- 34 -
W
A
LL
MOU
N
TED
ASTG30, 34
KMTA
2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number
Setting value
Setting description
Factory setting
11
00
Standard (400 hours)
01
Long interval (1,000 hours)
02
Short interval (200 hours)
03
No indication
♦
Function number
Setting value
Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00
Standard setting
♦
01
No correction 0.0 °C
02
-0.5 °C
More cooling
Less heating
03
-1.0 °C
04
-1.5 °C
05
-2.0 °C
06
-2.5 °C
07
-3.0 °C
08
-3.5 °C
09
-4.0 °C
10
+0.5 °C
Less cooling
More heating
11
+1.0 °C
12
+1.5 °C
13
+2.0 °C
14
+2.5 °C
15
+3.0 °C
16
+3.5 °C
17
+4.0 °C
Содержание AOTG30KMTA
Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASTG30KMTA ASTG34KMTA ...
Страница 15: ... 11 WALL MOUNTED ASTG30 34KMTA 5 Wiring diagram ...
Страница 21: ... 17 WALL MOUNTED ASTG30 34KMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Страница 44: ... 40 WALL MOUNTED ASTG30 34KMTA ...
Страница 45: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOTG30KMTA AOTG34KMTA ...
Страница 56: ... 52 OUTDOOR UNIT AOTG30 34KMTA 3 Refrigerant circuit 3 1 Model AOTG30KMTA ...
Страница 57: ... 53 OUTDOOR UNIT AOTG30 34KMTA 3 2 Model AOTG34KMTA ...
Страница 58: ... 54 OUTDOOR UNIT AOTG30 34KMTA 4 Wiring diagrams 4 1 Model AOTG30KMTA ...
Страница 59: ... 55 OUTDOOR UNIT AOTG30 34KMTA 4 2 Model AOTG34KMTA ...