En-3

2.3. Additional charge

Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
For the additional amount, see the table below.

Pipe length

15 m

20 m

Rate

Additional refrigerant

None

+100 g

20 g/m

 CAUTION

When adding refrigerant, add the refrigerant from the charging port at the completion 
of work.

The maximum length of the piping is 20 m. If the units are further apart than this, correct 
operation can not be guaranteed.

Between 15 m and 20 m, when using a connection pipe other than that in the table, charge 
additional refrigerant with 20 g/1 m as the criteria.

2.4. Electrical requirements

The rated voltage of this product is      

230 V    AC  50 Hz.

 WARNING

Before turning on the power, check if the voltage is within the 220 V -10 % to 240 V 
+10 % range.

Always use a special branch circuit and install a special receptacle to supply power to 
the room air conditioner.

Use a circuit breaker and receptacle matched to the capacity of the air conditioner.

Do not extend the power cable.

Perform wiring work in accordance with standards so that the air conditioner can be 
operated safely and positively.

Install a leakage circuit breaker in accordance with the related laws and regulations 
and electric company standards.

Always use a separate power supply line protected by a circuit breaker operating on all 
wires with a distance between contact of 3 mm for this unit.

 CAUTION

The power source capacity must be the sum of the air conditioner current and the cur-
rent of other electrical appliances. When the current contracted capacity is insuf

fi

 cient, 

change the contracted capacity.

When the voltage is low and the air conditioner is dif

fi

 cult to start, contact the power 

company the voltage raised.

Electric wire size and fuse capacity for each model are as follows:

Indoor unit capacity [Btu/h class] 

9,000

12,000

14,000

Power supply cable [mm

2

]

1.5

1.5

MAX.

4.0

MIN.

3.5

Connection cable [mm

2

] 1.5

1.5

1.5

Fuse capacity [A]

15

15

20

• Use conformed cable with Type 60245 IEC 57.
• Install all electrical works in accordance to the national standard.
• Install the circuit breaker nearby the units.

3.  SELECTING AN INSTALLATION LOCATION

With considering written conditions below, select an appropriate installing location in con-
sultation with the customer.

 WARNING

Securely install the outdoor unit at a location that can withstand the weight of the unit. 
Otherwise, the outdoor unit may fall and cause injury.

Be sure to install the outdoor unit as prescribed, so that it can withstand earthquakes 
or strong winds. Improper installation can cause the unit to topple or fall, or other 
accidents.

 CAUTION

Do not install the outdoor unit in the following areas:

• Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

• Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam. It will 

deteriorate plastic parts, causing the parts to fail or the unit to leak water.

• Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to 
corrode, which can cause refrigerant leakage.

• Area containing equipment that generates electromagnetic interference. It will cause 

the control system to malfunction, preventing the unit from operating normally.

• Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable dust, or volatile in

fl

 ammables such as paint thinner or gasoline. If gas leaks 

and settles around the unit, it can cause a 

fi

 re.

• Area that has heat sources, vapors, or the risk of the leakage of 

fl

 ammable gas in the 

vicinity.

• Area where small animals may live. It may cause failure, smoke or 

fi

 re if small ani-

mals enter and touch internal electrical parts.

• Area where animals may urinate on the unit or ammonia may be generated.

In places where the outdoor temperature drops to 0 

˚

C or lower, the drain water may 

freeze and may stop up the drain or cause other outdoor unit trouble. Therefore take 
measures so that the drain water will not freeze and clog the drain.

Set up the outdoor unit in a high place, and do not arrange the frame of installed stand 
under the drain port. Because the water dropped from the drain port repeats freezing 
and accumulating, and may block the drain port.

In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with 
snow, it might become dif

fi

 cult to get warm and it is likely to cause of the break-down. 

Construct a canopy or baf

fl

 e board.

If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

(1) If possible, do not install the unit where it will be exposed to direct sunlight. 

(If necessary, Install a blind that does not interfere with the air 

fl

 ow.)

(2)  Do not install the unit where a strong wind blows or where it is very dusty.
(3)  Do not install the unit where people pass.
(4)  Take you neighbors into consideration so that they are not disturbed by air blowing into their 

windows or by noise.

(5)  Provide the space shown in 

fi

 gure so that the air 

fl

 ow is not blocked. Also for ef

fi

 cient 

operation, leave open three of the four directions front, rear, and both sides.

(6)  Install the unit where keep away more than 3m from the antenna of TV set and Radio.
(7)  Outdoor unit should be set to a place where both drainage and itself will not be 

affected when heating.

(8)  Set up the unit in the place where has no in

fl

 uence on dropping the drain water from 

the outdoor unit.

[OUTDOOR UNIT]

10 cm or over

60 cm or over

10 cm or over

20 cm or over

25 cm or 
over

INDOOR UNIT

• Do not directly install it on the ground, 

otherwise it will cause failure.

• To obtain better operation efficiency, 

when the outdoor unit is installed, be 
sure to open the front and left side.

54 cm

32 cm

9319205106_IM.indb   3

9319205106_IM.indb   3

9/6/2011   10:14:39 AM

9/6/2011   10:14:39 AM

Содержание AOYG-09LTC

Страница 1: ...IKKÖ jaettu UTENDØRSENHET Delt utgave For authorized service personnel only Kun til autoriseret servicepersonale Vain valtuutetuille huoltohenkilöille Kun for autorisert servicepersonell Swedish INSTALLATIONSHANDBOK UTOMHUSENHET Split typ Endast för auktoriserad servicepersonal Polish INSTRUKCJA MONTAŻU URZĄDZENIE ZEWNĘTRZNE typu split Do użytku wyłącznie przez autoryzowany personel obsługi techni...

Страница 2: ...s for using R410A refrigerant The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools are special See the table below Especially when replacing a conventional re...

Страница 3: ...rts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause r...

Страница 4: ...r cover 2 Bend the end of the cable as shown in the figure 3 Connect the end of the connection cable fully into the terminal block 4 Fasten the sheath with a cable clamp 5 Install the connector cover Cable clamp Connection cable N L 3 2 1 1 2 3 4 Outdoor unit terminal block Indoor unit terminal block Connection cable Earth screw Earth screw Power supply cable N L 3 2 1 25mm 12mm 5mm 5mm 12mm 20mm ...

Страница 5: ...lowly loosen the valve stem of the 3 way valve When the compound pressure gauge reading reaches 0 1 0 2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnect ed it may be difficult to disconnect the charge hose 10 Fully open the valve stems of the 2 way valve and 3 way valve...

Отзывы: