EXTERNAL INPUT
11-1.
CONTROL INPUT (Operation/Stop)
The air conditioner can be remotely operated by means of the following on-site work.
Operation is started at the following contents by adding the contact input of a commercial ON/OFF
switch to a connector on the external control PC board and turning it ON.
Initial starting after power turned on
Starting other than at the left
Operation mode
Auto changeover
Mode at previous operation
Set temperature
24°C
Temperature at previous operation
Air flow mode
AUTO
Mode at previous operation
Circuit diagram example
z
Indoor
control PC board
Connector
1
2
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10 m.
Contact capacity : 5VDC or more, 15mA or more.
Please use the non-polar relays and switches.
Surely insulate with
insulation tape etc. since
this wire is not used.
*10 m
Connected unit
Ex.) Switch
When function setting is "Operation/Stop" mode
•
Operation
Stop
ON
OFF
Input signal
Indoor unit
Parts (Optional)
z
Model name
UTD-ECS5A
Wire (External input)
Содержание AO*A45LCTL series
Страница 2: ...1 INDOOR UNIT DTR_AR049E_02 2013 11 08 DUCT TYPE AR C45LCTU AR C54LCTU ...
Страница 14: ... 01 11 DUCT TYPE AR C45 54LC DUCT TYPE AR C45 54LC WIRING DIAGRAMS 555 MODEL AR C45LC AR C54LC ...
Страница 28: ... 01 25 DUCT TYPE AR C45 54LC DUCT TYPE AR C45 54LC Parts Optional z z Model name UTD ECS5A Wire Heater output ...
Страница 36: ...DTR_AO081E_02 2013 11 08 SINGLE TYPE AO A45LCTL AO A54LCTL 2 OUTDOOR UNIT ...
Страница 42: ... 02 05 OUTDOOR UNIT AO A45 54LC OUTDOOR UNIT AO A45 54LC REFRIGERANT CIRCUIT 444 MODEL AO A45LC AO A54LC ...
Страница 43: ... 02 06 OUTDOOR UNIT AO A45 54LC OUTDOOR UNIT AO A45 54LC WIRING DIAGRAMS 555 MODEL AO A45LC AO A54LC ...