6. INSTALLATION  INSTRUCTIONS

  INDOOR UNIT

• SERVICE SPACE

Leave the space reguired to service the air conditioner. (Fig.1)
(1) If a service hole is provided at the bottom of the product.

(2) If the service hole referenced in (1) is not provided.

• INSTALLING DRAIN PIPE

Position of drain piping and refrigerant piping.

The installed drain pipe should have a downward gradient of 1/50
to 1/100. Make sure that the drain pipe is installed without rises.
Use general hard polyvinylchloride pipe (VP25) and connect
it with adhesive (polyvinylchloride) so that there is no leak-
age. Do not perform air bleeding.

Main drain
On the main drain, provide one trap near the indoor unit.

Safety drain
There is no need to provide a trap for the safety drain. If the
safety drain is connected to the main drain, make the con-
nection below the main trap.

Once installation is complete, check the flow of drain water.

• INSTALLING THE DUCT

Follow the procedure in the following figure to install the duct.
Flange positions for connecting the duct.

Unit : mm

1,250

Inlet port flange

*20

370

14

*25

15

35

350

2 x 160 pitch = 320

75   Outlet port flange

7 x 150 pitch = 1,050

*Spacing between flange and drain pan

Install the air inlet grille for air circulation.
The correct temperature cannot be detected.

Unit

Air Outlet Grille

(Room)

  OUTDOOR UNIT

Provide the space shown in Fig.2 so that the air flow is not
blocked.
• Installing the unit individually

L1

L2

Top blower
outlet

Front air
intake

Rear
air
intake

H (1,200 mm or less)

h

H (1,200 mm or less)

h

• There is no limit to the height of the side wall.
• The height of the wall (H) at the front and rear should be

1,200mm or less.

• If the wall height exceeds 1,200mm, add dimension (h) to

the respective service space dimensions L1 and L2.

Fig. 2

10mm or more

200mm
or more

500mm
or more

10mm or more

Front

Air Inlet Grille

200

890

400

30

1,920

Unit : mm

Service hole

Fig.1

900

900

Unit

H1=100 mm (Approx.)
H2=50 to 100 mm

Drain pipe

Trap

H1

H2

Unit

Main

Safety

Drain Pipe

95
40

60
50

50

200

427

404

318

235

Safety drain pipe
ø25.4mm (O.D.)

Main drain pipe
ø38.1mm (O.D.)

Unit : mm

Содержание AO-90EP

Страница 1: ...HIGH STATIC PRESSURE DUCT TYPE AIR CONDITIONER T E C H N I C A L M A N UA L AR90 ...

Страница 2: ... 1 CONTENTS 1 FEATURES 2 2 DIMENSIONS 4 3 WIRING DIAGRAM 6 4 PERFORMANCE DATA 9 5 OPERATION DETAILS 11 6 INSTALLATION INSTRUCTIONS 12 7 SPECIFICATIONS 13 ...

Страница 3: ...ation ENERGY SAVE mode uses a computer program to economically control unit operation by raising the set temperature slightly in the cooling mode and lowering the set temperature in the heating mode Pipe length up to 50m with height differential up to 30m Easy maintenance Fan motor maintenance Fan motor maintenance can be performed from top bottom right side or left side Fig 1 Fan motor hooks to t...

Страница 4: ...N 2 TUE 3 WED 4 THU 5 FRI 6 SAT TEMP DAY ZONE ENERGYSAVE SET TIME CLOCK ADJUST START STOP SET DAY OFF 1 START STOP Button Pressed to start and stop operation 2 OPERATION Lamp Lights during operation and when the timer is on 3 DAY OFF Button Temporary cancellation of one day timer 4 ENERGY SAVE Button Turns energy save mode on and off 5 ENERGY SAVE Button Lights when the unit is in the energy save ...

Страница 5: ... 4 INDOOR UNIT Unit mm 2 DIMENSIONS OUTDOOR UNIT 1 550 1 410 660 700 600 450 650 1 300 650 1 380 SAMPLE INSTALLATION ...

Страница 6: ... HOOK METAL CONTROL BOX SAFETY DRAIN PORT AIR FLOW OUTLET AIR FLOW INLET COUPLING PIPE MAIN DRAIN PORT 38 1 DRAIN PIPE LIQUID 12 7 FLARE GAS 28 58 FLANGE 1 550 MAXIMUM 1 450 713 MAXIMUM 600 450 25 4 SAFETY DRAIN ...

Страница 7: ...CN 7 GRAY GRAY 2 3 1 CN 15 FLOAT SWITCH 3 5 1 4 3 5 CN 5 2 3 1 2 3 1 CN 1 2 1 3 2 1 3 CN 17 RED WHITE BLACK WHITE FUSE T3 15A 250V F101 BLACK GREEN WHITE RED BLACK BLUE WHITE RED BLACK BLUE BLUE THERMAL PROTECTOR PURPLE BLUE 1 2 3 N L TO OUTDOOR UNIT TERMINAL RED WHITE BLACK 1 2 N 3 TO POWER TERMINAL BLACK WHITE RED T S R 3 2 1 4 5 6 3 2 1 4 5 6 FM Models AR 90T AR 90E Note Y Europe version T Aust...

Страница 8: ... WHITE BLACK BLACK GREEN GREEN WHITE RED RED BLACK BLACK RED BELTHEATER B BELT HEATER A MAGNETIC RELAY B FAN MOTOR A FAN CAPACITOR PRESSURE SWITCH EARTH CR COMPOSITE 1 POWER RELAY A WHITE RED BLACK PURPLE 1 2 3 6 5 4 CN 9 3 2 1 RED BROWN BLUE ORANGE YELLOW WHITE 6 5 4 CN 11 3 2 1 1 2 CN 16 3 4 5 CN 18 3 2 1 CN 6 3 2 1 CN 4 3 2 1 CN 13 E 3 2 1 CN 7 1 2 3 4 5 BLACK 2 3 R S T N EV FM BLUE RED WHITE B...

Страница 9: ...PE TEMP BROWN BROWN GREEN GREEN WHITE RED RED BLACK BLACK RED BELTHEATER B BELT HEATER A MAGNETIC RELAY B FAN MOTOR A FAN CAPACITOR PRESSURE SWITCH SOLENOID COIL EARTH CR COMPOSITE 1 POWER RELAY A WHITE RED BLACK PURPLE 1 2 3 6 5 4 CN 9 3 2 1 RED BROWN BLUE ORANGE YELLOW WHITE 6 5 4 CN 11 3 2 1 1 2 CN 16 3 4 5 CN 18 3 2 1 CN 6 3 2 1 CN 4 3 2 1 CN 13 E 3 2 1 CN 7 1 2 3 4 5 BLACK 2 3 R S T N EV 4WV ...

Страница 10: ...input Outdoor DB C Capacity 120 COOLING 110 100 90 90 80 80 19 13 23 16 5 27 19 19 13 31 22 5 23 16 5 27 19 31 22 5 Indoor DB WB C 0 5 10 15 20 25 30 35 40 45 50 70 100 110 Total input Outdoor DB C Capacity 120 HEATING 110 100 90 90 80 80 15 27 20 27 20 15 Indoor DB C 5 0 5 10 15 20 6 2 3 7 5 12 17 5 70 100 110 Total input Outdoor DB C Capacity COOLING MODEL REVERSE MODEL ...

Страница 11: ...0 6000 900 1000 1100 1200 1300 1400 1500 1600 m3 h Sec Air Flow COOLING Temp C 3000 50 0 45 0 40 0 35 0 4000 5000 6000 900 1000 1100 1200 1300 1400 1500 1600 m3 h Sec Air Flow HEATING Temp C FAN CURVE OUTLET AIR TEMPERATURE CAPACITY BY AIR FLOW COOLING SENSIBLE CAPACITY INDOOR TEMP OUTDOOR TEMP C C 25 30 35 40 45 DB WB Total Sens Total Sens Total Sens Total Sens Total Sens 19 13 22 9 17 3 21 8 16 ...

Страница 12: ...the installation There is no extra re frigerant in the outdoor unit for air purging Use a vacuum pump for R407C exclusively Using the same vacuum pump for different refrigerant may dam age the vacuum pump or the unit When moving and installing the air conditioner do not mix gas other than the specified refrigerant R407C inside the refrigerant circuit When charging the refrigerant R407C always use ...

Страница 13: ...he following figure to install the duct Flange positions for connecting the duct Unit mm 1 250 Inlet port flange 20 370 14 25 15 35 350 2 x 160 pitch 320 75 Outlet port flange 7 x 150 pitch 1 050 Spacing between flange and drain pan Install the air inlet grille for air circulation The correct temperature cannot be detected Unit Air Outlet Grille Room OUTDOOR UNIT Provide the space shown in Fig 2 s...

Страница 14: ...oling kW kW 2 25 2 31 2 03 2 03 Heating 2 36 2 36 Fan Speed Indoor r p m 1 140 When static pressure is 200Pa Outdoor 730 Air Flow Indoor m3 h 4 300 1 194 When static pressure is 200Pa Outdoor s 5 800 1 611 Standard Static Pressure Pa 200 Net Indoor 450 x 1 550 x 700 Dimensions Outdoor mm 1 380 x 1 300 x 650 H x W x D Gross Indoor 550 x 1 750 x 825 Outdoor 1 535 x 1 400 x 700 Weights Net Gross Indo...

Страница 15: ...ED A SUBSIDIARY OF FUJITSU GENERAL LIMITED HEAD OFFICE SYDNEY 100 Holbeche Road Arndell Park N S W 2148 TEL 02 8822 2500 MELBOURNE Unit 7 14 Lionel Road Mount Waverley VIC 3149 TEL 03 9543 5899 also all Tasmanian enquiries BRISBANE Suite 1 Level 5 301 Coronation Drive Milton QLD 4064 TEL 07 3367 2008 ADELAIDE 146 Fullarton Road Rose Park S A 5067 TEL 08 8364 0588 PERTH Suite 3 5 Mumford Place Balc...

Отзывы: