background image

3

Cooling/Dry Mode

Heating Mode

Outdoor temperature

About 14 to 115 °F

About 5 to 75 °F

PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation or 
forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced 
cooling operation.)

(1)  Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening 

the low-pressure valve slightly.

(2)  Close the valve stem of 2 way valve completely.
(3)  Start the cooling operation or following forced cooling operation.
 

Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.

 

The operation indicator lamp and timer indicator lamp will begin to fl ash simultaneously during test run.

 

(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)

(4)  Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 MPa (7.25~0 psi).
(5)  Stop the operation.
 

• Press the START/STOP button of the remote control unit to stop the operation.

 

• Press the MANUAL AUTO button when stopping the operation from indoor unit side.

 

  (It is not necessary to press on keeping for more than 10 seconds.)

 

CAUTION

During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal 
pressure in the refrigeration cycle that leads to breakage and even injury.

OPERATING RANGE

 (1)  Match the terminal block numbers and connection cord 

colors with those of the indoor unit.

   

Erroneous wiring may cause burning of the electric 
parts.

  (2)  Connect the connection cords fi rmly to the terminal block. 

Imperfect installation may cause a fi re.

 (3)  Always fasten the outside covering of the connection 

cord with the cord clamp. (If the insulator is chafed, 
electric leakage may occur.)

  (4)  Securely earth the power cord.

 (5)  Do not use the earth screw for an external connector. 

Only use for interconnection between two units.

 

CAUTION

(1)  Remove the screws, then remove the control box cover.
(2)  Fasten the Inter-unit wire harness and power supply to the conduit holder using the lock nut.
(3)  Connect inter-unit wire harness and power supply to the terminal.
(4)  Use the screws to install the control box cover.

 

WARNING

Be sure to comply with local codes while running the wire from the in-
door unit to the outdoor unit (size of wire and wiring method, etc.).

Every wire must be connected fi rmly.

No wire should be allowed to touch refrigerant tubing, the compres-
sor or any moving part.

Loose wiring may cause the terminal to overheat or result in unit 
malfunction. A fi re hazard may also exist. Therefore, be sure all wiring 
is tightly connected. 

Connect wires to the matching numbers of terminals.

NOTE:

• 

Connector trade size for this unit is 1/2”(12.7 mm). The con-
nector can be bought at a hard ware store. Refer to “How 
to connect wiring to the terminals“ for instructions on con-
necting depending on the wire type you are using.

• 

The fuse located in the outdoor unit provides power supply 
protection and may blow when power is applied if the system 
has been in correctly wired.

Lock nut

Inter-unit wire 
harness

Control box cover

Power supply

Inter-unit wire 
hamess

1

2

1

2

3

L1

L2

G

G

3

Earth 
Screw

Connection cord

terminal block

Earth Screw

Power supply line

G

1

G

3

2

1

2

3

L2

L1

Indoor unit

Terminal

Terminal

PO

WER SUPPL

Y

Single-prase, 208/230V

Grounding line

Outdoor unit

Control line

208/230 V

208/230 V

208/230 V

(Inter Unit)
Power line

DISCONNECT 

SWITCH (FIELD 

SUPPLY)

OUTDOOR UNIT WIRING

CONNECTION

(1)  Install the outdoor unit wall cap (supplied with the optional installation set 

or procured at the site) to the wall pipe.

(2)  Connect the outdoor unit and indoor unit piping.
(3)  After matching the center of the fl are surface and tightening the nut hand 

tight, tighten the nut to the specifi ed tightening torque with a torque wrench.

(Table 1)

FLARING

(1)  Cut the connection pipe to the necessary 

length with a pipe cutter.

(2)  Hold the pipe downward so that cuttings will 

not enter the pipe and remove the burrs.

(3)  Insert the fl are nut onto the pipe and fl are 

the pipe with a fl aring tool.

Insert the fl are nut (always use the fl are  nut 
attached to the indoor and outdoor units re-
spectively) onto the pipe and perform the fl are 
processing with a fl are tool.
Use the special R410A  fl are tool, or the conv-
entional (for R22) fl are tool.
When using the conventional fl are tool, always 
use an allowance adjustment gauge and secure 
the A dimension shown in table 2 .

BENDING PIPES

(1)  When bending the pipe, be careful not to crush it.
(2)  To prevent breaking of the pipe, avoid sharp bends.
 

Bend the pipe with a radius of curvature of 2-13/16° (70mm) or 
over.

(3)  If the copper pipe is bend the pipe or pulled to often, it will become stiff. 

Do not bend the pipes more than three times at one place.

CONNECTING THE  PIPING

Check if [L] is fl ared uniformly 
and is not cracked or scratched.

Die

A

Pipe

Tighten with two wrenches.

Torque 
wrench

Wrench (fi xed)

Flare nut

Indoor unit pipe

Connection pipe

To prevent gas leakage, coat the fl are 
surface with refrigerator oil.

  1. 

Check if the piping connections are secure.

  2. 

Check that the stems of 2-way valve and 3-way valve are closed fully.

  3.  Connect the gauge manifold charge hose to the charging port of the 

3-way valve (side with the projection for pushing in the valve core).

  4.  Open the low pressure side valve of the gauge manifold fully.

  5.  Operate the vacuum pump and start pump down.

  6.  Slowly loosen the fl are nut of the 3-way valve and check if air enters, 

then retighten the fl are nut.

   

(When the fl are nut is loosened the operating sound of the vacuum 
pump changes and the reading of the compound pressure gauge goes 
from minus to zero.)

AIR PURGE

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the 
outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and do 
not operate it during the following work.

  7. 

Pump down the system for at least 15 minutes, then check if the compound 
pressure gauge reads -0.1 MPa (30 in.Hg ).

  8. 

At the end of pump down, close the low pressure side gauge of the gauge 
manifold fully and stop the vacuum pump.

 9.  Slowly loosen the valve stem of the 3-way valve. When the compound pres-

sure gauge reading reaches 0.1-0.2 MPa (14.5~28.9 psi), retighten the valve 
stem and disconnect the charge hose from the 3-way valve charging port.

   

(If the stem of the 3-way valve is opened fully before the charge hose 
is disconnected, it may be diffi cult to disconnect the charge hose.)

  10.  Fully open the valve stems of the 2-way valve and 3-way valve using a hexagon 

wrench. (After the valve stem begins to turn, turn it with a torque of less than 
2.9 N • m (30 kgf • cm) until it stops turning.)

  11.  Firmly tighten the 2-way valve and 3-way valve blank cap and the charg-

ing port cap.

 

CAUTION

 

(1)  Refrigerant must not be discharged into atmosphere.

 (2)  After connecting the piping , check the joints for gas 

leakage with gas leak detector. 

Additional charge

Refrigerant suitable for a piping length of 49 ft (15 m) is charged in the 
outdoor unit at the factory.
When the piping is longer than 49 ft (15 m), additional charging is necessary.
For the additional amount, see the table below.

Pipe length

 Additional 

refrigerant

49 ft (15 m)

None

66 ft (20 m)

+3.5 oz (+100 g)

 

 

Tightening torque [N·m (lbt·ft)]

Blank cap                                          20 to 25 (14.8 to 18.4)

Charging port cap                               10 to 12 (7.4 to 8.8)

 

CAUTION

 

(1)  When adding refrigerant, add the refrigerant from the 

charging port at the completion of work.

  (2)  The maximum length of the piping is 66 ft (20 m). If 

the units are further apart than this, correct operation 
can not be guaranteed.

Between 49 ft (15 m) and 66 ft (20 m), when using a connection pipe other than that 
in the table, charge additional refrigerant with 0.2 oz/ft (20 g/m) as the criteria.

Table 1 Flare nut tightening torque

Table 2 Pipe outside diameter

Flare nut

  1/4” (6.35  mm) dia.

  3/8” (9.52  mm) dia.

A [in (mm)]

Pipe outside

diameter

1/4” (6.35 mm)

3/8” (9.52 mm)

Flare tool for

R410A, clutch type

0 to 1/32 (0 to 0.5)

0 to 1/32 (0 to 0.5)

Conventional (R22) fl are tool

Clutch type

1/32 to 2/32 (0.5 to 1.5)

1/32 to 2/32 (0.5 to 1.5)

Wing nut type

2/32 to 3/32 (1.5 to 2.0)

2/32 to 3/32 (1.5 to 2.0)

 

CAUTION

(1) Fasten a fl are nut with a torque wrench as instructed in this manual. If 

fastened too tight, the fl are nut may be broken after a long period of time 
and cause a leakage of refrigerant.

(2) During installation, make sure that the refrigerant pipe is attached fi rmly 

before you run the compressor. Do not operate the compressor under the 
condition of refrigerant piping not attached properly with 2-way or 3-way 
valve open. This may cause abnormal pressure in the refrigeration cycle 
that leads to breakage and even injury.

Tightening torque [N·m (lbt·ft)]

 

16 to 18 (11.8 to 13.3)

 

32 to 42 (23.6 to 31.0)

Rate

0.2 oz/ft (20 g/m)

3-way valve  2-way valve 

Compound pressure gauge

-0.1 MPa 
(30 in.Hg )

Gauge manifold

Pressure gauge

High 
pressure 
side valve 
(closod)

Charge 
hose

Vacuum pump

Flare nut

Low prossure 
side valve

Valve stem

Blank cap

Charge hose

Charging port

Charging port cap

9379069052-03_IM_EN.indd   2

9379069052-03_IM_EN.indd   2

1/28/2011   2:58:40 PM

1/28/2011   2:58:40 PM

Содержание AOU9RLF

Страница 1: ...ghtly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air con ditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wa...

Страница 2: ...and The charging port thread diameter for R410A is 1 2 threads per inch 3 Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc 4 When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from ...

Страница 3: ...erant cycle the pressure inside the cycle will rise to an abnormally high value and cause breakage injury etc WARNING For authorized service personnel only 1 For the room air conditioner to operate satisfactory install it as outlined in this installation manual 2 Connect the indoor unit and outdoor unit with the air conditioner piping and cords available standards parts This installation manual de...

Страница 4: ...wing into their windows or by noise 5 Provide the space shown in the figure so that the air flow is not blocked Also for efficient operation leave open three of the four directions front rear and both sides WARNING Install at a place that can withstand the weight of the outdoor units and install positively so that the units will not topple or fall SELECTING THE MOUNTING POSITION CAUTION 1 Do not i...

Страница 5: ...s with those of the indoor unit Erroneous wiring may cause burning of the electric parts 2 Connecttheconnectioncordsfirmlytotheterminalblock Imperfect installation may cause a fire 3 Always fasten the outside covering of the connection cord with the cord clamp If the insulator is chafed electric leakage may occur 4 Securely earth the power cord 5 Do not use the earth screw for an external connecto...

Страница 6: ...y loosen the valve stem of the 3 way valve When the compound pres sure gauge reading reaches 0 1 0 2 MPa 14 5 28 9 psi retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnected it may be difficult to disconnect the charge hose 10 Fully open the valve stems of the 2 way valve and 3...

Отзывы: