

 (Unit : mm)

(1) Single parallel unit arrangement

150

600

1000

2000 or more

(2) Multiple parallel unit arrangement

500

600

1500

3000 or more

3.4. Transporting the unit

 

WARNING

Do not touch the fins. 

 

Otherwise, personal injury could result.

 

CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful. 

If the outdoor unit is carried from the bottom, hands or fingers may be pinched.

Carry slowly in the manner as shown on “Fig. B” holding the handles “Fig. A” in right 

• 

and left sides. (Be careful not to touch with hands or objects.)
Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on 

• 

the sides of the unit may be deformed.

Handle

Suction grille

Handle

Suction grille

Fig. A

Fig. B

Front view

Rear view

3.5. Installation

(Unit : mm)

4 - Φ 12 Hole

132

AIR

650

119

50

50

16

370

Install 4 anchor bolts at the locations indicated with arrows in the above figure.

• 

To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

• 

base (such as concrete blocks).

The foundation shall support the legs of the unit and have a width of 50 mm or more.

• 

Depending on the installation conditions, the outdoor unit may spread its vibration 

• 

during operation, which may cause noise and vibration. Therefore, attach damping 
materials (such as damping pads) to the outdoor unit during installation.

Install the foundation, making sure that there is enough space for installing the 

• 

connection pipes.

Secure the unit to a solid block using foundation bolts. 

 

• 

(Use 4 sets of commercially available M10 bolts, nuts, and washers.)
The bolts should protrude 20 mm.  

• 

(Refer to the figure below.)

If overturning prevention is required, purchase the necessary commercially available 

• 

items.

Bolt

20 mm

Nut

Block

Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt, 

nut and washer.)

9379069380_IM.indb   4

1/25/2013   12:00:46 PM

Содержание AOYG45LETL

Страница 1: ...uement MANUAL DE INSTALACIÓN UNIDAD EXTERIOR Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Apenas para pessoal de assistência autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для...

Страница 2: ...g not attached properly with 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to rupture and even injury When installing and relocating the air conditioner do not mix gases other than the specified refrigerant R410A to enter the refrigerant cycle If air or other gas enters the refrigerant cycle the pressure inside the cycle will rise to an abnormally high val...

Страница 3: ...gerant leak occurs during operation immediately vacate the premises and thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas The basic installation work procedures are the same as conventional refrigerant models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant...

Страница 4: ...pipe may freeze in extremely cold weather Reverse cycle model only As the drain water flows out of the outdoor unit during heating operation install the drain pipe and connect it to a commercial 16 mm hose Reverse cycle model only When installing the drain pipe plug all the holes other than the drain pipe mounting hole in the bottom of the outdoor unit with putty so there is no water leakage Rever...

Страница 5: ...n on Fig B holding the handles Fig A in right and left sides Be careful not to touch with hands or objects Be sure to hold the handles on the sides of the unit Otherwise the suction grilles on the sides of the unit may be deformed Handle Suction grille Handle Suction grille Fig A Fig B Front view Rear view 3 5 Installation Unit mm 4 Φ 12 Hole 132 AIR 650 119 50 50 16 370 Install 4 anchor bolts at ...

Страница 6: ...ength L m 50 Min piping length L m 5 Max height difference H Indoor unit to outdoor unit m 30 View Example H L sd 5 PIPE INSTALLATION 1 5 1 Opening a knock out hole CAUTION Be careful not to deform or scratch the panel while opening the knock out holes To protect the piping insulation after opening a knock out hole remove any burrs from the edge of the hole It is recommended to apply rust preventi...

Страница 7: ...to install the pipe against the port on the indoor unit and the outdoor unit correctly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the outdoor unit pipe until immediately before connecting the connection pipe After installing the piping make sure that the connection pipes do ...

Страница 8: ...y removing the blank caps from the gas and liquid pipes 2 Remove the charging port cap and connect the gauge manifold and the vacuum pump to the charging valve with the service hoses 3 Vacuum the indoor unit and the connecting pipes until the pressure gauge indicates 0 1 MPa 76 cmHg 4 When 0 1 MPa 76 cmHg is reached operate the vacuum pump for at least 60 minutes 5 Disconnect the service hoses and...

Страница 9: ...ry For the additional amount see the table below Additional charging amount Refrigerant pipe size mm in Piping length L 20 m 30 m 40 m 50 m g m Liquid 9 52 3 8 None 400 g 800 g 1 200 g 40 g m Gas 15 88 5 8 sd Refer to 4 3 Refrigerant pipe size and allowable piping length 6 ELECTRICAL WIRING Cable Cable size mm Type Remarks Power Supply Cable 6 Type60245 IEC66 3 Cable Ground 1 Φ 230 V Connection Ca...

Страница 10: ...f the knock out hole from cutting the wires It is recommended to apply anti rust paint to the edge of the knock out hole Knock out holes are provided for wiring Fig A Knock out holes are provided 2 each in the same size in front lateral and rear sides Fig A Installation method of One touch bush Please fix the One touch bush accessory as shown below Fig B Fig B Pipe cover rear Pipe cover front Fron...

Страница 11: ...locally to avoid any gap Fig A If small animals such as insects enter the external unit a short circuit may be caused near electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and ...

Страница 12: ...witches Never touch the terminals or the patterns on the parts that are mounted on the board 9 1 Field setting buttons Remove the front panel of the outdoor unit access the print circuit board of the display unit Print circuit board buttons for various settings and LED displays are shown in the figure LED display part Button part 9 2 Function settings Various functions can be set Follow the settin...

Страница 13: ... SW2 and adjust LED lamp as shown below Current setting is displayed LOW NOISE L2 L3 PEAK CUT MODE Blink Sign Lights off 4 Press ENTER button SW3 LOW NOISE L2 L3 PEAK CUT MODE Sign Lights off Lights on 5 Press SELECT button SW2 and adjust LED lamp as shown in below figure PEAK CUT L4 L5 L6 Level 1 0 of rated input ratio Blink Level 2 50 of rated input ratio Blink Level 3 75 of rated input ratio Bl...

Страница 14: ...roblems adjust immediately and recheck 10 1 2 Low noise mode CN10 This features reduces the operating sound of the outdoor unit from the normal sound The air conditioner is set to the Low noise mode when closing the contact input of a commercial timer or ON OFF switch to a connector on the outdoor control PC board Performance may drop depending on the outside air temperature condition etc Set the ...

Страница 15: ...et with test operation setting refer to installation instructions manual of indoor unit for further details available in the remote controller Cooling Operation and Heating Operation can be set using SELECT button and ENTER button available on the board of display unit Make sure to perform the first test operation with cooling operation Set as per the procedure given below LED display part Button ...

Страница 16: ...nk 3 times Outdoor unit Heat Ex liquid temp sensor error Blink 2 times Blink 7 times Blink 3 times Outdoor temp sensor error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Current sensor 1 error stoppage permanently Blink 2 times Blink 8 times Blink 4 times Pr...

Страница 17: ... PUMP DOWN button is pressed while the compressor is operating the compressor will stop then start again in about 3 minutes 4 LED display will change as shown below about 3 minutes after the compressor starts Fully close the 3 way valve on the liquid pipe side at this stage POWER ERROR PUMP DOWN LOW NOISE PEAK CUT MODE L1 L2 L3 L4 L5 L6 Sign Lights off Lights on If the valve on the liquid pipe sid...

Отзывы: