17. COMPRESSOR PREHEATING
18. MINIMUM HEAT OPERATION
MINIMUM HEAT OPERATION performs as below when pressing MIN. HEAT button or Weekly timer
setting on the remote controller.
Mode Heating
Setting temperature 50°F(10°C)
Fan mode Auto
LED display Economy
Defrost operation Operate as normal
( Table 17 : Minimum heat operation )
19. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller.
At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation
for cooling and heating.
The ECONOMY operation is almost the same operation as below settings.
Mode
Cooling/ Dry Heating
Target temperature Setting temp.+2°F(+1°C) Setting temp.-2°F(-1°C)
( Table 18 : Economy operation )
When the outdoor heat exchanger temperature is lower than 41°F(5°C) and the all operation has
been stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor heat exchanger temperature rises
01-14
to 44.6°F(7°C) or greater, preheating is ended.
Содержание AOU18RLB
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 24: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 71: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan December 2014 Printed in Japan ...