4) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a
correction.
The settings may be changed as shown in the table below.
(
... Factory setting)
Setting description
Function number
Setting value
Standard
31
00
Lower control
01
Slightly warmer control
02
Warmer control
03
When using floor console installation, change the setting value to "01".
5) Auto restart
Enable or disable automatic system restart after a power outage.
(
... Factory setting)
Setting description
Function number
Setting value
Yes
40
00
No
01
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, or external input device.
6) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller
temperature sensor.
(
... Factory setting)
Setting description
Function number
Setting value
No
42
00
Yes
01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller
unit sensor.
7) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(
... Factory setting)
Setting description
Function number
Setting value
A
44
00
B
01
C
02
D
03
8) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
... Factory setting)
Setting description
Function number
Setting value
Operation/Stop mode
46
00
(Setting forbidden)
01
Forced stop mode
02
Содержание AO*G12LALL series
Страница 2: ...1 INDOOR UNIT DUCT TYPE AR G12LLTB AR G14LLTB AR G18LLTB DTR_AR054E_02 2013 02 28 ...
Страница 49: ...2 OUTDOOR UNIT SINGLE TYPE AO G12LALL AO G14LALL AO G18LALL AO G24LALA DTR_AO099E_02 2013 02 28 ...
Страница 55: ... 02 05 OUTDOOR UNIT AO G12 24LAL OUTDOOR UNIT AO G12 24LAL MODEL AO G24LALA ...
Страница 65: ... 02 15 OUTDOOR UNIT AO G12 24LAL OUTDOOR UNIT AO G12 24LAL SOUND LEVEL CHECK POINT 88888 Airflow ...