En-9
6.4.8. Function Setting
This procedure changes the function settings used to control the indoor
unit according to the installation conditions. Incorrect settings can cause
the indoor unit to malfunction. Perform the “Function Setting” according to
the installation conditions using the remote controller.
• Refer to the indoor unit installation manual for details on the function
numbers and setting numbers, before the start of function setting.
1.
Touch the [Function Setting] on the “Maintenance” screen. The
“Function Setting” screen is displayed.
Touch the [Address] on the “Function Setting” screen. The “Address”
screen is displayed.
2.
Touch [ ] or [ ] to select the address of the indoor units to be
con
fi
gured. (To set all indoor units at the same time, touch [All].)
Touch [OK] to return to the Function Setting screen.
3.
Touch the [Function No.] on the “Function Setting” screen. The
“Function No.” screen is displayed.
1.
2.
3.
[002–01]
[00]
[00]
Address
Function No.
Setting No.
Function Setting
Back
Setting
002–01
Address
Cancel
OK
All
[002–01]
[00]
[00]
Address
Function No.
Setting No.
Function Setting
Back
Setting
4.
Touch [ ] or [ ] to set the function number. Touch [OK] to return to
the “Function Setting” screen.
5.
Touch the [Setting No.] on the “Function Setting” screen. The “Set-
ting No.” screen is displayed.
6.
Touch [ ] or [ ] to set the setting number. Touch [OK] to return to
the “Function Setting” screen.
4.
5.
6.
00
Function No.
Cancel
OK
[002–01]
[00]
[00]
Address
Function No.
Setting No.
Function Setting
Back
Setting
00
[002–01]
[00]
Function Setting
Cancel
OK
Address
Function No.
Setting No.
7.
Touch [Back] to return to the “Maintenance”
screen.
[002–01]
[00]
[00]
Address
Function No.
Setting No.
Function Setting
Back
Setting
6.4.9. Installer Password Change
Change the Installer password.
1.
Touch the [Installer Password Change] on the “Maintenance”
screen. The “Installer Password Veri
fi
cation” screen is displayed.
Enter the current password, then touch the [OK].
The default password is “0000” (4 digits).
2.
The “Installer Password Change” screen is displayed.
Enter the new password, then touch the [OK]. It returns to the
“Maintenance” screen.
1.
2.
0
0
CL
5
1
6
2
7
3
8
4
9
Cancel
OK
Installer Password Verification
Enter Current Password
0
CL
5
1
6
2
7
3
8
4
9
Cancel
OK
Installer Password Change
Enter New Password
6.4.10. Initialization
Require an Installer password.
1.
Touch the [Initialization] on the “Main-
tenance” screen. Enter the Installer
password. The “Initialization” screen is
displayed.
When the [OK] is touched, this unit restarts
automatically after initialization. Perform
each setting.
Cancel
OK
Initialization
Remote controller will be initialized
to the factory default setting. OK?
When relocating the set remote controller, initialize it.
7. TEST RUN
• Refer to the indoor unit installation manual.
For how to carry out a test run, refer to
6. 4. Maintenance (Other Settings)
→
6.4.5. Test Run.
8. ERROR CODES
Check the error
1.
If an error occurs, an error icon appears on the “Monitor mode
screen”.
Touch the [Status] on the “Monitor mode screen”. The “Status”
screen is displayed.
2.
Touch the [Error Information] on the “Status” screen. The “Error
Information” screen is displayed. (If there are no errors, the [Error
Information] will not be displayed.)
3.
2-digit numbers correspond to the error code in the table below.
Touch the [Next page] (or [Previous page]) to switch to other con-
nected indoor units.
1.
2.
3.
Set Temp.
Mode
Menu
Status
Fan
Fri 10:00AM
Status
Air Flow Direction
VT
Off
1
3
Off
HZ
Economy
Individual
Anti Freeze
Page 1/ 4
Monitor
Next
Page
Error
Information
02-01
14,15, 41, 44
Error Information
Page 1/ 5
Address
Error Code
Back
Next
Page
For the details of the indoor unit or outdoor unit error, refer to the error
codes in each installation manual.
Error code
Contents
CC.1
Sensor error
C2.1
Transmission PCB error
12.1
Wired remote controller communication error
12.3
Number excess of device in wired remote controller
system
12.4
Wired remote controller system start-up error
26.4
Address duplication in wired remote controller system
26.5
Address setting error in wired remote controller system
15.4
Data acquisition error