1. SAFETY PRECAUTIONS

1.1. For authorized service personnel only

 WARNING

This mark indicates procedures which, if improperly per-

formed, might lead to the death or serious injury of the user.

For the room air conditioner to operate satisfactory, install it as outlined in this installa-
tion manual.

Connect the indoor unit and outdoor unit with the air conditioner piping and cords avail-
able standards parts. This installation manual describes the correct connections using 
the standard accessories and the parts speci

¿

 ed in this installation manual.

Have installation work done by authorized service personnel only.

Do not use an extension cord.

Do not turn on the power until all installation work is complete.

 CAUTION

This mark indicates procedures which, if improperly 

performed, might possibly result in personal harm to the user, 

or damage to property.

When installing pipes shorter than 3 m, sound of the outdoor unit will be transferred to 
the indoor unit, which will cause large operating sound or some abnormal sound.

This installation manual describes how to install the outdoor unit only. 
To install the indoor unit, refer to the installation manual included with the indoor unit.

•  Be careful not to scratch the air conditioner when handling it.
•  After installation, explain correct operation to the customer, using the operating manual.

Let the customer keep this installation manual because it is used when the air condi-
tioner is serviced or moved.

The maximum length of the piping is 20 m. The maximum height difference of the pip-
ing is 15 m, if the units are further apart than these, correct operation can not be guar-
anteed.

2. ABOUT THE UNIT

2.1. Precautions for using R410A refrigerant

The basic installation work procedures are the same as conventional refrigerant (R22) 
models.
However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of conventional refrigerant 
(R22) models, some of the piping and installation and service tools are special. (See 
the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant 
R410A model, always replace the conventional piping and flare nuts with the R410A piping 
and 

À

 are nuts.

Models that use refrigerant R410A have a different charging port thread diameter to pre-
vent erroneous charging with conventional refrigerant (R22) and for safety. Therefore, 
check beforehand. [The charging port thread diameter for R410A is 1/2 inch.]

Contents

1.

SAFETY PRECAUTIONS .......................................................................................... 1

2.

ABOUT THE UNIT ..................................................................................................... 1

3. 

SELECTING THE MOUTING POSITION .................................................................. 2

4.

INSTALLATION DIAGRAM ........................................................................................ 2

5.

INSTALLATION  ......................................................................................................... 2

6.

PUMP DOWN ............................................................................................................ 4

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 
refrigerant (R22) models. Also, when storing the piping ,securely seal the opening by 
pinching, taping, etc.

When charging the refrigerant, take into account the slight change in the composition of 
the gas and liquid phases. And always charge from the liquid phase where refrigerant 
composition is stable.

2.2. Special tools for R410A

Tool name

Contents of change

Gauge manifold

Pressure is high and cannot be measured with a conven-
tional (R22) gauge. To prevent erroneous mixing of other 
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals -0.1 to 5.3 MPa 
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.

Charge hose

To increase pressure resistance, the hose material and base 
size were changed.

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter.

Gas leakage detector

Special gas leakage detector for HFC refrigerant R410A.

Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount of residual 
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or 
discolored portion (especially on the interior surface). Otherwise, the expansion value or 
capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is neces-
sary to choose adequate materials. 
Thicknesses of copper pipes used with  R410A are as shown in Table1. Never use copper 

pipes thinner than 0.8mm even when it is available on the market.

Thicknesses of Annealed Copper Pipes

Thickness (mm)

Nominal diameter

Outer diameter (mm)

R410A

[ref.] R22

1/4 in.

6.35

0.80

0.80

3/8 in.

9.52

0.80

0.80

 WARNING

Do not use the existing (for R22) piping and 

À

 are nuts.

If the existing materials are used, the pressure inside the refrigerant cycle will rise and 
cause failure, injury, etc. (Use the special R410A materials.)

When installing and relocating the air conditioner, do not mix gases other than 
the speci

¿

 ed refrigerant (R410A) to enter the refrigerant cycle.

If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to 
an abnormally high value and cause failure, injury, etc.

2.3. Power

• The rated voltage

230V    AC  50Hz.

 WARNING

The rated voltage of this product is 230 V AC 50 Hz.

Before turning on the power, check if the voltage is within the 220 V -10 % to 240 V 
+10 % range.

Always use a special branch circuit and install a special receptacle to supply power to 
the room air conditioner.

Use a circuit breaker and receptacle matched to the capacity of the air conditioner.

Do not extend the power cable.

Perform wiring work in accordance with standards so that the air conditioner can be 
operated safely and positively.

Install a leakage circuit breaker in accordance with the related laws and regulations 
and electric company standards.

 CAUTION

The power source capacity must be the sum of the air conditioner current and the cur-
rent of other electrical appliances. When the current contracted capacity is insuf

¿

 cient, 

change the contracted capacity.
When the voltage is low and the air conditioner is dif

¿

 cult to start, contact the power 

company the voltage raised.

AIR CONDITIONER
OUTDOOR UNIT

INSTALLATION MANUAL

9319205007

9319205007_IM_EN.indd   1

12/29/2010 9:16:48 AM

Содержание AOYG09-12LEC

Страница 1: ...h s i l g n E INSTALLATION MANUAL For authorized service personnel only INSTALLATION MANUAL 2 OUTDOOR UNIT PART NO 9319205007 ...

Страница 2: ... change in the composition of the gas and liquid phases And always charge from the liquid phase where refrigerant composition is stable 2 2 Special tools for R410A Tool name Contents of change Gauge manifold Pressure is high and cannot be measured with a conven tional R22 gauge To prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended the gauge ...

Страница 3: ...ht of the outdoor units and install positively so that the units will not topple or fall CAUTION Do not install where there is the danger of combustible gas leakage Do not install near heat sources In places where the outdoor temperature drops to 0 ÛC or lower the drain water may freeze and may stop up the drain or cause other outdoor unit trouble Therefore take measures so that the drain water wi...

Страница 4: ...curvature of 70mm or over 3 If the copper pipe is bend the pipe or pulled to often it will become stiff Do not bend the pipes more than three times at one place Tighten with two wrenches Torque wrench Wrench xed Flare nut Indoor unit pipe Connection pipe To prevent gas leakage coat the Àare surface with refrigerator oil Table 1 Flare nut size and tightening torque Flare nut Diameter mm Torque N m ...

Страница 5: ...ash slowly OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage 6 PUMP DOWN 6 1 Pump down PUMP DOWN OPERATION FORCED COOLING OPERATION To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal recover refrigerant by doing the cooling operation or for...

Отзывы: