4-3. Swing operation
• To select vertical airflow swing operation
When the swing signal is received, the vertical airflow direction louver starts to swing.
– Swinging range
• Cooling mode/dry mode/fan mode (1 to 5): 1 ↔ 5
• Heating mode/fan mode (6 to 8): 5 ↔ 8 (assist louver works with the vertical airflow direction
louver notch)
– When the indoor fan is S-LOW or stop mode, the swing operation is interrupted and it stops at
either upper end or bottom end.
4-3. Swing operation
- (04-16) -
4. Louver control