background image

En-13

]1

7.3. Function setting 

•  FUNCTION SETTING can be performed with the wired or wireless remote controller.
  (The remote controller is optional equipment)
•  Refer to the wired or wireless remote controller manual for detailed setting information. 

(Set IU AD, REF AD SW to 0)

•  Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address 

settings.

•  Turn the power of the indoor unit ON before starting the setting.

*  Turning on the power to the indoor units initializes EEV, so make sure the piping air 

tight test and vacuuming have been conducted before turning on the power.

*  Also check again to make sure no wiring mistakes were made before turning on the 

power.

Function details

Function

Function 

number

Setting number

Default

Details

Filter 

indicator 

interval

11

00

Standard

Adjust the 

fi

 lter cleaning interval 

noti

fi

 cation. If the noti

fi

 cation is too 

early, change to setting 01. If the 
noti

fi

 cation is too late, change to 

setting 02.

01

Longer

02

Shorter

Filter 

indicator 

action

13

00

Enable

Enable or disable the 

fi

 lter indica-

tor. Setting 02 is for use with a 
central remote controller.

01

Disable

02

Display 
only on 

central 

remote 

controller

Cool air 

tem-

perature 

trigger

30

00

Standard

Adjust the cool air trigger tem-
perature. To lower the trigger 
temperature, use setting 01. To 
raise the trigger temperature, use 
setting 02.

01

Adjust (1)

02

Adjust (2)

Heat air 

tem-

perature 

trigger

31

00

Standard

Adjust the heat air trigger 
temperature. To lower the trigger 
temperature by 6 degrees C, use 
setting 01. To lower the trigger 
temperature by 4 degrees C, use 
setting 02. To raise the trigger 
temperature, use setting 03.

01

Adjust (1)

02

Adjust (2)

03

Adjust (3)

Auto 

restart

40

00

Enable

Enable or disable automatic system 
restart after a power outage.

01

Disable

Cool Air 
Preven-

tion

43

00

Super low

Restrain the cold air

fl

 ow with mak-

ing the air

fl

 ow lower when starting 

heating operation. To correspond to 
the ventilation, set to 01.

01

Follow the 

setting on 

the remote 

controller

External 

control

46

00

Start/Stop

Allow an external controller to start 
or stop the system, or to perform 
an emergency stop.
*  If an emergency stop is performed 

from an external controller, 
all refrigerant systems will be 
disabled. 

*  If forced stop is set, indoor unit 

stops by the input to the external 
input terminals, and Start/Stop by 
a remote controller is restricted.

01

Emergen-

cy stop

02

Forced 

stop

Error re-

port target

47

00

All

Change the target for reporting er-
rors. Errors can either be reported 
in all locations, or only on the wired 
remote.

01

Display 
only on 

central 

remote 

controller

Fan set-

ting when 

cooling 

thermostat 

OFF

49

00

Follow the 

setting on 

the remote 

controller

When set to 01, the fan stops when 
the thermostat is OFF in cooling 
operation. Connection of the wired 
remote controller (2-wire type 
or 3-wire type) and switching its 
thermistor are necessary.

01

Stop

Switching 

func-

tions for 
external 

inputs and 

external 

outputs 

terminals

60

00

Mode 0

•  Set this function when connecting 

the VRF system to a ventilator, 
economizer, humidi

fi

 er, or other 

external device. 

•  The connection terminal functions 

can be changed depending on the 
type of external device. For details 
of the connection terminal func-
tions, see the Design & Technical 
Manual. 

01

Mode 1

02

Mode 2

03

Mode 3

04

Mode 4

05

Mode 5

06

Mode 6

07

Mode 7

08

Mode 8

Control 

switching 

of external 

heaters

61

00

Auxil-

iary heater 

control 1

Sets the control method for the 
external heater being used. For 
details of the control method, see 
the Design & Technical Manual.

01

Auxil-

iary heater 

control 2

02

Heat 

pump 

prohibition 

control

03

Heater 

selection 

control 

using 

outdoor 

tempera-

ture 1

04

Heater 

selection 

control 

using 

outdoor 

tempera-

ture 2

Operating 

tem-

perature 

switching 

of external 

heaters

62

00

Setting 0

•  Sets the temperature conditions 

when the external heater is ON. 

•  For the temperature conditions, 

see "Temperature conditions when 
the external heater is ON". For a 
more detailed explanation, see the 
Design & Technical Manual. 

01

Setting 1

02

Setting 2

03

Setting 3

04

Setting 4

05

Setting 5

Temperature conditions when the external heater is ON 

Temperature (t) when the external heater is ON= Room temperature - set temperature 

Set value of function: 61

00

01

02

03

04

Set value of 

function: 62

00

t < -5.4°F (-3°C)

 -0.9°F (-0.5°C)

01

t < -3.6°F (-2°C)

 -1.8°F (-1°C)

02

t < -3.6°F (-2°C)

 -3.6°F (-2°C)

03

t < -5.4°F (-3°C)

 -5.4°F (-3°C)

04

t < -7.2°F (-4°C)

 -7.2°F (-4°C)

05

t < -9.0°F (-5°C)

 -9.0°F (-5°C)

8. TEST RUN

]1

8.1. Test run using Outdoor unit (PCB) 

•  Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to 

be used for the test run.

8.2. Test run using remote controller

•  Refer to the Installation Manual for the remote controller to perform the test run using 

the remote controller.

•  When the air conditioner is being test run, the OPERATION and TIMER indicator lamps 

fl

 ash slowly at the same time.

For details, please refer to the Manual of “IR Receiver Unit” or “Wired Remote Controller”.

9. CHECK LIST

]1

Pay special attention to the check items below when installing the indoor unit(s). After 
installation is complete, be sure to check the following check items again.

Check items

If not performed correctly

Check 

box

Has the indoor unit been installed cor-
rectly?

Vibration, noise, indoor unit may drop

Has there been a check for gas leaks 
(refrigerant pipes)?

No cooling, No heating

Has heat insulation work been com-
pleted?

Water leakage

Does water drain easily from the 
indoor units?

Water leakage

Is the voltage of the power source the 
same as that indicated on the label on 
the indoor unit?

No operation, heat or burn damage

Are the wires and pipes all connected 
completely?

No operation, heat or burn damage

Is the indoor unit earthed (grounded)?

Short circuit

Is the connection cable the speci

fi

 ed 

thickness?

No operation, heat or burn damage

Are the inlets and outlets free of any 
obstacles?

No cooling, No heating

Does start and stop air conditioner 
operation by remote controller or 
external device?

No operation

9373870135-03_IM.indb   Sec1:13

9373870135-03_IM.indb   Sec1:13

10/24/2013   2:57:18 PM

10/24/2013   2:57:18 PM

Содержание Airstage VR-II ARUH36TLAV

Страница 1: ...0135 03 ARUH36TLAV ARUH48TLAV ARUH60TLAV MANUEL D INSTALLATION MANUAL DE INSTALACIÓN APPAREIL INTÉRIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado 9373870135 03_IM indb 1 9373870135 03_IM indb 1 10 24 2013 2 57 02 PM 10 24 2013 2 57 02 PM ...

Страница 2: ... added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow ...

Страница 3: ...nd thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas 1 2 2 Special tool for R410A WARNING To install a unit that uses R410A refrigerant use dedicated tools and piping materials that have been manufactured specifically for R410A use Because the pressure of R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated p...

Страница 4: ...tall the unit near a source of heat steam or flammable gas Install the unit where drainage does not cause any trouble Install the indoor unit power supply cable transmission cable and remote controller cable at least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you...

Страница 5: ...after a prolonged period causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attach...

Страница 6: ...before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Flare nut in mm Tightening torque lbf ft N m 1 4 6 35 dia 11 8 to 13 3 16 to 18 3 8 9 52 dia 23 6 to 31 0 32 to 42 1 2 12 70 dia 36 1 to 45 0 49 to 61 5 8 15 88 dia 46 5 to 55 3 63 to 75 3 4 19 05 dia 66 4 to 81 1 90 to 110 4 4 ...

Страница 7: ...e outdoor unit or RB unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the i...

Страница 8: ... be located in sight from and readily accessible from all indoor units 1 When connecting to the Heat Recovery System refer to the installation manual of the RB unit 2 When connecting the 2 wire type remote controller Y3 is not used Remote controller Slave Remote controller Indoor unit Remote control 2 2 2 Indoor unit Indoor unit Crossover wiring of power supply Breaker2 Breaker1 Indoor unit Power ...

Страница 9: ...ich will lead to a communication failure 1 6 4 Connection of wiring 1 Remove the control box cover and install each connection cable Loosen the screws 2 locations Cover box 2 After wiring is complete clamp the remote controller cable transmission cable and power supply cable with cable tie CAUTION When switching the DIP switch SW1 be sure to turn off the power supply to the indoor unit Otherwise t...

Страница 10: ...s DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected unit be sure to make a branch outside the indoor unit using a pull box etc as shown on below example DC power supply 12 to 24V connected unit Load resistance P C B P ...

Страница 11: ...ible current 50mA Output select When indicator etc are connected directly Indicator 1 Indicator 2 Indicator 3 Indicator 4 connected unit P C B CNB 01 When connecting with unit equipped with a power supply CNB 01 P C B Connected device 1 Connected device 2 Connected device 3 Connected device 4 Relay Field supply Operation behavior If function setting 60 is set to 00 Connector Output voltage Status ...

Страница 12: ...ceiver unit Optional parts For the installation method please refer to the INSTALLATION MANUAL of IR receiver unit Connection methods Connection terminals Controller PCB IR receiver unit terminal CN18 Wiring arrangement Core Controller PCB Cable clamp Cable tie Field supply 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting...

Страница 13: ... 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 0 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from ...

Страница 14: ...tputs terminals 60 00 Mode 0 Set this function when connecting the VRF system to a ventilator economizer humidifier or other external device The connection terminal functions can be changed depending on the type of external device For details of the connection terminal func tions see the Design Technical Manual 01 Mode 1 02 Mode 2 03 Mode 3 04 Mode 4 05 Mode 5 06 Mode 6 07 Mode 7 08 Mode 8 Control...

Страница 15: ...door unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 13 1 RB unit error Indicator mode 0 5s ON 0 5s OFF 0 1s ON 0 1s O...

Отзывы: