2-11. Safety devices
Type of protection
Protection form
Model
AOYG07KETA
AOYG09KETA
Circuit protection
Current fuse (Main PCB)
250 V, 20 A
250 V, 5 A
Fan motor
protection
Terminal protection
program
Activate
85—122 °C
Fan motor stop
Reset
77—114 °C
Fan motor restart
Compressor
protection
Terminal protection
program
(Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
Type of protection
Protection form
Model
AOYG12KETA
AOYG14KETA
Circuit protection
Current fuse (Main PCB)
250 V, 20 A
250 V, 5 A
Fan motor
protection
Terminal protection
program
Activate
85—122 °C
Fan motor stop
Reset
77—114 °C
Fan motor restart
Compressor
protection
Terminal protection
program
(Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
- 62 -
2-11. Safety devices
OUTDOOR UNIT
AOYG07-14KETA
OUTDOOR UNIT
AOYG07-14KETA