Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AS*G18LFCA
[Condition]
Ambient
temperature
Indoor 15, 20, 23 °C / Outdoor 2, 7, 12 °C
Refrigerant
amount
Standard amount
Piping
5.0m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*G18LFCA
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
outdoor unit overall current with the current clamp meter at Power Cable.
length
03-06
2.1
2.3
2.5
2.7
2.9
3.1
0
2
4
6
8
10
12
14
High-pressure
of
outdoor
unit
[MPa]
[50Hz-230V]
Outdoor ambient temperature [ C]
23 C
20 C
15 C
Indoor ambient
temperature[ C]
6.0
6.4
6.8
7.2
7.6
[50Hz-230V]
23 C
20 C
15 C
Indoor ambient
temperature[ C]
Outdoor ambient temperature [ C]
Outdoor
total
electric
current
[A]
0
2
4
6
8
10
12
14
8.0
AS*G18LFCA
Содержание AO*G18LFC series
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 55: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 63: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Sep 2011 Printed in Japan ...