•  Be sure to read this Manual thoroughly before installation.
•  The warnings and precautions indicated in this Manual contain important information 

pertaining to your safety. Be sure to observe them.

•  Hand this Manual, together with the Operating Manual, to the customer. Request the 

customer to keep them on hand for future use, such as for relocating or repairing the 
unit.

 WARNING

Request your dealer or a professional installer to install the indoor unit in accordance 
with this Installation Manual. An improperly installed unit can cause serious accidents 
such as water leakage, electric shock, or 

fi

 re. If the indoor unit is installed in disregard 

of the instructions in the Installation Manual, it will void the manufacturer’s warranty.

Do not turn ON the power until all work has been completed. Turning ON the power 
before the work is completed can cause serious accidents such as electric shock or 

fi

 re.

If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant 
comes in contact with a 

fl

 ame, it produces a toxic gas.

Installation must be performed in accordance with the requirement of NEC (National 
Electrical Code) and CEC (Canadian Electrical Code) by authorized personnel only.

Except for EMERGENCY, never turn off main as well as sub breaker of the indoor units 
during operation. It will cause compressor failure as well as water leakage. First, stop 
the indoor unit by operating the control unit, converter or external input device and then 
cut the breaker.
Make sure to operate through the control unit, converter or external input device.
When the breaker is designed, locate it at a place where the users cannot start and 
stop in the daily work.

2.  ABOUT THIS PRODUCT

1

2.1. Precautions for using R410A refrigerant

 WARNING

Do not introduce any substance other than the prescribed refrigerant into the 
refrigeration cycle. If air enters the refrigeration cycle, the pressure in the refrigeration 
cycle will become abnormally high and cause the piping to rupture.

If there is a refrigerant leak, make sure that it does not exceed the concentration limit. 
If a refrigerant leak exceeds the concentration limit, it can lead to accidents such as 
oxygen starvation.

Do not touch refrigerant that has leaked from the refrigerant pipe connections or other 
area. Touching the refrigerant directly can cause frostbite.

If a refrigerant leak occurs during operation, immediately vacate the premises and 
thoroughly ventilate the area. If the refrigerant comes in contact with a flame, it 
produces a toxic gas.

]1

2.2. Special tool for R410A

 WARNING

To install a unit that uses R410A refrigerant, use dedicated tools and piping materials 
that have been manufactured specifically for R410A use. Because the pressure 
of R410A refrigerant is approximately 1.6 times higher than the R22, failure to 
use dedicated piping material or improper installation can cause rupture or injury. 
Furthermore, it can cause serious accidents such as water leakage, electric shock, or 

fi

 re.

Tool name

Changes

Gauge manifold

The pressure in the refrigerant system is extremely high and 
cannot be measured with a conventional (R22) gauge. To 
prevent erroneous mixing of other refrigerants, the diameter 
of each port has been changed. It is recommended to use 
a gauge manifold with a high pressure display range of 
30in.Hg to 768 psi (–0.1 to 5.3 MPa) and a low pressure 
display range of 30in.Hg to 551 psi (–0.1 to 3.8 MPa).

Charging hose

To increase pressure resistance, the hose material and 
base size were changed.
(The charging port thread diameter for R410A is 1/2 UNF 20 
threads per inch.)

Vacuum pump

A conventional (R 22) vacuum pump can be used by 
installing a vacuum pump adapter.
Be sure that the pump oil does not backflow into the 
system. Use one capable for vacuum suction of 5 Torr, 
–755 mmHg (–100.7 kPa).

Gas leakage detector

Special gas leakage detector for R410A refrigerant.

]1

2.3. Accessories

 WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or 
other prescribed parts. The use of non-prescribed parts can cause serious accidents 
such as the unit falling, water leakage, electric shock, or 

fi

 re.

The following installation parts are furnished. Use them as required.

Keep the Installation Manual in a safe place and do not discard any other accessories 
until the installation work has been completed.

Name and Shape

Q’ty

Application

Operating Manual

1

Installation Manual

1

(This book)

Cable tie (Large)

4

For 

fi

 xing the coupler heat 

insulation

Cable tie (Medium)

2

For transmission and remote con-
troller cable binding

Coupler heat insulation (Small)

1

For indoor side pipe joint (Small)

Coupler heat insulation (Large)

1

For indoor side pipe joint (Large)

Special nut A 
(Large 

fl

 ange)                

4

For suspending the indoor unit from 
ceiling

Special nut B 
(Small 

fl

 ange)                    

4

Drain hose

2

For installing drain pipe

Φ

 3/4 in. (19 mm) [I.D.],

Φ

 1-1/16 in. (27 mm) [O.D.]

Hose Band

2

For installing drain hose

Drain hose insulation

2

For installing drain hose

9373870135-03_IM.indb   Sec1:2

9373870135-03_IM.indb   Sec1:2

10/24/2013   2:57:10 PM

10/24/2013   2:57:10 PM

Содержание Airstage VR-II ARUH36TLAV

Страница 1: ...0135 03 ARUH36TLAV ARUH48TLAV ARUH60TLAV MANUEL D INSTALLATION MANUAL DE INSTALACIÓN APPAREIL INTÉRIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado 9373870135 03_IM indb 1 9373870135 03_IM indb 1 10 24 2013 2 57 02 PM 10 24 2013 2 57 02 PM ...

Страница 2: ... added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow ...

Страница 3: ...nd thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas 1 2 2 Special tool for R410A WARNING To install a unit that uses R410A refrigerant use dedicated tools and piping materials that have been manufactured specifically for R410A use Because the pressure of R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated p...

Страница 4: ...tall the unit near a source of heat steam or flammable gas Install the unit where drainage does not cause any trouble Install the indoor unit power supply cable transmission cable and remote controller cable at least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you...

Страница 5: ...after a prolonged period causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attach...

Страница 6: ...before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Flare nut in mm Tightening torque lbf ft N m 1 4 6 35 dia 11 8 to 13 3 16 to 18 3 8 9 52 dia 23 6 to 31 0 32 to 42 1 2 12 70 dia 36 1 to 45 0 49 to 61 5 8 15 88 dia 46 5 to 55 3 63 to 75 3 4 19 05 dia 66 4 to 81 1 90 to 110 4 4 ...

Страница 7: ...e outdoor unit or RB unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the i...

Страница 8: ... be located in sight from and readily accessible from all indoor units 1 When connecting to the Heat Recovery System refer to the installation manual of the RB unit 2 When connecting the 2 wire type remote controller Y3 is not used Remote controller Slave Remote controller Indoor unit Remote control 2 2 2 Indoor unit Indoor unit Crossover wiring of power supply Breaker2 Breaker1 Indoor unit Power ...

Страница 9: ...ich will lead to a communication failure 1 6 4 Connection of wiring 1 Remove the control box cover and install each connection cable Loosen the screws 2 locations Cover box 2 After wiring is complete clamp the remote controller cable transmission cable and power supply cable with cable tie CAUTION When switching the DIP switch SW1 be sure to turn off the power supply to the indoor unit Otherwise t...

Страница 10: ...s DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected unit be sure to make a branch outside the indoor unit using a pull box etc as shown on below example DC power supply 12 to 24V connected unit Load resistance P C B P ...

Страница 11: ...ible current 50mA Output select When indicator etc are connected directly Indicator 1 Indicator 2 Indicator 3 Indicator 4 connected unit P C B CNB 01 When connecting with unit equipped with a power supply CNB 01 P C B Connected device 1 Connected device 2 Connected device 3 Connected device 4 Relay Field supply Operation behavior If function setting 60 is set to 00 Connector Output voltage Status ...

Страница 12: ...ceiver unit Optional parts For the installation method please refer to the INSTALLATION MANUAL of IR receiver unit Connection methods Connection terminals Controller PCB IR receiver unit terminal CN18 Wiring arrangement Core Controller PCB Cable clamp Cable tie Field supply 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting...

Страница 13: ... 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 0 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from ...

Страница 14: ...tputs terminals 60 00 Mode 0 Set this function when connecting the VRF system to a ventilator economizer humidifier or other external device The connection terminal functions can be changed depending on the type of external device For details of the connection terminal func tions see the Design Technical Manual 01 Mode 1 02 Mode 2 03 Mode 3 04 Mode 4 05 Mode 5 06 Mode 6 07 Mode 7 08 Mode 8 Control...

Страница 15: ...door unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 13 1 RB unit error Indicator mode 0 5s ON 0 5s OFF 0 1s ON 0 1s O...

Отзывы: