background image

AIR CONDITIONER

Wall mounted type

DESIGN & TECHNICAL MANUAL

INDOOR

ASYG07LMCE

ASYG09LMCE

ASYG12LMCE

ASYG14LMCE

OUTDOOR

AOYG07LMCE

AOYG09LMCE

AOYG12LMCE

AOYG14LMCE

DR_AS037EF_01

2016.12.05

Содержание AOYG07LMCE

Страница 1: ...AIR CONDITIONER Wall mounted type DESIGN TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016 12 05 ...

Страница 2: ...roduct specifications and design are subject to change without notice for future improvement For further details please check with our authorized dealer Copyright 2016 Fujitsu General Limited All rights reserved ...

Страница 3: ...ir velocity distributions 9 5 2 Airflow 11 6 Operation noise sound pressure 13 6 1 Noise level curve 13 6 2 Sound level check point 15 7 Safety devices 16 8 Remote controller 17 8 1 Wireless remote controller 17 9 External input and output 19 9 1 External input 19 9 2 External output 21 10 Function settings 23 10 1 Function settings by using remote controller 23 10 2 Custom code setting for wirele...

Страница 4: ...40 5 3 Model AOYG14LMCE 41 6 Capacity compensation rate for pipe length and height difference 42 6 1 Models AOYG07LMCE and AOYG09LMCE 42 6 2 Model AOYG12LMCE 43 6 3 Model AOYG14LMCE 44 7 Additional charge calculation 45 7 1 Models AOYG07LMCE and AOYG09LMCE 45 7 2 Model AOYG12LMCE 45 7 3 Model AOYG14LMCE 45 8 Airflow 46 8 1 Models AOYG07LMCE and AOYG09LMCE 46 8 2 Model AOYG12LMCE 46 8 3 Model AOYG1...

Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE ...

Страница 6: ...ow fan 1 Motor output W 30 Sound pressure level 2 Cooling HIGH dB A 43 44 MED 40 40 LOW 32 33 QUIET 21 25 Heating HIGH 43 44 MED 38 40 LOW 33 35 QUIET 22 27 Heat exchanger type Dimensions H W D mm Main 320 630 20 Sub 84 630 13 3 Fin pitch Man 1 1 Sub 1 4 Rows Stages Main 2 20 Sub 1 4 Pipe type Copper tube Fin type Aluminum Enclosure Material Polystyrene Color White Pearl white painted Approximate ...

Страница 7: ...5 C 2 5 35 C 3 4 35 C 4 0 35 C Heating Average 2 3 10 C 2 4 10 C 3 5 10 C 3 9 10 C SEER Cooling kWh kWh 6 80 7 00 7 00 6 90 SCOP Heating Average 4 10 4 10 4 00 4 00 Annual energy consumption QCE kWh a 103 125 170 203 QHE Average 786 820 1 225 1 365 Sound power level Cooling HIGH dB A 59 59 59 60 Heating 59 59 59 60 3 WALL MOUNTED ASYG07 14LMCE ...

Страница 8: ... Models ASYG07LMCE ASYG09LMCE ASYG12LMCE and ASYG14LMCE Unit mm 270 270 34 218 209 74 870 204 870 426 310 444 165 144 178 233 321 315 295 Outline of unit 65 for pipe inlet 65 for pipe inlet 4 WALL MOUNTED ASYG07 14LMCE ...

Страница 9: ...ce requirement Provide sufficient installation space for product safety Unit mm 45 or more 1 800 or more 63 or more Outline of unit 25 or more 52 or more 144 or more 1 500 or more 86 or more 5 WALL MOUNTED ASYG07 14LMCE ...

Страница 10: ...3 Wiring diagrams 3 1 Models ASYG07LMCE ASYG09LMCE ASYG12LMCE and ASYG14LMCE 6 WALL MOUNTED ASYG07 14LMCE ...

Страница 11: ... 65 2 65 1 61 0 66 2 80 1 72 0 66 40 1 76 1 22 0 63 1 96 1 23 0 64 2 03 1 33 0 64 2 16 1 34 0 65 2 23 1 44 0 65 2 36 1 44 0 66 2 50 1 53 0 66 43 1 63 1 13 0 62 1 82 1 14 0 63 1 88 1 24 0 64 2 00 1 24 0 64 2 07 1 34 0 65 2 19 1 33 0 65 2 31 1 42 0 66 Model ASYG12LMCE AFR m3 h 750 Indoor temperature CDB 18 21 23 25 27 29 32 CWB 12 15 16 18 19 21 23 Outdoor temperature CDB TC SHC IP TC SHC IP TC SHC ...

Страница 12: ... 1 13 3 90 1 15 3 80 1 17 10 8 4 76 1 19 4 65 1 21 4 53 1 24 4 42 1 26 4 31 1 29 15 10 4 53 1 09 4 42 1 12 4 31 1 14 4 20 1 16 4 10 1 18 Model ASYG12LMCE AFR m3 h 750 Indoor temperature 16 18 20 22 24 Outdoor temperature CDB CWB TC IP TC IP TC IP TC IP TC IP kW kW kW kW kW 15 16 2 94 1 54 2 87 1 57 2 80 1 60 2 73 1 63 2 66 1 66 10 11 3 73 1 60 3 64 1 63 3 55 1 67 3 46 1 70 3 37 1 73 5 7 4 40 1 62 ...

Страница 13: ... 7 8 9 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 0 2 0 1 0 1 0 0 5 0 5 3 2 1 0 1 2 3 Unit m s m m 0 1 2 3 4 5 6 7 8 9 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 1 0 0 5 3 2 1 0 Unit m s m m 0 1 2 3 4 5 6 7 8 9 Side view Vertical airflow direction louver Down Horizontal airflow direction louver C...

Страница 14: ...tion louver Up Horizontal airflow direction louver Left Right 1 0 1 0 0 5 0 5 3 2 1 0 1 2 3 Unit m s m m 0 1 2 3 4 5 6 7 8 9 2 0 2 0 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 1 0 0 5 3 2 1 0 Unit m s m m 0 1 2 3 4 5 6 7 8 9 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 1 0 0 5 3 2 1 0 Unit m s m m...

Страница 15: ... m3 h 750 l s 208 CFM 441 MED m3 h 640 l s 178 CFM 377 LOW m3 h 480 l s 133 CFM 283 QUIET m3 h 310 l s 86 CFM 182 Heating Fan speed Airflow HIGH m3 h 750 l s 208 CFM 441 MED m3 h 640 l s 178 CFM 377 LOW m3 h 520 l s 144 CFM 306 QUIET m3 h 330 l s 92 CFM 194 11 WALL MOUNTED ASYG07 14LMCE ...

Страница 16: ...M 453 MED m3 h 680 l s 189 CFM 400 LOW m3 h 530 l s 147 CFM 312 QUIET m3 h 360 l s 100 CFM 212 Heating Fan speed Airflow HIGH m3 h 770 l s 214 CFM 453 MED m3 h 680 l s 189 CFM 400 LOW m3 h 560 l s 156 CFM 330 QUIET m3 h 380 l s 106 CFM 224 12 WALL MOUNTED ASYG07 14LMCE ...

Страница 17: ... 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Model ASYG09LMCE Cooling HIGH QUIET Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating HIGH QUIET Octave band sou...

Страница 18: ...00 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Model ASYG14LMCE Cooling HIGH QUIET Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating HIGH QUIET Octave band sound pressure level dB 0 dB 0...

Страница 19: ...6 2 Sound level check point 0 8 m 1 m Microphone Microphone 15 WALL MOUNTED ASYG07 14LMCE ...

Страница 20: ...ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE Circuit protection Current fuse PCB 250 V 3 15 A Fan motor protection Thermal protector program Activate 105 10 C Fan motor stop Reset 90 10 C Fan motor restart PCB Printed Circuit Board 16 WALL MOUNTED ASYG07 14LMCE ...

Страница 21: ...TIMER button TIMER CANCEL button NOTE Functions may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator Clock and Timer indicator LOW NOISE mode indicator Transmit indicator Temperature indicator Fan speed indicator Swing indicator To facilitate explanation the accompanying illustration has been drawn to show all possible indica tors in actual o...

Страница 22: ...iew Side view 205 17 61 Size H W D mm 205 61 17 Weight g 122 without batteries Holder Unit mm 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R Size H W D mm 150 69 3 26 2 Weight g 27 18 WALL MOUNTED ASYG07 14LMCE ...

Страница 23: ...of the following on site work Unit operation is started at the following contents by adding the contact input of a commercial on off switch to a connector on the external control PCB and turning it on Unit operation Initial setting after power is on Starting mode other than initial setting Operation mode Auto changeover Mode at previous operation Set temperature 24 C Temperature at previous operat...

Страница 24: ...invalidity On Off Operation Stop Forced stop Normal Optional part Part name Model name Exterior External connect kit UTY XWZXZ5 External input wire Communication kit UTY XCBXZ2 For operating the external function the wall mounted type requires the communication kit in addition to the wire UTY XWZXZ5 20 WALL MOUNTED ASYG07 14LMCE ...

Страница 25: ...it control PCB Communication kit Connected unit Example Relay unit 1 2 Signal Relay power supply V Connector 10 m DC 24 V Make the distance from the PCB to the connected unit within 10 m Relay spec Max DC 24 V 10 mA to less than 500 mA On Off Operation Stop Indoor unit Output signal Optional part Part name Model name Exterior External connect kit UTY XWZXZ5 External output wire Communication kit U...

Страница 26: ...ctor 10 m DC 24 V Make the distance from the PCB to the connected unit within 10 m Relay spec Max DC 24 V 10 mA to less than 500 mA On Off Error Normal Error status Output signal Optional part Part name Model name Exterior External connect kit UTY XWZXZ5 External output wire Communication kit UTY XCBXZ2 For operating the external function the wall mounted type requires the communication kit in add...

Страница 27: ...e power supply of the indoor unit Entering function setting mode While pressing the POWERFUL button and TEMP button simultaneously press the RESET button to enter the function setting mode STEP 1 Setting the remote controller custom code Use the following steps to select the custom code of the remote controller Note that the air con ditioner cannot receive a custom code if the air conditioner has ...

Страница 28: ...HEAT button 2 Press the POWERFUL button to proceed the setting value To re turn the function number selection press the POWERFUL button again 3 Press the TEMP buttons to select the setting value To switch between the left and right digits press the 10 C HEAT but ton 4 Press the MODE button and START STOP button in the order listed to confirm the settings 5 Press the RESET button to cancel the func...

Страница 29: ...dication is not required select No indication 03 Function number Setting value Setting description Factory setting 11 00 Standard 400 hours 01 Long interval 1 000 hours 02 Short interval 200 hours 03 No indication 2 Room temperature sensor control for cooling Depending on the installed environment correction of the room temperature sensor may be re quired Select the appropriate control setting acc...

Страница 30: ...ng the remote controller 6 Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Function number Setting value Setting description Factory setting 44 00 A 01 B 02 C 03 D 7 External input control Operation Stop mode or Forced stop mode can be selected Function number Setting value Setting description Factory s...

Страница 31: ...pped during cooling operation Function number Setting value Setting description Factory setting 49 00 Disable 01 Enable 00 When the outdoor unit is stopped the indoor unit fan operates continuously following the set ting on the remote controller 01 When the outdoor unit is stopped the indoor unit fan operates intermittently at a very low speed 27 WALL MOUNTED ASYG07 14LMCE ...

Страница 32: ...to operate for the air conditioner 1 Press the START STOP button until only the clock is displayed on the remote controller display 2 Press the MODE button for at least 5 seconds to display the cur rent custom code Initially set to 3 Press the TEMP buttons to change the custom code be tween Match the code on the display to the air conditioner custom code Initially set to 4 Press the MODE button ag...

Страница 33: ... manual 1 Cloth tape 1 Installation manual 1 Tapping screw large M4 25 mm 5 Wall hook bracket 1 Tapping screw small M3 12 mm 2 Remote controller 1 Air cleaning filter 2 Battery 2 Filter holder 2 Remote controller holder 1 Seal A for 15 model 1 29 WALL MOUNTED ASYG07 14LMCE ...

Страница 34: ...sor Wire type Polar 3 wire Simple remote controller UTY RSNYM Compact remote controller concentrates on the basic functions such as Start Stop fan control temperature setting and operation mode Wire type Polar 3 wire NOTE Available functions may differ by the remote controller For details refer to the operation manual 12 2 Others Exterior Part name Model name Summary External connect kit UTY XWZXZ...

Страница 35: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE ...

Страница 36: ...r Beige Approximate color of MUNSELL 10YR7 5 1 0 Dimensions H W D Net mm 535 663 293 540 790 290 Gross 595 790 395 648 938 400 Weight Net kg 21 26 34 Gross 25 30 37 Connection pipe Size Liquid mm in Ø 6 35 Ø 1 4 Gas Ø 9 52 Ø 3 8 Ø 12 7 Ø 1 2 Method Flare Pre charge length m 15 Max length 20 Max height difference 15 Operation range Cooling C 10 to 43 Heating 15 to 24 Drain hose Material PP LLDPE LD...

Страница 37: ...2 Dimensions 2 1 Models AOYG07LMCE AOYG09LMCE and AOYG12LMCE Top view Unit mm Front view Side view 20 663 68 293 Drain hole 30 330 454 Pitch of bolt 103 535 15 48 352 330 33 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 38: ...2 Model AOYG14LMCE 790 290 352 68 20 10 18 Top view 540 320 209 Side view Front view Airflow 175 110 9 20 540 Drain pipe mounting place ø20 4 ø11 3mm hole Bottom view Unit mm 34 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 39: ...e obstacles at the rear and sides 100 or more 250 or more 100 or more 100 or more When there are obstacles at the front only When there are obstacles at the front and rear 600 or more 600 or more 100 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above When there are obstacles at the rear sides and above 100 or more Max 200 600 or more 600 ...

Страница 40: ...nly When there are obstacles at the front only 200 or more 1 000 or more When there are obstacles at the front and rear 200 or more 1 000 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above 1 500 or more 200 or more Max 300 36 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 41: ...N Do not install the outdoor unit in two stage where the drain water could freeze Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in ex tremely cold climate For reverse cycle m...

Страница 42: ...hR ThR ThHO ThHO ThO ThO 3 way valve Muffler Cooling Heating Thermistor Discharge temperature Thermistor Outdoor temperature Thermistor Heat exchanger out temperature Thermistor Room temperature Thermistor Pipe temperature Compressor 4 way valve Strainer Expansion valve Strainer 2 way valve 38 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 43: ...5 Wiring diagrams 5 1 Models AOYG07LMCE and AOYG09LMCE 39 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 44: ...5 2 Model AOYG12LMCE 40 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 45: ...5 3 Model AOYG14LMCE 41 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 46: ... unit 1 15 0 872 0 910 10 0 961 0 886 0 925 7 5 0 979 0 965 0 890 0 929 5 0 992 0 983 0 969 0 893 0 933 0 1 000 0 991 0 976 0 901 0 940 Indoor unit is lower than outdoor unit 2 5 1 000 0 991 0 976 0 901 0 940 7 5 0 991 0 976 0 901 0 940 10 0 976 0 901 0 940 15 0 901 0 940 HEATING Pipe length m 5 7 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 832 0 822 10 0 917 0 ...

Страница 47: ...Indoor unit is lower than outdoor unit 2 5 1 000 0 972 0 944 0 887 0 896 7 5 0 972 0 944 0 887 0 896 10 0 944 0 887 0 896 15 0 887 0 896 HEATING Pipe length m 5 7 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 896 0 879 10 0 968 0 890 0 879 7 5 0 994 0 968 0 896 0 879 5 1 000 0 994 0 968 0 896 0 879 0 1 000 0 994 0 968 0 896 0 879 Indoor unit is lower than outdoor ...

Страница 48: ...Indoor unit is lower than outdoor unit 2 5 1 000 0 987 0 970 0 923 0 939 7 5 0 987 0 970 0 923 0 939 10 0 970 0 923 0 939 15 0 923 0 939 HEATING Pipe length m 5 7 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 956 0 938 10 1 004 0 956 0 938 7 5 1 013 1 004 0 956 0 938 5 1 000 1 013 1 004 0 956 0 938 0 1 000 1 013 1 004 0 956 0 938 Indoor unit is lower than outdoor ...

Страница 49: ...g m Additional charge g 0 100 7 2 Model AOYG12LMCE Refrigerant type R410A Refrigerant amount g 850 Refrigerant charge Total pipe length m 15 or less 20 Max 20 g m Additional charge g 0 100 7 3 Model AOYG14LMCE Refrigerant type R410A Refrigerant amount g 1 050 Refrigerant charge Total pipe length m 15 or less 20 Max 20 g m Additional charge g 0 100 45 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 50: ...l s 464 CFM 983 Heating m3 h 1 470 l s 408 CFM 865 8 2 Model AOYG12LMCE Cooling m3 h 1 830 l s 508 CFM 1 077 Heating m3 h 1 600 l s 444 CFM 942 8 3 Model AOYG14LMCE Cooling m3 h 1 940 l s 539 CFM 1 142 Heating m3 h 1 700 l s 472 CFM 1 001 46 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 51: ...C 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz Model AOYG09LMCE Cooling 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz Heating 80 70 60 50 40 30 20 10 0 63 125 250 ...

Страница 52: ...5 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz Model AOYG14LMCE Cooling 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz Heating 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000...

Страница 53: ...evel check point 1 m Microphone Microphone Rear Airflow Rear view Side view NOTE Detailed shape of the actual outdoor unit might be slightly different from the one illustrat ed above 49 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 54: ... cable 3 mm2 1 5 Limited wiring length m 21 1 Maximum current is the total current of the indoor unit and the outdoor unit 2 Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 As the regulations of wire size and circuit breaker differ in each country or region select appropri ate devices complied to the regional standard 3 Limit voltage drop to less than 2 If volta...

Страница 55: ...50 V 3 15 A 250 V 5 A Fan motor protection Terminal protection program Activate 100 15 C Fan motor stop 150 15 C Fan motor stop Reset 95 10 C Fan motor restart 120 15 C Fan motor restart Compressor protection Terminal protection program Discharge temp Activate 110 C Compressor stop Reset After 7 minutes Compressor restart 51 OUTDOOR UNIT AOYG07 14LMCE ...

Страница 56: ...12 Accessories Part name Exterior Q ty Part name Exterior Q ty Installation manual 1 Drain pipe 1 52 OUTDOOR UNIT AOYG07 14LMCE ...