11. Safety devices
Type of protection
Protection form
Model
AOYA09KLWA and AOYA12KLWA
Circuit protection
Current fuse (Main PCB)
250 V, 20 A
Fan motor protection
Terminal protection program
Activate
1 A
Fan motor stop
Reset
After 3 minutes
Fan motor restart
Compressor protection
Terminal protection program
(Current)
Activate
18 A
Compressor stop
Reset
After 3 minutes
Compressor restart
Terminal protection program
(Discharge temp.)
Activate
115 °C
Compressor stop
Reset
90 °C
Compressor restart
- 32 -
11. Safety devices
OUTDOOR UNIT
AOYA09-12KLWA
OUTDOOR UNIT
AOYA09-12KLWA