25. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
When the discharge temperature becomes higher than Temperature , the compressor frequency
is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the protection control of the
compressor frequency will be released.
When the discharge temperature becomes higher than Temperature , the compressor is stopped
and the indoor unit LED starts blinking.
219.2°F
(104°C)
213.8°F
(101°C)
230°F
(110°C)
( Table 22 : Discharge temperature over rise prevension control / Release temperature )
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceed
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
( Table 23 : Current release operation value / Release value )
AOU18RLB
AOU24RLB
AOU18RLB
AOU24RLB
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
OT (Control / Release)
OT : Outdoor Temperature
OT (Control / Release)
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
OT (Control / Release)
4.5A / 4.0A
6.0A / 5.5A
11.0A / 10.5A
114.8°F
(46°C)
104°F
(40°C)
OT : Outdoor Temperature
OT (Control / Release)
7.0A / 6.5A
9.0A / 8.5A
11.0A / 10.5A
13.0A / 12.5A
62.6°F
(17°C)
53.6°F
(12°C)
41°F
(5°C)
4.5A / 4.0A
6.0A / 5.5A
7.5A / 7.0A
114.8°F
(46°C)
104°F
(40°C)
7.0A / 6.5A
9.0A / 8.5A
10.0A / 9.5A
11.0A / 10.5A
62.6°F
(17°C)
53.6°F
(12°C)
41°F
(5°C)
01-19
Содержание AOU18RLB
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 24: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 71: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan December 2014 Printed in Japan ...