•
Operation status
On
On
12 V
Off
Off
0 V
Heater
Fan
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
Heat pump
prohibition
zone
Combination zone
* The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
46.4°F (8°C)
42.8°F (6°C)
-0.4°F (-18°C)
-4°F (-20°C)
NOTE:
In following operations, compressor will be on in heat pump prohibition zone.
• Other than heating
• Test run
2-4. Details of function
- (05-29) -
2. External input and output
FIELD
WORKING
FIELD
WORKING
Содержание AOUH18LPAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS051EF_02 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2021 07 04 SR_CH02_AS051EF_01 ...
Страница 33: ...3 TROUBLESHOOTING 2021 08 04 SR_CH03_AS051EF_01 ...
Страница 36: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2021 08 04 SR_CH04_AS051EF_01 ...
Страница 129: ...5 FILED WORKING 2021 08 04 SR_CH05_AS051EF_01 ...