En-2

2.4. Electric requirement

•  Electric wire size and fuse capacity:

MODEL

7,000 ~ 12,000 BTU class

Power supply cord (mm

2

)

1.5

Connection cord (mm

2

)

1.5 or 1

Fuse capacity (A)

15

• Use conformed cable with Type245 IEC57.
• Install all electrical works in accordance to the national standard.
•  Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the 

units. (Both indoor unit and outdoor unit)

• Install the circuit breaker nearby the units.

2.5. Accessories

Drain pipe

1

2.6. Additional charge

Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
For the additional amount, see the table below.

Pipe length

15 m

20 m

Rate

Additional refrigerant

None

+100 g

20 g/m

 CAUTION

When adding refrigerant, add the refrigerant from the charging port at the completion 
of work.

The maximum length of the piping is 20 m. If the units are further apart than this, correct 
operation can not be guaranteed.

Between 15 m and 20 m, when using a connection pipe other than that in the table, charge 
additional refrigerant with 20 g/1 m as the criteria.

3. SELECTING THE MOUNTING POSITION

•  Decide the mounting position with the customer as follows:

Do not set to a place where there is oily smoke, oil is used in the factory, the unit can
contact sea breeze, sul

¿

 de gases will be generated in the hot spring area, corrosive

gases will be generated, animal may urine on the unit and ammonia will be generated
and a dusty place.

3.1. Outdoor unit

(1)  If possible, do not install the unit where it will be exposed to direct sunlight. 

(If necessary, Install a blind that does not interfere with the air 

À

 ow.)

(2)  Do not install the unit where a strong wind blows or where it is very dusty.
(3)  Do not install the unit where people pass.
(4)  Take you neighbors into consideration so that they are not disturbed by air blowing into their 

windows or by noise.

(5)  Provide the space shown in 

¿

 gure so that the air 

À

 ow is not blocked. Also for ef

¿

 cient 

operation, leave open three of the four directions front, rear, and both sides.

(6)  Install the unit where keep away more than 3m from the antenna of TV set and Radio.
(7)  Outdoor unit should be set to a place where both drainage and itself will not be 

affected when heating.

 WARNING

Install at a place that can withstand the weight of the outdoor units and install positively 
so that the units will not topple or fall.

 CAUTION

Do not install where there is the danger of combustible gas leakage.

Do not install near heat sources.

In places where the outdoor temperature drops to 0 

Û

C or lower, the drain water may 

freeze and may stop up the drain or cause other outdoor unit trouble. Therefore take 
measures so that the drain water will not freeze and clog the drain.

In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with 
snow, it might become dif

¿

 cult to get warm and it is likely to cause of the breakdown. 

Please construct a canopy and a pedestal or place the unit on a high stand (local 
con

¿

 gured).

If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

4. INSTALLATION DIAGRAM

Connection Cord

Conform to Type245 IEC57

[OUTDOOR UNIT]

10 cm or over

60 cm or over

10 cm or over

20 cm or over

25 cm or 
over

5 cm or over

INDOOR UNIT

Outdoor unit 
bottom

Drain pipe

Drain hose

•  Do not directly install it on the 

ground, otherwise it will cause 
failure.

•  To obtain better operation ef-

ficiency, when the outdoor unit 
is installed, be sure to open the 
front and left side.

45.4 cm

32 cm

 CAUTION

When the outdoor temperature is 0 

Û

C or less, do not use the accessory drain pipe 

and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may 
freeze in extreme cold weather. (Reverse cycle model only)

In the area with heavy snowfall, if the intake and outlet of outdoor units blocked with 
snow, it might become dif

¿

 cult to get warm and it is likely to cause of the breakdown. 

Please construct a canopy and a pedestal or place the unit on a high stand (local 
con

¿

 gured).

5. INSTALLATION

5.1. Outdoor unit installation

x

  Set the unit on a strong stand such as thing made of concrete blocks to minimize shock 

and vibration.

x

  Do not set the unit directly on the ground because it will cause trouble.

Switch cover A, B removal

(1) Remove the three tapping screws.
(2) Push downward the Switch cover B.
(3) Push upward the Switch cover A.

Installing the Switch cover A, B

(1)  After inserting the three hooks of Switch cover A, 

then push upward, and then tighten the two tap-
ping screws.

(2)  After inserting the three hooks of Switch cover B, 

then push upward, and then tighten the one tap-
ping screw.

 WARNING

Install the unit where it will not be tilted by more than 5°.

When installing the outdoor unit where it may exposed to strong wind, fasten it securely.

Hook

Hooks

Hooks

Switch cover A

Switch cover B

9319205007_IM_EN.indd   2

12/29/2010 9:16:49 AM

Содержание AOYG09-12LEC

Страница 1: ...h s i l g n E INSTALLATION MANUAL For authorized service personnel only INSTALLATION MANUAL 2 OUTDOOR UNIT PART NO 9319205007 ...

Страница 2: ... change in the composition of the gas and liquid phases And always charge from the liquid phase where refrigerant composition is stable 2 2 Special tools for R410A Tool name Contents of change Gauge manifold Pressure is high and cannot be measured with a conven tional R22 gauge To prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended the gauge ...

Страница 3: ...ht of the outdoor units and install positively so that the units will not topple or fall CAUTION Do not install where there is the danger of combustible gas leakage Do not install near heat sources In places where the outdoor temperature drops to 0 ÛC or lower the drain water may freeze and may stop up the drain or cause other outdoor unit trouble Therefore take measures so that the drain water wi...

Страница 4: ...curvature of 70mm or over 3 If the copper pipe is bend the pipe or pulled to often it will become stiff Do not bend the pipes more than three times at one place Tighten with two wrenches Torque wrench Wrench xed Flare nut Indoor unit pipe Connection pipe To prevent gas leakage coat the Àare surface with refrigerator oil Table 1 Flare nut size and tightening torque Flare nut Diameter mm Torque N m ...

Страница 5: ...ash slowly OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage 6 PUMP DOWN 6 1 Pump down PUMP DOWN OPERATION FORCED COOLING OPERATION To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal recover refrigerant by doing the cooling operation or for...

Отзывы: