En-10

Dry contact terminal ([CNA01])

When a power supply is unnecessary at the input device you want to connect, use 
the Dry contact terminal ([CNA01]).

*a: Select very low current use 

contacts (usable at DC12V, 
DC1mA or less).

*b: The wiring is different from 

Apply voltage terminals. Be 
suf

fi

 ciently careful when wiring.

1
2

connected unit

PC Board

GND

*a

*b

CNA01

When connected to Dry contact terminals of multiple RB units with a connected unit, 
insulate each RB unit with relay, etc. as shown on below example.

RB

 u

n

it

RB

 u

n

it

P

ow

er s

up

pl

y f

or r

el

ay

Input device

K1-K2 : Relay 
(Device for DC current)

PC board

PC board

K1

K2

CNA 01

CNA 01

 

NOTE : 

When connected to multiple RB units directly, it will cause breakdown.

Apply voltage terminal ([CNA02])

When a power supply must be provided at the input device you want to connect, use 
the Apply voltage terminal ([CNA02])

1
2
3

+

+

-

-

Input

 de

vic

e

Load 

resistance

*1

DC power sup-

ply 12 - 24V

connected unit

PC board

CNA02

*c

*d

*1: Make the power supply DC12 to 24V. Select a power supply capacity with an 

ample surplus for the connected load.

Do not impress a voltage exceeding 24V across pins 1-3.

*c: The allowable current is DC 5mA to 10mA. (Recommended: DC5mA) 

Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).

*d: The polarity is [+] for pin 1 and [-] for pin 3. Connect correctly.

When connected to Apply voltage terminals of multiple RB units with a connected 
unit, be sure to make a branch outside the RB unit using a pull box, etc. as shown on 
below example.

In

p

u

t d

ev

ic

RB

 u

n

it

RB

 u

n

it

Load 
resistance

DC power sup-
ply 12 - 24V

connected unit

PC board

PC board

CNA 
02

CNA 
02

COOLING/HEATING PRIORITY FUNCTION

"Edge" input only

Connector

Input signal

Command

CNA01 or CNA02

OFF 

 ON

Heating priority

ON 

 OFF

Cooling priority

CNA01 or 
CNA02

Priority mode 

Heating

On

Off

Cooling

10.  TEST RUN

10.1. Test run using Outdoor unit (PC board)

• Refer to the Installation Manual for the outdoor unit to perform the test run using the 

outdoor unit.

10.2. Test run using Remote Controller

• Refer to the Installation Manual for the remote controller to perform the test run 

using the remote controller.

11.  CHECK LIST

Pay special attention to the check items below when installing the RB unit(s). After 
installation is complete, be sure to check the following check items again.

CHECK ITEMS

If not performed correctly

CHECK 

BOX

Has the RB unit been installed 
correctly?

Vibration, noise, RB unit may 
drop

Has there been a check for gas 
leaks (refrigerant pipes)?

No cooling, No heating

Has heat insulation work been 
completed?

Water leakage

Is the voltage of the power source 
the same as that indicated on the 
label on the RB unit?

No operation, heat or burn 
damage

Is the address setting correctly 
configured?

No operation

Are the wires and pipes all 
connected completely?

No operation, heat or burn 
damage

Is the RB unit earthed (grounded)?

Short circuit

Is the connection cable the specified 
thickness?

No operation, heat or burn 
damage

12.  INDICATOR LAMP STATUS

Power indi-

cator lamp

(Green)

Error

indicator lamp

(Red)

Status contents

(Lit)

Lit when the power is turned on.

(Lit)

(Lit)

The wiring is incorrect. The "IN/U" terminal of RB 

unit and outdoor unit transmission terminal are 

connected with the transmission cable. Correctly 

connect the wiring. When re-wiring, you must turn 

off the power.

(Lit)

(Flashing)

There is a fault with the communication board or 

the main board.

● 

: 0.1s ON / 0.1s OFF

9366249047-03_IM.indb   Sec1:10

9366249047-03_IM.indb   Sec1:10

2015/3/10   14:27:49

2015/3/10   14:27:49

Содержание Airstage UTP-RX01AH

Страница 1: ...NSTALLAZIONE UNITÀ REFRIGERANTE SECONDARIA A uso esclusivo del personale tecnico autorizzato Ελληνικά Português ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΜΟΝΆΔΑ ΔΙΑΚΛΆΔΩΣΗΣ ΨΥΚΤΙΚΟΎ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE DE DERIVAÇÃO DE REFRIGERANTE Apenas para técnicos autorizados Русский Türkçe РУКОВОДСТВО ПО УСТАНОВКЕ МОДУЛЬ ВЕТКИ ОХЛАЖДЕНИЯ Только для авторизованного обслуживающ...

Страница 2: ...rectly grounded and the supply line must be equipped with a dif ferential breaker in order to protect the persons The units are not explosion proof and therefore should not be installed in explosive atmosphere Do not turn on the power until all installation work is complete This unit contains no user serviceable parts Always consult authorized service per sonnel to repairs When moving consult auth...

Страница 3: ...or connectable indoor units refer to the catalogue or the Design Technical manual 4 PIPING SPECIFICATIONS For details of piping specifications refer to the outdoor unit installation manual 5 INSTALLATION WORK 5 1 Selecting an installation location WARNING Take into consideration whether the place you install the main unit can fully with stand its weight For hanger bolts use embedded inserts or emb...

Страница 4: ...33 18 22 147 172 298 147 89 Unit mm Top side A B C 198 155 124 206 48 75 198 268 30 Indoor unit side Outdoor unit side 400 400 100 Unit mm service access Service access A C B Outdoor unit side 500 or more 500 or more 20 or more 20 or more Ceiling hanging Installation limit Unit mm 5 2 2 Wall hanging 333 18 15 198 268 198 7 Unit mm service space grille 20 or more Installation limit 20 or more 300 o...

Страница 5: ... Control box Control box cover Cable clamp 6 Change the control box attachment position 7 Attach the cable clamp ac cessory Thereafter put the cable in the cable clamp 8 Fix the control box position 4 screws 9 Attach Cover B to Cover A 1 screw 10 Attach Cover A 4 screws 11 Attach the control box cover 2 screws 5 7 Installation of the unit WARNING Perform installation in a location which can proper...

Страница 6: ... ø12 7 1 2 Reducer 5 6 7 1 8 0 9 0 ø15 88 5 8 Reducer ø12 7 1 2 ø15 88 5 8 Reducer 11 2 12 5 14 0 ø19 05 3 4 ø12 7 1 2 ø19 05 3 4 18 0 ø19 05 3 4 ø15 88 5 8 Reducer ø19 05 3 4 Table 3 Connection pipe selection for when 2 to 8 indoor units are connected Total capacity of indoor unit kW Suction gas pipe mm in Discharge gas pipe mm in Gas pipe mm in 4 4 to 11 1 ø15 88 5 8 Reducer ø12 7 1 2 ø15 88 5 8...

Страница 7: ...n Locally purchased Cable tie Locally purchased RB Unit 7 ELECTRICAL WIRING 7 1 Safety precautions for electrical wiring WARNING Electrical work must be performed in accordance with this Manual by a person certified under the national or regional regulations Be sure to use a dedicated circuit for the unit An insufficient power supply circuit or improperly performed electrical work can cause seriou...

Страница 8: ...ly and transmission cable Recommended cable size mm2 Cable type Remark Power supply cable 2 5 Type60245 IEC57 or equivalent 1ø 50 Hz 198 to 264 V 2 Cable earth ground Transmission cable 0 33 LONWORKS compatible cable 22 AWG LEVEL 4 NEMA non polar 2 core twisted pair solid core diameter 0 65 mm 7 3 Wiring 7 3 1 Power supply cable Keep the ground cable longer than the other cables 20 mm Power supply...

Страница 9: ...cable cannot be used to connect indoor units belonging to different RB groups GOOD PROHIBITED Refrigerant pipe RB group 1 RB group 1 RB group 2 RB group 2 Transmission line Transmission line L N L N L N L N L N L N Crossover wiring of power supply RB unit RB unit Pull box Power supply Power supply Power supply Breaker Power supply 230V 1ø 50Hz RB unit RB unit Power supply GOOD PROHIBITED Transmiss...

Страница 10: ...ddress Manual address setting Setting example 2 RB AD 10 RB AD 1 Automatic address setting Set this switch to 00 at factory setting 0 to 63 Refrigerant circuit address Manual address setting Setting example 63 REF AD 10 REF AD 1 Automatic address setting Set this switch to 00 at factory setting 0 to 99 For details of automatic address setting please refer to the outdoor unit installation manual 8 ...

Страница 11: ...OOLING HEATING PRIORITY FUNCTION Edge input only Connector Input signal Command CNA01 or CNA02 OFF ON Heating priority ON OFF Cooling priority CNA01 or CNA02 Priority mode Heating On Off Cooling 10 TEST RUN 10 1 Test run using Outdoor unit PC board Refer to the Installation Manual for the outdoor unit to perform the test run using the outdoor unit 10 2 Test run using Remote Controller Refer to the...

Отзывы: