6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Models: AOYA09KLWA and AOYA12KLWA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
10
20
25
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
10
—
0.973
0.948
0.936
5
0.995
0.983
0.958
0.945
0
1.000
0.988
0.963
0.950
Indoor unit is lower than
outdoor unit *2
-5
1.000
0.988
0.963
0.950
-10
—
0.988
0.963
0.950
HEATING
Pipe length (m)
5
10
20
25
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
10
—
0.993
0.978
0.970
5
1.000
0.993
0.978
0.970
0
1.000
0.993
0.978
0.970
Indoor unit is lower than
outdoor unit *2
-5
0.992
0.985
0.970
0.962
-10
—
0.977
0.962
0.955
- 26 -
6-1. Models: AOYA09KLWA and AOYA12KLWA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYA09-12KLWA
OUTDOOR UNIT
AOYA09-12KLWA