En-2
• Be sure to read this Manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information
pertaining to your safety. Be sure to observe them.
• Hand this Manual, together with the Operating Manual, to the customer. Request the
customer to keep them on hand for future use, such as for relocating or repairing the
unit.
WARNING
Request your dealer or a professional installer to install the indoor unit in accordance
with this Installation Manual. An improperly installed unit can cause serious accidents
such as water leakage, electric shock, or
fi
re. If the indoor unit is installed in disregard
of the instructions in the Installation Manual, it will void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed. Turning ON the power
before the work is completed can cause serious accidents such as electric shock or
fi
re.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a
fl
ame, it produces a toxic gas.
Installation must be performed in accordance with the requirement of NEC (National
Electrical Code) and CEC (Canadian Electrical Code) by authorized personnel only.
Except for EMERGENCY, never turn off main as well as sub breaker of the indoor units
during operation. It will cause compressor failure as well as water leakage. First, stop
the indoor unit by operating the control unit, converter or external input device and then
cut the breaker.
Make sure to operate through the control unit, converter or external input device.
When the breaker is designed, locate it at a place where the users cannot start and
stop in the daily work.
2. ABOUT THIS PRODUCT
1
2.1. Precautions for using R410A refrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the
refrigeration cycle. If air enters the refrigeration cycle, the pressure in the refrigeration
cycle will become abnormally high and cause the piping to rupture.
If there is a refrigerant leak, make sure that it does not exceed the concentration limit.
If a refrigerant leak exceeds the concentration limit, it can lead to accidents such as
oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leak occurs during operation, immediately vacate the premises and
thoroughly ventilate the area. If the refrigerant comes in contact with a flame, it
produces a toxic gas.
]1
2.2. Special tool for R410A
WARNING
To install a unit that uses R410A refrigerant, use dedicated tools and piping materials
that have been manufactured specifically for R410A use. Because the pressure
of R410A refrigerant is approximately 1.6 times higher than the R22, failure to
use dedicated piping material or improper installation can cause rupture or injury.
Furthermore, it can cause serious accidents such as water leakage, electric shock, or
fi
re.
Tool name
Changes
Gauge manifold
The pressure in the refrigerant system is extremely high and
cannot be measured with a conventional (R22) gauge. To
prevent erroneous mixing of other refrigerants, the diameter
of each port has been changed. It is recommended to use
a gauge manifold with a high pressure display range of
30in.Hg to 768 psi (–0.1 to 5.3 MPa) and a low pressure
display range of 30in.Hg to 551 psi (–0.1 to 3.8 MPa).
Charging hose
To increase pressure resistance, the hose material and
base size were changed.
(The charging port thread diameter for R410A is 1/2 UNF 20
threads per inch.)
Vacuum pump
A conventional (R 22) vacuum pump can be used by
installing a vacuum pump adapter.
Be sure that the pump oil does not backflow into the
system. Use one capable for vacuum suction of 5 Torr,
–755 mmHg (–100.7 kPa).
Gas leakage detector
Special gas leakage detector for R410A refrigerant.
]1
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts. The use of non-prescribed parts can cause serious accidents
such as the unit falling, water leakage, electric shock, or
fi
re.
The following installation parts are furnished. Use them as required.
Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Name and Shape
Q’ty
Application
Operating Manual
1
Installation Manual
1
(This book)
Cable tie (Large)
4
For
fi
xing the coupler heat
insulation
Cable tie (Medium)
2
For transmission and remote con-
troller cable binding
Coupler heat insulation (Small)
1
For indoor side pipe joint (Small)
Coupler heat insulation (Large)
1
For indoor side pipe joint (Large)
Special nut A
(Large
fl
ange)
4
For suspending the indoor unit from
ceiling
Special nut B
(Small
fl
ange)
4
Drain hose
2
For installing drain pipe
Φ
3/4 in. (19 mm) [I.D.],
Φ
1-1/16 in. (27 mm) [O.D.]
Hose Band
2
For installing drain hose
Drain hose insulation
2
For installing drain hose
9373870135-03_IM.indb Sec1:2
9373870135-03_IM.indb Sec1:2
10/24/2013 2:57:10 PM
10/24/2013 2:57:10 PM