CAPACITY COMPENSATION RATE FOR PIPE LENGTH
5.
AND HEIGHT DIFFERENCE
MODEL
: AOTG09KMCA
HEATING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.924
0.873
10
-
-
0.975 0.924 0.873
7.5
-
1.000 0.975 0.924 0.873
5
1.006 1.000 0.975 0.924 0.873
0
1.006 1.000 0.975 0.924 0.873
2
Indoor unit is
lower than
outdoor unit.
-5
1.001 0.995 0.970 0.919 0.869
-7.5
-
0.993 0.968 0.917 0.866
-10
-
-
0.966 0.915 0.864
-15
-
-
-
0.906 0.856
COOLING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.931 0.907
10
-
-
0.971 0.947 0.922
7.5
-
0.988 0.975 0.950 0.926
5
1.005 0.992 0.979 0.953 0.930
0
1.013 1.000 0.987 0.962 0.937
2
Indoor unit is
lower than
outdoor unit.
-5
1.013 1.000 0.987 0.962 0.937
-7.5
-
1.000 0.987 0.962 0.937
-10
-
-
0.987 0.962 0.937
-15
-
-
-
0.962 0.937
Height difference H
1: Indoor unit is higher than outdoor unit.
2: Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
Содержание AOTG09KMCA
Страница 2: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG09KMCA ASTG12KMCA DTR_AS081E_01 2013 07 19 ...
Страница 10: ... 01 07 WALL MOUNTED TYPE ASTG09 12KMCA WALL MOUNTED TYPE ASTG09 12KMCA INSTALLATION PLACE Unit mm ...
Страница 19: ... 01 16 WALL MOUNTED TYPE ASTG09 12KMCA WALL MOUNTED TYPE ASTG09 12KMCA SOUND LEVEL CHECK POINT 8 2 ...
Страница 30: ...2 OUTDOOR UNIT SINGLE TYPE AOTG09KMCA AOTG12KMCA DTR_AO143E_01 2013 07 19 ...
Страница 35: ... 02 04 OUTDOOR UNIT AOTG09 12KMCA OUTDOOR UNIT AOTG09 12KMCA WIRING DIAGRAMS 4 MODELS AOTG09KMCA AOTG12KMCA ...
Страница 41: ... 02 10 OUTDOOR UNIT AOTG09 12KMCA OUTDOOR UNIT AOTG09 12KMCA SOUND LEVEL CHECK POINT 8 2 ...