Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AS*G18LFCA
[Condition]
Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
length
5.0m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Cooling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*G18LFCA
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*G18LFCA
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor
unit overall current with the current clamp meter at Power Cable.
03-05
0.7
0.8
0.9
1.0
1.1
1.2
1.3
16
18
20
22
24
26
28
30
32
Low-pressure of outdoor unit [MPa
[50Hz-230V]
RH70%
RH60%
RH50%
In/Outdoor ambient temperature [ C]
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
16
18
20
22
24
26
28
30
32
In/Outdoor ambient temperature [ C]
Outdoor total electric current [A]
RH70%
RH60%
RH50%
[50Hz-230V]
3-2. Outdoor unit Pressure Value and Total Electric Current Curve
Содержание AO*G18LFC series
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 55: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 63: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Sep 2011 Printed in Japan ...