4) Auto restart
Enable or disable automatic restart after a power interruption.
(
... Factory setting)
Setting description
Function number
Setting value
Enable
40
00
Disable
01
* Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external input device.
5) Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
(
... Factory setting)
Setting description
Function number
Setting value
Indoor unit
42
00
Both
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
6) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
(
... Factory setting)
Setting description
Function number
Setting value
A
44
00
B
01
C
02
D
03
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
... Factory setting)
Setting description
Function number
Setting value
Operation/Stop mode
46
00
(Setting prohibited)
01
Forced stop mode
02
8) Indoor unit fan control for energy saving for cooling
Enable or disable the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
(
... Factory setting)
Setting description
Function number
Setting value
Disable
49
00
Enable
01
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
Содержание AOTG18KMCA
Страница 2: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Страница 10: ... 01 07 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA INSTALLATION PLACE Unit mm ...
Страница 22: ... 01 19 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 33: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Страница 48: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...