PEAK CUT MODE
Operation that suppressed the current value can be performed by means of the following on-
•
site work.
The air conditioner is set to the Peak cut mode when closing the contact input of a
commercial ON/OFF switch to a connector on the outdoor control PC board.
Circuit diagram example
z
Contact capacity : 24VDC or more, 10mA or more.
Outdoor unit
control PC board
Connector
1
2
Signal
Field supply
*10m
Connected unit
Ex.) Switch
* Make the distance from the PC board to the connected unit within 10m.
Use the following parts and construct a circuit as shown above.
•
Input Signal···ON : Peak cut mode, Input Signal···OFF : Normal operation
•
*To set the "Peak cut mode" level, refer to "13.FUNCTION SETTINGS".
ON
OFF
ON
OFF
Input Signal
Peak cut mode
Parts (Optional)
z
Parts name
External connect kit
Model name
UTY-XWZXZ3