02-11
Trouble shooting 8
INDOOR UNIT
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Intake grille error
Indoor unit Controller PCB
Micro switch
When the Micro switch is detected open while running the compressor.
1. Micro switch failure 2. Shorted connector/ wire 3.Controller PCB failure
Indicate or Display:
Refer to error code table.
Check Point 2 :
Check Point 2 : Check Connector (CN11) / Wire
Check Point 1 : Check Limit switch
Check Point 3 : Replace Controller PCB
OK
OK
Check operation of Micro switch. (any blocking by dust, etc.)
Remove Micro switch and check ON/OFF switching operation by using a meter.
>>If Micro switch is detective, replace it.
Check loose contact of CN11 /shorted wire (pinched wire).
>>Replace Micro switch if the wire is abnormal
OK
OK
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
Содержание AO*G09LTCN
Страница 4: ......
Страница 5: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 26: ......
Страница 27: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 64: ......
Страница 65: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2011 Printed in Japan ...