background image

11

OPERATING TIPS

Operation and Performance

*Heating Performance

*Microcomputer-controlled Automatic Defrosting

This air conditioner uses a heat pump which absorbs
heat from outside air and brings it indoors. As a result,
its heating performance is reduced as the temperature
of outside air drops. If you find that insufficient room
heat is produced, we recommend that you use the air
conditioner together with other heating appliances.

Heat-pump type air conditioners use warm-air
recirculation to warm your entire room. As a result, some
time will be required after starting operation until your
entire room becomes warm.

When the outside temperature is low and the humid-
ity high, frost will collect on the outside unit, reducing
heater efficiency. When this happens, the computer will
automatically start the defrost cycle. During the defrost
cycle, the indoor fan will shutdown and  DEFROST  will
be displayed on the remote controller. It will take any-
where from 4 to 15 minutes before the air conditioner
starts up again.

Outdoor Unit Fan Speed Control

Depending on the outdoor temperature, the outdoor unit
automatically stops the fans or adjusts their speed.

*When Indoor and Outdoor Temperatures are High

When both indoor and outdoor temperatures are high
during use of the heating mode, the outdoor unit’s fan
may stop at times.

Cooling Mode

About 0 to 52°C

About 21 to 52°C

About 0 to 52°C

About 0 to 52°C

About 18 to 32°C

About 80% or less

If the unit is used for long pe-
riods under high-humidity
conditions, condensation
may form on the surface of
the indoor unit, and drip onto
the floor or other objects un-
derneath.

*Heating Mode

About -8 to 21°C

About -5 to 21°C

About 30°C or less

Outdoor temperature

Indoor temperature

Indoor humidity

HEAT & COOL MODEL

(Reverse Cycle)

Temperature and Humidity Range

If the air conditioner is operated under higher temperature conditions than those listed, the built-in protection circuit may
operate to prevent internal circuit damage. Also, during Cooling and Dry modes, if the unit is used under conditions of
lower temperatures than those listed above, the heat-exchanger may freeze, leading to water leakage and other damage.

Do not use this unit for any purposes other than the Cooling, (*)Heating, Dehumidifying, and air-circulation of rooms in
ordinary dwellings.

Instructions relating to heating(*) are applicable only to “HEAT & COOL MODEL” (Reverse Cycle).

COOLING MODEL

ART60RL

ART36RL
ART45RL

ART60AL

ART36AL
ART45AL

Содержание AOT36AC3

Страница 1: ...5AL 3 H ART45RL 3 H ART60AL 3 ART60RL 3 Outdoor Unit AOT36AC 3 AOT36RC 3 AOT45AC 3 AOT45RC 3 AOT60AB 3 AOT60RB 3 P N9362589017 OPERATING MANUAL AIR CONDITIONER DUCT TYPE KEEP THIS OPERATION MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED ...

Страница 2: ...AFETY PRECAUTIONS 3 NAME OF PARTS 4 PREPARATION 6 OPERATION 6 TIMER OPERATION 8 ENERGY SAVE OPERATION 9 CARE AND MAINTENANCE 10 ERRORS AND SELF DIAGNOSIS 10 OPERATING TIPS 11 SYSTEM OPERATION 12 TROUBLESHOOTING 13 ...

Страница 3: ...on of the installation stand for damage Do not place animals or plants in the direct path of the air flow When restarting after a long period of disuse in the winter do Turn the power switch on at least 12 hours before starting the unit Do not drink the water drained from the air conditioner Do not use in applications involving the storage of foods plants or animals precision equipment or art work...

Страница 4: ...shows all possible displays The actual display shows only that area that is being adjusted or used NON STOP OFF ON CLOCK TEMP OFF ON ON OFF TIMER TIMER PROGRAM FAN AUTO HEAT FAN COOL DEFROST FAN HIGH FAN MED FAN LOW REPEAT TIMER MODE CLOCK ADJUST SET TIME FAN CONTROL MASTER CONTROL SET TEMP ENERGY SAVE START STOP ZONE CONTROL TEST NON STOP OFF ON CLOCK TEMP OFF ON ON OFF TIMER TIMER PROGRAM FAN AU...

Страница 5: ...OL Button 9 ZONE CONTROL Lamp ENERGY SAVE Button A ENERGY SAVE Lamp B CLOCK ADJUST Button C TIMER MODE Button D SET TIME Button E SET TEMP Button F FAN CONTROL Button G MASTER CONTROL Button H Remote Controller Display Fig 5 I Clock Display CLOCK TIMER J Set Temperature Display TEMP K Operation Mode Display L Timer Mode Display M Fan Speed Display N DEFROST Display O TEST Display ...

Страница 6: ...OFF ON CLOCK TEMP OFF ON ON OFF TIMER TIMER PROGRAM FAN AUTO HEAT FAN COOL DEFROST FAN HIGH FAN MED FAN LOW REPEAT TIMER MODE CLOCK ADJUST SET TIME FAN CONTROL MASTER CONTROL SET TEMP ENERGY SAVE START STOP ZONE CONTROL TEST Example Set the time to 9 31 Instructions relating to heating are applicable only to HEAT COOL MODEL Reverse Cycle OPERATION To Select Mode Operation 1 Press the START STOP bu...

Страница 7: ... The display contents disappear and only the current time is displayed c c c c NON STOP OFF ON CLOCK TEMP OFF ON ON OFF TIMER TIMER PROGRAM FAN AUTO HEAT FAN COOL DEFROST FAN HIGH FAN MED FAN LOW REPEAT TIMER MODE CLOCK ADJUST SET TIME FAN CONTROL MASTER CONTROL SET TEMP ENERGY SAVE START STOP ZONE CONTROL TEST Example When Set to HIGH Example When set to 26 C About Mode Operation Heating Always s...

Страница 8: ...will stop operating Each time the button is pressed the timer function changes in the follow ing order RESET OFF ON REPEAT PROGRAM OFF ON OFF ON 2 Press the SET TIME button and set the timer time Use to advance the time forward Use to turn the time back Press once to move the time 1 minute hold down and the time will move 10 minutes at a time NON STOP OFF ON CLOCK TEMP OFF ON ON OFF TIMER TIMER PR...

Страница 9: ...s To Use the ENERGY SAVE Press the ENERGY SAVE button The unit will run in the ENERGY SAVE mode NON STOP OFF ON CLOCK TEMP OFF ON ON OFF TIMER TIMER PROGRAM FAN AUTO HEAT FAN COOL DEFROST FAN HIGH FAN MED FAN LOW REPEAT TIMER MODE CLOCK ADJUST SET TIME FAN CONTROL MASTER CONTROL SET TEMP ENERGY SAVE START STOP ZONE CONTROL TEST About the ENERGY SAVE The energy conservation mode ENERGY SAVE raises ...

Страница 10: ...educed leading to reduced performance and increased operation noise Be sure to clean the filters regularly How to Cleaning Use a vacuum cleaner to remove dust and dirt from the air filter or wash in a synthetic detergent After washing dry in a shaded place then reinstall When used for extended periods the unit may accumulate dirt inside reducing its performance We recommend that the unit be inspec...

Страница 11: ...ps the fans or adjusts their speed When Indoor and Outdoor Temperatures are High When both indoor and outdoor temperatures are high during use of the heating mode the outdoor unit s fan may stop at times Cooling Mode About 0 to 52 C About 21 to 52 C About 0 to 52 C About 0 to 52 C About 18 to 32 C About 80 or less If the unit is used for long pe riods under high humidity conditions condensation ma...

Страница 12: ...the ZONE CONTROL When the ZONE CONTROL button is pressed while multiple air condition ers are being centralized controlled only the preset air conditioners stop Press the ZONE CONTROL button Preset units will stop To Stop the ZONE CONTROL Press the ZONE CONTROL button one more time Those units that were stopped will start again NON STOP OFF ON CLOCK TEMP OFF ON ON OFF TIMER TIMER PROGRAM FAN AUTO ...

Страница 13: ... hear a slight squeaking sound This is caused by minute expansion and contraction of the front cover resulting from change in temperature Some smell may be emitted from the indoor unit This smell is the result of room odors furniture tobacco etc which have been taken into the air conditioner During the Cooling operation a thin mist may be seen emitted from the indoor unit This is a result of sudde...

Отзывы: