5.5. Test run

1.  Make a TEST RUN in accordance with installation instruction sheet for the 

indoor unit.

CHECK ITEMS

INDOOR UNIT

(1)  Is operation of each button on the remote control unit normal?
(2)  Does each lamp light normally?
(3)  Do the air flow-direction louver operate normally?
(4)  Is the drain normal?
(5)  Is there any abnormal noise and vibration during operation? 

OUTDOOR UNIT

(1)  Is there any abnormal noise and vibration during operation?

(2)  Will noise, wind, or drain water from the unit disturb the neighbors?
(3)  Is there any gas leakage?
•  Do not operate the air conditioner in the test running state for a long time.
•  For the operation method, refer to the operating manual and perform operation check.

6. PUMP DOWN

6.1. Pump down

PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, 
recover refrigerant by doing the cooling operation or forced cooling operation according 
to the following procedure. (When the cooling operation cannot start in winter, and so on, 
start the forced cooling operation.).
(1)  Do the air purging of the charge hose by connecting the charging hose of gauge mani-

fold to the charging port of 3 way valve and opening the low-pressure valve slightly.

(2)  Close the valve stem of 2 way valve completely.
(3)  Start the cooling operation or following forced cooling operation. Keep on pressing the 

MANUAL AUTO button of the indoor unit for more than 10 seconds. The operation in-
dicator lamp and timer indicator lamp will begin to flash simultaneously during test run. 
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on 
pressing for more than 10 seconds.)

(4)  Close the valve stem of 3 way valve when the reading on the compound pressure 

gage becomes 0.05~0 Mpa (0.5~0 kg/cm

2

).

(5)  Stop the operation.

• Press the START/STOP button of the remote control unit to stop the operation.
•  Press the MANUAL AUTO button when stopping the operation from indoor unit side. (It 

is not necessary to press on keeping for more than 10 seconds.)

 CAUTION

During the pump-down operation, make sure that the compressor is turned off before 
you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2 way or 
3 way valve open. This may cause abnormal pressure in the refrigeration cycle that 
leads to breakage and even injury.

9377863133_IM.indb   6

9377863133_IM.indb   6

11/25/2011   11:30:59 AM

11/25/2011   11:30:59 AM

Содержание AOYG12-14LBLA

Страница 1: ... INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION...

Страница 2: ... in the indoor or outdoor unit to avoid personal injury when you install or maintain the unit Do not place any other electrical products or household belongings under indoor unit or outdoor unit Dripping condensation from the unit might get them wet and may cause damage or malfunction of your property Be careful not to scratch the air conditioner when handling it After installation explain correct...

Страница 3: ...Application Installation Manual 1 This manual Drain pipe 1 For outdoor unit drain piping work Adapter assy 12 7mm 9 52mm 1 For use when connecting 12 type only 2 6 Limitation of refrigerant piping length CAUTION The total maximum pipe lengths and height difference of this product are shown in the table If the units are further apart than this correct operation cannot be guaranteed Pipe length Maxi...

Страница 4: ...imals may live It may cause failure smoke or fire if small ani mals enter and touch internal electrical parts Area where animals may urinate on the unit or ammonia may be generated 1 If possible do not install the unit where it will be exposed to direct sunlight If necessary Install a blind that does not interfere with the air flow 2 Do not install the unit where a strong wind blows or where it is...

Страница 5: ...nnect them securely and fasten them so that there is 3 no stress placed on the terminals Use an appropriate screwdriver to tighten the terminal screws Do not use a 4 screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened Do not tighten the terminal screws too much otherwise the screws may break 5 See the table below for the termi...

Страница 6: ...efrigerant must not be discharged into atmosphere After connecting the piping check the joints for gas leakage with gas leak detector Gas leak checks are performed using either vacuum or nitrogen gas so select the proper one depending on the situation Checking gas leaks with vacuum 1 Check if the piping connections are secure 2 Remove the cap of 3 way valve and connect the gauge manifold charge ho...

Страница 7: ...he air purging of the charge hose by connecting the charging hose of gauge mani fold to the charging port of 3 way valve and opening the low pressure valve slightly 2 Close the valve stem of 2 way valve completely 3 Start the cooling operation or following forced cooling operation Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds The operation in dicator lamp and ...

Отзывы: