Fujitsu aoyg45lbt8 Скачать руководство пользователя страница 14

En-12

Function settings

81 21 

Various functions can be set. Set when necessary.

Perform settings after all indoor units have stopped operation.

Refer to Table A for the items that can be set.

A: List of Settings

Table1 

No

Setting Item

7 seg

Factory 

default

Content

First 2 digits Last 2 digits

11

Cooling capacity shift

Standard

1

1

0

0

•  

Please set this item when cooling ability is inadequate.

•  

If cooling ability is inadequate due to the setting of “High power mode1”, 

please set it to “High power mode2”.

High power mode1

0

1

High power mode2

0

2

20

Switching between batch 

stop or emergency stop

Batch stop

2

0

0

0

This mode selects the pattern of the stop function to be operated by the 

external input terminal (CN934). 

•  

Batch stop: The stop of all indoor units connected to same refrigerant 

system due to input signal coming from CN934. 

•  Emergency stop: The air conditioner returns to the original operation if 

input from the CN934 is stopped. Furthermore, the air conditioner does 

not accept the operation of the indoor unit when emergency stop is 

actuated.

Emergency stop

0

1

21

Operation mode selecting 

method

Priority given to the frst 

command

2

1

0

0

Select the priority setting of the operation mode.

•  Priority given to the first command: Priority is given to the operation 

mode which is set first. 

•  Priority given to external input of outdoor unit: Priority is given to the 

operation mode which is set by the external input terminal (CN932).

Priority given to external 

input of outdoor unit

0

1

28

Forbidden

Forbidden

2

8

0

0

Setting forbidden

0

1

29

Forbidden

Forbidden

2

9

0

0

Setting forbidden

0

1

30

Energy saving level  

setting

Level 1 (stop)

3

0

0

0

The capacity limit can be selected when operating with the “Energy 

Saving Peak Cut function.”

The operation selection can be done by external input terminal (CN933).

The lower the level, the more the effect of energy saving, but the cooling/

heating performance decreases.

Level 2 (Limited at 50%)

0

1

Level 3 (Limited at 75%)

0

2

Level 4 (Limited at 100%)

0

3

34

Frost

Protection Fan

Mode

On

3

4

0

0

This mode is the function to prevent frosting to the propeller fan of 

outdoor unit during heating operation.

Off

3

4

0

1

41

Low noise mode setting

Off (Normal)

4

1

0

0

When “Low noise mode ON” is selected, the operating noise will be 

suppressed.

Without external input terminal: It operates by selecting Low noise mode 

ON.

With external input terminal: The operation selection can be done by 

external input terminal (CN931) by selecting Low noise mode OFF. 

On (Low noise mode)

0

1

42

Low noise mode operation 

level setting

Level 1 (-3dB)

4

2

0

0

The noise level when operating in the low noise mode can be set.

Cooling/heating performance decreases by lowering operation noise 

level.

Level 2 (-6dB)

0

1

Level 3 (-9dB)

0

2

9379069366_IM.indb   13

15/11/2555   11:18:25

Содержание aoyg45lbt8

Страница 1: ...AZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ MONTAJ KILAVUZU For authorized personnel only Nur für autorisiertes Personal Pour le personnel agréé uniquement Solo para personal autorizado Ad uso esclusivo del personale autorizzato Για εξουσιοδοτημένο προσωπικό σέρβις Apenas para técnicos autorizados Для уполномоченного персонала Yetkili servis personeli içindir 93790...

Страница 2: ...gauge manifold and charging hose for R410A exclusively CAUTION This mark indicates procedures which if improperly performed might possibly result in personal harm to the user or damage to property Read carefully all security information before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by...

Страница 3: ...e gauge with seals 0 1 to 5 3 MPa 1 to 53 bar for high pressure 0 1 to 3 8 MPa 1 to 38 bar for low pressure Charge hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A Accessories 222222 WARNING For installat...

Страница 4: ...ome with them Primary unit Branch box that is connected to the Outdoor unit Secondary unit Branch box that is connected to the Branch box Primary Branch box Secondary2 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Separation tube Separation tube Outdoor unit Piping Power supply Transmission line Power supply and Transmisson line Power supply Power ...

Страница 5: ...not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substa...

Страница 6: ...rrangement 500 600 1500 3000 or more Transportation of the unit 333333 WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Be sure to hold the handles on the sides of the unit Otherwise holding the suction grille ...

Страница 7: ... j k l m Between outdoor unit and the first separation tube 5 or more a Between outdoor unit and branch box when there is no separation tube 5 or more a d Allowable height difference Between outdoor unit and indoor unit 30 or less H1 Between outdoor unit and branch box 30 or less H2 Between branch box and branch box 15 or less H3 Between indoor unit and indoor unit 15 or less H4 Pipe size selectio...

Страница 8: ...r on the front of the outdoor unit and open the knockout hole provided at the bottom corner of the piping outlet It can be installed as shown on Fig B cutting out the 2 slits as indicated on Fig C When cutting slits use a steel saw Service panel Fig A Slit Slit Fig B Bottom connection Fig C Front connection Bottom connection Lateral connection Rear connection Separation tube connection 555555 CAUT...

Страница 9: ...uid Flare nut Connection pipe Gas Flare nut CAUTION Hold the torque wrench at its grip keeping it in a right angle with the pipe in order to tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a holding wrench spanner and fasten with a torque wrench refer to below diagram Do not apply force to the blank cap of the valv...

Страница 10: ...les and breaker differs from each locality refer in accordance with local rules Voltage rating 1Φ 230V 50Hz Operating range 198 264V Cable Cable size mm2 1 Remarks Power supply cable 6 0 2 cable Ground 1 Ø 230V Connection cable 2 5 3 cable Ground 1 Ø 230V Selected sample Select the correct cable type and size according to the country or region s regulations Max wire length Set a length so that the...

Страница 11: ...h box Branch box Secondary2 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Optional terminal Optional terminal Optional terminal Primary Connecting of wiring 666666 1 Remove the service covers and insulation sheet And connect the wires to the terminal in accordance with the terminal nameplate Fig A Fig B 2 After connecting the wires use binders to s...

Страница 12: ...ing valve with the service hoses Vacuum the indoor unit and the connecting pipes until the pressure gauge indicates 0 1 MPa 1bar When 0 1 MPa 1bar is reached make sure it hold vacuum for 60 minutes Disconnect the service hoses and fit the charging port cap to the charging valve to the specified torque Refer to below table Remove the blank caps and fully open the 3 way valves with a hexagon wrench ...

Страница 13: ... piping holes and wiring holes with putty supplied locally to avoid any gap Fig A If small animals such as insects enter the external unit a short circuit may be caused near electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit The...

Страница 14: ...t first Priority given to external input of outdoor unit Priority is given to the operation mode which is set by the external input terminal CN932 Priority given to external input of outdoor unit 0 1 28 Forbidden Forbidden 2 8 0 0 Setting forbidden 0 1 29 Forbidden Forbidden 2 9 0 0 Setting forbidden 0 1 30 Energy saving level setting Level 1 stop 3 0 0 0 The capacity limit can be selected when op...

Страница 15: ...conds after the setting the display will return to 2 Setting the first 2 digits If there is no operation for 5 seconds after the setting the display will return to 2 Setting the first 2 digits Press the MODE EXIT button to cancel the setting mode Setting is complete when the lamp lights up Setting is complete when the lamp lights up Press the ENTER button for more than 3 seconds Press the ENTER bu...

Страница 16: ...e the room temperature could get too low or too high Depending on the difference of the room temperature of each room a judgment may be impossible Operating procedure for Check run 999999999 1 Turn power on the outdoor unit indoor units and branch boxes After the displayed number of 8888 has been turned off press the CHECK button approximately 2 minutes 2 Press and hold the CHECK button for more t...

Страница 17: ...ct the Connection cable which is connected to the terminal A on Branch box Primary to the terminal B on Branch box Secondary2 A Branch box Terminal A b Branch box Terminal B C Branch box Terminal C 1 Branch box Primary 2 Branch box Secondary 1 3 Branch box Secondary 2 unit error This is a unit error For error content please refer to 11 2 Error display mode TEST RUN 999999 Pre test run check items ...

Страница 18: ...seconds This will be displayed when the cooling test run starts This will be displayed when the cooling operation mode is canceled It takes approximately 30 seconds for the outdoor unit to stop its operation It takes approximately 30 seconds for the outdoor unit to stop its operation It takes approximately 30 seconds for the outdoor unit to start its operation It takes approximately 30 seconds for...

Страница 19: ...ield supply Ex Switch Connection cable option Signal Connector 1 1 1 1 2 2 2 2 10 m Make the distance from the PC board to the connected unit within 10m Contact capacity 24VDC or more 10mA or more Low noise mode CN931 1111111111 This features reduces the operating sound of the outdoor unit from the normal sound The air conditioner is set to the Low noise mode when closing the contact input of a co...

Страница 20: ... alternately displayed on the 7 seg display The latest error code can be confirmed by pressing the ENTER button When error codes are displayed all the error codes can be confirmed by pressing the SELECT button When the error display appears even though the measures for error are taken switch on the power again after turning off the power When the power is turned on again after turned off wait appr...

Страница 21: ...En 20 7 seg display 㪃 㪃 㪃 㪃 㪃 㪃 㪃 㪃 㫋㪑 㪣㪑 㪎㪑 㪟㪑 㪡㪑 㪍㪑 㪘㪑 㪚㪑 㪜㪑 㪝㪑 㪃 㪃 㪻㪑 㫉㪑 㪃 㪃 㪃 㪃 㪃 㪐㪑 㪧㪑 㪬㪑 㪪㪑 㪏㪑 㪃 㪃 㪃 㪃 㪌㪑 㪊㪑 㪋㪑 㪈㪑 㪉㪑 㪃 㪙㪑 㫅㪑 㫆㪑 㪃 㪃 9379069366_IM indb 20 15 11 2555 11 18 28 ...

Отзывы: