En-3

 CAUTION

If the outdoor unit must be installed in an area within easy reach of the general public, 

install as necessary a protective fence or the like to prevent their access.

Install the outdoor unit in a location that would not inconvenience your neighbors, as 

they could be affected by the airflow coming out from the outlet, noise, or vibration. If it 

must be installed in proximity to your neighbors, be sure to obtain their approval.
If the outdoor unit is installed in a cold region that is affected by snow accumulation, 

snow fall, or freezing, take appropriate measures to protect it from those elements. To 

ensure a stable operation, install inlet and outlet ducts.
Install the outdoor unit in a location that is away from exhaust or the vent ports that 

discharge vapor, soot, dust, or debris.

Install the indoor unit, outdoor unit, power supply cable, connection cable, and remote 

controller cable at least 1 m away from a television or radio receivers. The purpose of 

this is to prevent TV reception interference or radio noise. (Even if they are installed 

more than 1 m apart, you could still receive noise under some signal conditions.)

Branch switch and 

circuit breaker

1 m or more

1 m or more

Branch switch and 

circuit breaker

If children under 10 years old may approach the unit, take preventive measures so that 

they cannot reach the unit.

Keep the length of the piping of the indoor and outdoor units within the allowable range.

For maintenance purposes, do not bury the piping.

3.2. Drain installation

 CAUTION

Perform drain work in accordance with this Manual, and ensure that the drain water is 

properly drained. If the drain work is not carried out correctly, water may drip down from 

the unit, wetting the furniture.

When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe 

and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may 

freeze in extremely cold weather. (Reverse cycle model only)

Outdoor unit to be fasten with bolts at the four places indicated by the arrows without fail.

AIR

Bottom side

Drain cap 

mounting place

Drain pipe  

mounting place

Since the drain water flows out of the outdoor unit during heating operation, install the drain 

pipe and connect it to a commercial 16 mm hose. (Reverse cycle model only)

When installing the drain pipe, plug all the holes other than the drain pipe mounting hole 

in the bottom of the outdoor unit with putty so there is no water leakage. (Reverse cycle 

model only)

Drain pipe mounting hole

Base

Drain pipe

3.3. Installation dimensions

 CAUTION

Select installation locations that can properly support the weight of the indoor and 

outdoor units. Install the units securely so that they do not topple or fall.

 WARNING

Do not install where there is the danger of combustible gas leakage.
Do not install the unit near heat source of heat, steam, or flammable gas.
If children under 10 years old may approach the unit, take preventive measures so that 

they cannot reach the unit.

 CAUTION

Install the unit where it will not be tilted by more than 3˚. However, do not install the unit 

with it tilted towards the side containing the compressor.
When installing the outdoor unit where it may exposed to strong wind, fasten it securely.

Decide the mounting position with the customer as follows:

(1) Install the outdoor unit in a location which can withstand the weight of the unit and 

vibration, and which can install horizontally.

(2) Provide the indicated space to ensure good airflow.

(3) If possible, do not install the unit where it will be exposed to direct sunlight.

  (If necessary, install a blind that does not interfere with the airflow.)

(4) Do not install the unit near a source of heat, steam, or flammable gas.

(5) During heating operation, drain water flows from the outdoor unit.

  Therefore, install the outdoor unit in a place where the drain water flow will not be 

obstructed. (Reverse cycle model only)

(6) Do not install the unit where strong wind blows or where it is very dusty.

(7) Do not install the unit where people pass.

(8) Install the outdoor unit in a place where it will be free from being dirty or getting wet by 

rain as much as possible.

(9) Install the unit where connection to the indoor unit is easy.

3.3.1. Single outdoor unit installation

When the upward area is open

When there are 

 

obstacles at the 

back 

side.

100 mm

 

or more

AIR

When there are 

 

obstacles at the 

back and front 

sides.

100 mm

 

or more

600 mm

 

or more

AIR

9374995295_IM.indb   3

22/1/2556   16:12:17

Содержание AOYG30LETL

Страница 1: ...vicio autorizado MANUALE DI INSTALLAZIONE UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Apenas para pessoal de assistência autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU DIŞ ÜNİTE Yalnızca...

Страница 2: ...r purging Use a vacuum pump for R410A exclusively Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit Use a clean gauge manifold and charging hose for R410A exclusively During the pump down operation make sure that the compressor is turned off before you remove the refrigerant piping Do not remove the connection pipe while the compressor is in operation wit...

Страница 3: ...leak occurs during operation immediately vacate the premises and thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas The basic installation work procedures are the same as conventional refrigerant models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 mo...

Страница 4: ... place Since the drain water flows out of the outdoor unit during heating operation install the drain pipe and connect it to a commercial 16 mm hose Reverse cycle model only When installing the drain pipe plug all the holes other than the drain pipe mounting hole in the bottom of the outdoor unit with putty so there is no water leakage Reverse cycle model only Drain pipe mounting hole Base Drain p...

Страница 5: ...the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space for installing the connection pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commercially ...

Страница 6: ...rect operation cannot be guaranteed 5 2 1 Flaring Use special pipe cutter and flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that the cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the...

Страница 7: ...essure has not decreased When the outdoor air temperature changes 5 C the test pressure changes 0 05 MPa If the pressure has dropped the pipe joints may be leaking If a leak is found immediately repair it and perform the sealing test again After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly 5 4 Vacuum process CAUTION Perform a refrigerant lea...

Страница 8: ...mmediately after the power supply has been turned off Electrical shock may occur After turning off the power always wait 5 minutes or more before touching electrical components Use a dedicated power supply circuit Insufficient power capacity in the electrical circuit or improper wiring may cause electric shock or fire Be sure to install a breaker of the specified capacity When selecting breaker pl...

Страница 9: ... power supply wiring for the outdoor unit If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease When the electrical switchboard is installed outdoors place it under lock and key so that it is not easily accessible Start wiring work after closing branch switch and over current breaker Transmission cable between indoor unit and outdoor unit is...

Страница 10: ...wn in the figure Fill in a gap at the entrance of the cables with insulation seal Cable clip Power supply cable and connection cable Insulation Seal CAUTION Fix cables so that cables do not make contact with the pipes especially on high pressure side Do not make power supply cable and connection cable come in contact with valve Gas Power supply cable and connection cable Valve Gas Gap 6 Put the se...

Страница 11: ...switch is pressed while the compressor is in operation PUMP DOWN operation starts automatically When the switch is pressed while the compressor is in stop the compressor starts to operate automatically and then move on to PUMP DOWN operation 2 PUMP DOWN operation continues for a bout 1 minute When PUMP DOWN operation is completed the compressor stops automatically Then close the 2 way valve and 3 ...

Отзывы: