1-3. Dry operation
The compressor rotation frequency shall change according to the temperature, set temperature, and
room temperature variation which the room temperature sensor of the indoor unit has detected as
shown in the table below.
Zone is defined by set temperature and room temperature.
•
Compressor frequency range
Unit: rps
Model name
Outdoor temperature zone
Operating frequency
ASYG09KHCA
ASYG12KHCA
X zone
18
J zone
12
Y zone
0
ASYG14KHCA
X zone
20
J zone
12
Y zone
0
•
Compressor control based on room temperature
Ts+0.5°C
Ts -1.5
°C
Ts-0.5
°C
Ts+1.5
°C
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
1-4. Compressor frequency at normal start-up
¢
Models: AOYG09KHCAN, AOYG12KHCAN, and AOYG14KHCAN
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Time 1
Time 2
Time 3
Time 4
Time 5
Frequency (rps)
I
II
III
IV
V
40
56
77
90
99
Time (sec)
1
2
3
4
5
60
240
280
360
400
1-3. Dry operation
- (04-4) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOYG09KHCAN
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 01 27 SR_CH01_AS032EF_01 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 27 SR_CH02_AS032EF_01 ...
Страница 35: ...3 TROUBLESHOOTING 2020 03 19 SR_CH03_AS032EF_01 ...
Страница 82: ...5 2 Outdoor unit 03 46 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 83: ...4 CONTROL AND FUNCTIONS 2020 04 07 SR_CH04_AS032EF_01 ...
Страница 117: ...5 FILED WORKING 2020 04 07 SR_CH05_AS032EF_01 ...