Drain installation

21 21 

 

CAUTION

Perform drain work in accordance with this Manual, and ensure that the drain 

 

water is properly drained. If the drain work is not carried out correctly, water may 

drip down from the unit, wetting the furniture.
When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe 

 

and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe 

may freeze in extremely cold weather. (Reverse cycle model only)
As the drain water flows out of the outdoor unit during heating operation, install the 

 

drain pipe and connect it to a commercial 16mm hose. (Reverse cycle model only)

When installing the drain pipe, plug all the holes other than the drain pipe 

 

mounting hole in the bottom of the outdoor unit with putty so there is no water 

leakage. (Reverse cycle model only)

341

305

227

438

50

622

Drain cap mounting hole ×2

(Unit:mm)

Drain pipe mounting 

 hole ×1

Base

Drain pipe

Drain pipe mounting hole

Installation dimensions

21 21 

 

CAUTION

The installation space shown in the following examples is based on an ambient 

 

temperature under cooling operation of 35 °C (DB) at the air intake of the 

outdoor unit. Provide more space around the air intake than shown in the 

examples if the ambient temperature exceeds 35 °C (DB) or if the thermal load 

of all of the outdoor units exceeds the capacity.
Consider the transportation route, installation space, maintenance space, and 

 

access, and install the unit in a location with sufficient space for the refrigerant 

piping.

Observe the installation space specifications that are shown in the figures. 

 

 

Provide the same space for the air intake at the rear of the outdoor unit.  

If the installation is not performed according to the specifications, it could cause 

a short circuit and result in a lack of operating performance. As a result, the 

outdoor unit might easily be stopped by high-pressure protection.

Air intake

Rear view

Installation methods not shown in the following examples are not recommended. 

 

Performance may drop significantly.

INSTALLATION WORK

21 

Please obtain the approval of the customer when selecting the location of installation 

and installing the unit.

Selecting an installation location

21 11 

 

WARNING

Securely install the outdoor unit at a location that can withstand the weight of 

 

the unit. Otherwise, the outdoor unit may fall and cause injury.
Be sure to install the outdoor unit as prescribed, so that it can withstand 

 

earthquakes and typhoons or other strong winds. Improper installation can 

cause the unit to topple or fall, or other accidents.
Do not install the outdoor unit near the edge of a balcony. Otherwise, children 

 

may climb onto the outdoor unit and fall off of the balcony.

 

CAUTION

Do not install the outdoor unit in the following areas:

 

Area with high salt content, such as at the seaside. It will deteriorate metal 

 

parts, causing the parts to fail or the unit to leak water.

Area filled with mineral oil or containing a large amount of splashed oil or 

 

steam, such as a kitchen. It will deteriorate plastic parts, causing the parts to 

fail or the unit to leak water.

Area that generates substances that adversely affect the equipment, such as 

 

sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and 

brazed joints to corrode, which can cause refrigerant leakage.

Area containing equipment that generates electromagnetic interference. It will 

 

cause the control system to malfunction, preventing the unit from operating 

normally.

Area that can cause combustible gas to leak, contains suspended carbon 

 

fibers or flammable dust, or volatile inflammables such as paint thinner or 

gasoline. If gas leaks and settles around the unit, it can cause a fire.

Area that has heat sources, vapors, or the risk of the leakage of flammable 

 

gas in the vicinity.

Area where small animals may live. It may cause failure, smoke or fire if small 

 

animals enter and touch internal electrical parts.

Area where animals may urinate on the unit or ammonia may be generated.

 

Please install the outdoor unit without slant.

 

Install the outdoor unit in a well-ventilated location away from rain or direct 

 

sunlight.
If the outdoor unit must be installed in an area within easy reach of the general 

 

public, install as necessary a protective fence or the like to prevent their access.
Install the outdoor unit in a location that would not inconvenience your 

 

neighbors, as they could be affected by the airflow coming out from the outlet, 

noise, or vibration. If it must be installed in proximity to your neighbors, be sure 

to obtain their approval.
If the outdoor unit is installed in a cold region that is affected by snow 

 

accumulation, snow fall, or freezing, take appropriate measures to protect it 

from those elements. To ensure a stable operation, install inlet and outlet ducts.
Install the outdoor unit in a location that is away from exhaust or the vent ports 

 

that discharge vapor, soot, dust, or debris.
Install the indoor unit, outdoor unit, power supply cable, connection cable, and 

 

remote control cable at least 1 m away from a television or radio receivers. The 

purpose of this is to prevent TV reception interference or radio noise. (Even if 

they are installed more than 1 m apart, you could still receive noise under some 

signal conditions.)

Branch switch and 

circuit breaker

Branch switch and 

circuit breaker

1m or more

1 m or more

If children under 10 years old may approach the unit, take preventive measures 

 

so that they cannot reach the unit.
Keep the length of the piping of the indoor and outdoor units within the allowable 

 

range.

For maintenance purposes, do not bury the piping.

 

9379069366_IM.indb   4

15/11/2555   11:17:48

Содержание aoyg45lbt8

Страница 1: ...AZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ MONTAJ KILAVUZU For authorized personnel only Nur für autorisiertes Personal Pour le personnel agréé uniquement Solo para personal autorizado Ad uso esclusivo del personale autorizzato Για εξουσιοδοτημένο προσωπικό σέρβις Apenas para técnicos autorizados Для уполномоченного персонала Yetkili servis personeli içindir 93790...

Страница 2: ...gauge manifold and charging hose for R410A exclusively CAUTION This mark indicates procedures which if improperly performed might possibly result in personal harm to the user or damage to property Read carefully all security information before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by...

Страница 3: ...e gauge with seals 0 1 to 5 3 MPa 1 to 53 bar for high pressure 0 1 to 3 8 MPa 1 to 38 bar for low pressure Charge hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A Accessories 222222 WARNING For installat...

Страница 4: ...ome with them Primary unit Branch box that is connected to the Outdoor unit Secondary unit Branch box that is connected to the Branch box Primary Branch box Secondary2 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Separation tube Separation tube Outdoor unit Piping Power supply Transmission line Power supply and Transmisson line Power supply Power ...

Страница 5: ...not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substa...

Страница 6: ...rrangement 500 600 1500 3000 or more Transportation of the unit 333333 WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Be sure to hold the handles on the sides of the unit Otherwise holding the suction grille ...

Страница 7: ... j k l m Between outdoor unit and the first separation tube 5 or more a Between outdoor unit and branch box when there is no separation tube 5 or more a d Allowable height difference Between outdoor unit and indoor unit 30 or less H1 Between outdoor unit and branch box 30 or less H2 Between branch box and branch box 15 or less H3 Between indoor unit and indoor unit 15 or less H4 Pipe size selectio...

Страница 8: ...r on the front of the outdoor unit and open the knockout hole provided at the bottom corner of the piping outlet It can be installed as shown on Fig B cutting out the 2 slits as indicated on Fig C When cutting slits use a steel saw Service panel Fig A Slit Slit Fig B Bottom connection Fig C Front connection Bottom connection Lateral connection Rear connection Separation tube connection 555555 CAUT...

Страница 9: ...uid Flare nut Connection pipe Gas Flare nut CAUTION Hold the torque wrench at its grip keeping it in a right angle with the pipe in order to tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a holding wrench spanner and fasten with a torque wrench refer to below diagram Do not apply force to the blank cap of the valv...

Страница 10: ...les and breaker differs from each locality refer in accordance with local rules Voltage rating 1Φ 230V 50Hz Operating range 198 264V Cable Cable size mm2 1 Remarks Power supply cable 6 0 2 cable Ground 1 Ø 230V Connection cable 2 5 3 cable Ground 1 Ø 230V Selected sample Select the correct cable type and size according to the country or region s regulations Max wire length Set a length so that the...

Страница 11: ...h box Branch box Secondary2 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Optional terminal Optional terminal Optional terminal Primary Connecting of wiring 666666 1 Remove the service covers and insulation sheet And connect the wires to the terminal in accordance with the terminal nameplate Fig A Fig B 2 After connecting the wires use binders to s...

Страница 12: ...ing valve with the service hoses Vacuum the indoor unit and the connecting pipes until the pressure gauge indicates 0 1 MPa 1bar When 0 1 MPa 1bar is reached make sure it hold vacuum for 60 minutes Disconnect the service hoses and fit the charging port cap to the charging valve to the specified torque Refer to below table Remove the blank caps and fully open the 3 way valves with a hexagon wrench ...

Страница 13: ... piping holes and wiring holes with putty supplied locally to avoid any gap Fig A If small animals such as insects enter the external unit a short circuit may be caused near electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit The...

Страница 14: ...t first Priority given to external input of outdoor unit Priority is given to the operation mode which is set by the external input terminal CN932 Priority given to external input of outdoor unit 0 1 28 Forbidden Forbidden 2 8 0 0 Setting forbidden 0 1 29 Forbidden Forbidden 2 9 0 0 Setting forbidden 0 1 30 Energy saving level setting Level 1 stop 3 0 0 0 The capacity limit can be selected when op...

Страница 15: ...conds after the setting the display will return to 2 Setting the first 2 digits If there is no operation for 5 seconds after the setting the display will return to 2 Setting the first 2 digits Press the MODE EXIT button to cancel the setting mode Setting is complete when the lamp lights up Setting is complete when the lamp lights up Press the ENTER button for more than 3 seconds Press the ENTER bu...

Страница 16: ...e the room temperature could get too low or too high Depending on the difference of the room temperature of each room a judgment may be impossible Operating procedure for Check run 999999999 1 Turn power on the outdoor unit indoor units and branch boxes After the displayed number of 8888 has been turned off press the CHECK button approximately 2 minutes 2 Press and hold the CHECK button for more t...

Страница 17: ...ct the Connection cable which is connected to the terminal A on Branch box Primary to the terminal B on Branch box Secondary2 A Branch box Terminal A b Branch box Terminal B C Branch box Terminal C 1 Branch box Primary 2 Branch box Secondary 1 3 Branch box Secondary 2 unit error This is a unit error For error content please refer to 11 2 Error display mode TEST RUN 999999 Pre test run check items ...

Страница 18: ...seconds This will be displayed when the cooling test run starts This will be displayed when the cooling operation mode is canceled It takes approximately 30 seconds for the outdoor unit to stop its operation It takes approximately 30 seconds for the outdoor unit to stop its operation It takes approximately 30 seconds for the outdoor unit to start its operation It takes approximately 30 seconds for...

Страница 19: ...ield supply Ex Switch Connection cable option Signal Connector 1 1 1 1 2 2 2 2 10 m Make the distance from the PC board to the connected unit within 10m Contact capacity 24VDC or more 10mA or more Low noise mode CN931 1111111111 This features reduces the operating sound of the outdoor unit from the normal sound The air conditioner is set to the Low noise mode when closing the contact input of a co...

Страница 20: ... alternately displayed on the 7 seg display The latest error code can be confirmed by pressing the ENTER button When error codes are displayed all the error codes can be confirmed by pressing the SELECT button When the error display appears even though the measures for error are taken switch on the power again after turning off the power When the power is turned on again after turned off wait appr...

Страница 21: ...En 20 7 seg display 㪃 㪃 㪃 㪃 㪃 㪃 㪃 㪃 㫋㪑 㪣㪑 㪎㪑 㪟㪑 㪡㪑 㪍㪑 㪘㪑 㪚㪑 㪜㪑 㪝㪑 㪃 㪃 㪻㪑 㫉㪑 㪃 㪃 㪃 㪃 㪃 㪐㪑 㪧㪑 㪬㪑 㪪㪑 㪏㪑 㪃 㪃 㪃 㪃 㪌㪑 㪊㪑 㪋㪑 㪈㪑 㪉㪑 㪃 㪙㪑 㫅㪑 㫆㪑 㪃 㪃 9379069366_IM indb 20 15 11 2555 11 18 28 ...

Отзывы: