8. COMPRESSOR CONTROL
01-08
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 11.
Cooling / Dry
Heating
Minimum
Maximum
Minimum
Maximum
AOU09RL2
AOU12RL2
18rps
80rps
18rps
120rps
96rps
AOU09RL2
AOU12RL2
AOU09RL2
AOU12RL2
56rps
67rps
75rps
(Table 11 : Compressor frequency range)
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.9.
(Fig.9 : Compressor control at start-up)
Time
Time
Time
Time
Time
(Frequency)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Time
Time
Time
Time
Time
80sec
140sec
200sec
(Time)
AOU09RL2
AOU12RL2
78rps
78rps
Frequency
Time
6
Frequency
Time
6
78rps
56rps
74rps
87rps
97rps
108rps
119rps
380sec
440sec
440sec
60sec
100sec
140sec
200sec
410sec
350sec
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.
Under
Over
Under
Over
Under
Over
45rps
27rps
35rps
23rps
30rps
-------
(Table12 : Limitation of Compressor Frequency)
AOU09RL2
AOU12RL2
10°C
(50°F)
14°C
(59°F)
40°C
(104°F)
Under
Over
Under
Over
Under
Over
Under
Over
34rps
22rps
27rps
36rps
27rps
27rps
30rps
-------
- 3°C
(26°F)
7°C
(45°F)
14°C
(59°F)
40°C
(104°F)
[ Cooling/ Dry ]
[ Heating ]
Содержание AOU09RL2
Страница 4: ......
Страница 5: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 53: ......
Страница 54: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 61: ......
Страница 62: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2012 Printed in Japan ...