En-2

2.  ABOUT THIS PRODUCT

2.1.  Precautions for using the R410A refrigerant

 WARNING

Do not introduce any substance other than the prescribed refrigerant into the refrigera-
tion cycle. 
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become 
abnormally high and cause the piping to rupture.
If there is a refrigerant leakage, make sure that it does not exceed the concentration 
limit. 
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such as 
oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other 
area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leakage occurs during operation, immediately vacate the premises and 
thoroughly ventilate the area. 
If the refrigerant comes in contact with a flame, it produces a toxic gas.

2.2.  Special tool for R410A

 

WARNING

To install a unit that uses the R410A refrigerant, use dedicated tools and piping materi-
als that have been manufactured specifically for R410A use. 
Because the pressure of the R410A refrigerant is approximately 1.6 times higher than 
the R22, failure to use dedicated piping material or improper installation can cause 
rupture or injury. 
Furthermore, it can cause serious accidents such as water leakage, electric shock, or 
fire.

Tool name

Contents of change

Gauge manifold

Pressure is huge and cannot be measured with a conventional (R22) 
gauge. To prevent erroneous mixing of other refrigerants, the diam-
eter of each port has been changed.
It is recommended to use a gauge manifold with a high pressure dis-
play range 30 in Hg to 768 psi (–0.1 to 5.3 MPa) and a low pressure 
display range 30 in Hg to 551 psi (–0.1 to 3.8 MPa).

Charging hose

To increase pressure resistance, the hose material and base size 
were changed.

Vacuum pump

A conventional (R22) vacuum pump can be used by installing a 
vacuum pump adapter.
Be sure that the pump oil does not backflow into the system. Use 
one capable for vacuum suction of 5 Torr, –755 mm Hg (–100.7 kPa).

Gas leakage 
detector

Special gas leakage detector for HFC refrigerant R410A.

2.3. Accessories

 WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or other 
prescribed parts. 
The use of non-prescribed parts can cause serious accidents such as the unit to fall, 
water leakage, electric shock, or fire.
The following installation parts are furnished. Use them as required.
Keep the Installation Manual in a safe place and do not discard any other accessories 
until the installation work has been completed.

Do not discard any accessories needed for installation until the installation work has been 
completed.

Name and Shape

Q’ty

Application

Operating manual

1

Installation manual

1

(This book)

Cable tie (Large)

4

For fixing the connection pipe 
(Large and Small)

Cable tie (Medium)

2

For transmission and remote 
controller cable binding.

Coupler heat 
insulation 
(Small)

1

For indoor side pipe joint (Small)

Name and Shape

Q’ty

Application

Coupler heat 
insulation 
(Large)

1

For indoor side pipe joint (Large)

Special nut A (Large 
flange)

4

For installing indoor unit

Special nut B 
(Small flange)

4

For installing indoor unit

Template 
(Carton top)

1

For ceiling openings cutting 
Also used as packing

Drain hose

1

For installing drain pipe
(Ø 3/4 in [I.D.]; Ø 1-1/16 in [O.D.])

Hose band

1

For installing drain hose

Drain hose 
insulation

1

For installing drain hose

Cassette grille accessories

Name and Shape

Q’ty

Application

Connector cover

1

For covering connector

Tapping screw
(M5 × 12mm)

4

For mounting cassette grille

Tapping screw 
(M4 × 12mm)

1

For mounting connector cover

2.4. Optional 

parts

Description

Model

Application

External connect kit

UTY-XWZXZC

For output function

(Output terminal / CNB01)

UTY-XWZXZB

For control input function

(Apply voltage terminal / CNA01)

UTY-XWZXZD

For control input function

(Dry contact terminal / CNA02)

UTY-XWZXZ7

For forced thermostat off function

(Apply voltage terminal / CNA03)

UTY-XWZXZE

For forced thermostat off function

(Dry contact terminal / CNA04)

Insulation kit for high 

humidity

UTZ-KXGC

Install when the condition under the roof is 

over 80% in humidity and over 86 °F (30 °C) 

in temperature.

2.5.  About unit of the length

All Fujitsu General products are manufactured to metric units and tolerances. United 
States customary units are provided for reference only. In cases where exact dimensions 
and tolerances are required, always refer to metric units.

9371022581-02_IM.indb   Sec1:2

9371022581-02_IM.indb   Sec1:2

2018/1/23   11:17:07

2018/1/23   11:17:07

Содержание Airstage AUUA4TLAV1

Страница 1: ...4TLAV1 AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV INSTALLATION MANUAL For authorized service personnel only MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado 9371022581 02_IM indb 1 9371022581 02_IM indb 1 2018 1 23 11 17 06 2018 1 23 11 17 06 ...

Страница 2: ...s and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical components immediately after the power supply has been turned off Elec...

Страница 3: ...s be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit to fall water leakage electric shock or fire The following installation parts are furnished Use them as required Keep the Installation Manual in a safe place and do not discard any other accessories until the installation work has been compl...

Страница 4: ...unit where the drain pipe can be easily installed 8 Install the unit where noise and vibrations are not amplified 9 Take servicing etc into consideration and leave the spaces Also install the unit where the filter can be removed 3 2 Installation dimensions Leave the space specified in Fig A so that the air from the blower will cover the entire room Install the indoor unit on a place having a suffi...

Страница 5: ...ses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are avail able on the market Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter in mm Thickness in mm 1 4 6 35 0 032 0 80 3 8 9 52 0 032 0 80 1 2 12 70 0 032 0 80 5 8 15 88 0 039 1 00 3 4 19 05 0 039 1 20 4 2 Pipe requirement CAUTION Refer to the...

Страница 6: ...er heat insulation wrap both end with vinyl tape so that there is no gap After affixing the coupler heat insulation secure it with 2 cable ties large one on each end of the insulation Make sure that the cable ties overlap the heat insulation pipe Coupler heat insulation Accessories Cable tie Large Accessories Heat insulation Heat insulation Cover this portion with heat insulation CAUTION After che...

Страница 7: ...ic parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur We suggest installing GFEB...

Страница 8: ...switch shall be installed between indoor unit and pull box 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring figure below Conduit connector Earth ground wire 2 3 4 in 70 mm 1 3 4 in 45 mm A For solid core wiring 1 To connect the electrical terminal follow the below diagram and conn...

Страница 9: ... of the indoor unit may be damaged Do not bundle the remote controller cable or wire the remote controller cable in paral lel with the indoor unit connection cable to the outdoor unit and the power supply cable It may cause erroneous operation 1 Remove the control box cover and install each connection cable Screw Control box cover 2 Connect the connection cable with the cable tie Conduit connector...

Страница 10: ...ternal dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input select Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously Apply voltage terminal CNA01 CNA03 When a power supply must be provided at the input device you want to connect use the Apply volt...

Страница 11: ...roller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each indoor unit within the group Selection method of functions Operation Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit Forced thermostat off function Edge input only Connector Input signal Command Ch3 of CNA03 or CNA04...

Страница 12: ...ibed 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing...

Страница 13: ...rt Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error report target 47 00 All Change the target for reporting er rors Errors can either be reported in all locations or only on the central remote controller 01 Display only on central remote con troller Fan set ting when cooling thermostat OFF 49 00 Follow the setting on the remote controller When set to 01 the fan stop...

Страница 14: ... FILTER indicator lamp Red Setting number 0 to 9 0 5s ON 0 5s OFF Example Function 31 Setting number 2 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 11 sec 10 sec 9 sec 1 cycle 12 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF 8 CASSETTE GRILLE INSTALLATION 8 1 Remove the intake grille 1 Slide the 2 grille hook Grille hoo...

Страница 15: ...stallation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns See the lamp blinking patterns and error codes in the table below Erro...

Отзывы: