En-14

8.3.  Attach the intake grille

The installation is the reverse of “REMOVING THE INTAKE GRILLE”.
The intake grille can be rotated and installed 4 ways to suit the user’s preference.

 CAUTION

The louver angle cannot be changed if the power is not on, (If moved by hand, it may 
be damaged.)

The grille assembly is directional relative to the air conditioner body.

Install so that there is no gap between the grille assembly and the air conditioner body.

9. TEST 

RUN

9.1.  Test run using Outdoor unit (PCB)

• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to 

be used for the test run.

9.2.  Test run using Outdoor unit (PCB)

• Refer to the Installation Manual for the remote controller to perform the test run using the 

remote controller.

• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps 

flash slowly at the same time.

10. CHECK LIST

Pay special attention to the check items below when installing the indoor unit(s). After 
installation is complete, be sure to check the following check items again.

CHECK ITEMS

If not performed correctly

CHECK 

BOX

Has the indoor unit been installed cor-
rectly?

Vibration, noise, indoor unit 
may drop

Has there been a check for gas leaks 
(refrigerant pipes)?

No cooling, No heating

Has heat insulation work been completed?

Water leakage

Does water drain easily from the indoor 
units?

Water leakage

Is the voltage of the power source the 
same as that indicated on the label on the 
indoor unit?

No operation, heat or burn 
damage

Are the wires and pipes all connected 
completely?

No operation, heat or burn 
damage

Is the indoor unit earthed (grounded)?

Short circuit

Is the connection cable the specified 
thickness?

No operation, heat or burn 
damage

Are the inlets and outlets free of any 
obstacles?

No cooling, No heating

Does start and stop air conditioner opera-
tion by remote control unit or external 
device?

No operation

After installation is completed, has the 
proper operation and handling been 
explained to the user?

11. ERROR CODES

If you use a wired type remote controller, error codes will appear on the remote controller 
display. If you use a wireless remote controller, the lamp on the photodetector unit will 
output error codes by way of blinking patterns. See the lamp blinking patterns and error 
codes in the table below.

Error indications

Wired Remote 

Controller 

Error code

Error contents

OPERATION 
lamp (green)

TIMER 

lamp 

(orange)

FILTER 

lamp (red)

 (1)

 (2)

Remote controller 
communication error

 (1)

 (4)

Network communication error

 (1)

 (6)

Peripheral unit communication 
error

 (2)

 (6)

Indoor unit address setting 
error

 (2)

 (9)

Connection unit number error 
in wired remote controller 
system

Error indications

Wired Remote 

Controller 

Error code

Error contents

OPERATION 
lamp (green)

TIMER 

lamp 

(orange)

FILTER 

lamp (red)

 (3)

 (1)

Indoor unit power supply 
abnormal

 (3)

 (2)

Indoor unit main PCB error

 (3)

 (10)

Indoor unit communication 
circuit (wired remote controller) 
error

 (4)

 (1)

Indoor unit room temp. 
thermistor error

 (4)

 (2)

Indoor unit heat ex. temp. 
thermistor error

 (5)

 (1)

Indoor unit fan motor 1 error

 (5)

 (2)

Indoor unit coil (expansion 
valve) error

 (5)

 (3)

Indoor unit water drain 
abnormal

 (9)

 (15)

Outdoor unit miscellaneous 
error

 (13)

 (1)

RB unit error

Display mode

:

0.5 s ON / 0.5 s OFF

:

0.1 s ON / 0.1 s OFF

( )

:

Number of flashing

Wired remote controller display

UTY-RNKU (3-wire type)

Error code

UTY-RNRUZ* (2-wire type)

Status

Air Flow Direction

VT

Off

1

3

Off

HZ

Economy

Individual

Anti Freeze

Page  1/  4

Monitor

Next

Page

Error

Information

Set Temp.

Mode

Menu

Status

Fan

Fri 10:00AM

Unoccupied

Error icon

Touch the [Status].

Touch the [Error Information].

2-digit numbers are corresponding to 
the error code in the preceding table.

Touch the [Next Page] (or [previous page]) 
to switch to other indoor unit information.

For more information, refer to the installation manual of the remote controller.

For details on marking the ERROR CODES, please refer to the Manual of “IR Receiver 
Unit” or “Wired Remote Controller”.

9371022581-02_IM.indb   Sec1:14

9371022581-02_IM.indb   Sec1:14

2018/1/23   11:17:12

2018/1/23   11:17:12

Содержание Airstage AUUA4TLAV1

Страница 1: ...4TLAV1 AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV INSTALLATION MANUAL For authorized service personnel only MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado 9371022581 02_IM indb 1 9371022581 02_IM indb 1 2018 1 23 11 17 06 2018 1 23 11 17 06 ...

Страница 2: ...s and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical components immediately after the power supply has been turned off Elec...

Страница 3: ...s be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit to fall water leakage electric shock or fire The following installation parts are furnished Use them as required Keep the Installation Manual in a safe place and do not discard any other accessories until the installation work has been compl...

Страница 4: ...unit where the drain pipe can be easily installed 8 Install the unit where noise and vibrations are not amplified 9 Take servicing etc into consideration and leave the spaces Also install the unit where the filter can be removed 3 2 Installation dimensions Leave the space specified in Fig A so that the air from the blower will cover the entire room Install the indoor unit on a place having a suffi...

Страница 5: ...ses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are avail able on the market Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter in mm Thickness in mm 1 4 6 35 0 032 0 80 3 8 9 52 0 032 0 80 1 2 12 70 0 032 0 80 5 8 15 88 0 039 1 00 3 4 19 05 0 039 1 20 4 2 Pipe requirement CAUTION Refer to the...

Страница 6: ...er heat insulation wrap both end with vinyl tape so that there is no gap After affixing the coupler heat insulation secure it with 2 cable ties large one on each end of the insulation Make sure that the cable ties overlap the heat insulation pipe Coupler heat insulation Accessories Cable tie Large Accessories Heat insulation Heat insulation Cover this portion with heat insulation CAUTION After che...

Страница 7: ...ic parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur We suggest installing GFEB...

Страница 8: ...switch shall be installed between indoor unit and pull box 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring figure below Conduit connector Earth ground wire 2 3 4 in 70 mm 1 3 4 in 45 mm A For solid core wiring 1 To connect the electrical terminal follow the below diagram and conn...

Страница 9: ... of the indoor unit may be damaged Do not bundle the remote controller cable or wire the remote controller cable in paral lel with the indoor unit connection cable to the outdoor unit and the power supply cable It may cause erroneous operation 1 Remove the control box cover and install each connection cable Screw Control box cover 2 Connect the connection cable with the cable tie Conduit connector...

Страница 10: ...ternal dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input select Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously Apply voltage terminal CNA01 CNA03 When a power supply must be provided at the input device you want to connect use the Apply volt...

Страница 11: ...roller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each indoor unit within the group Selection method of functions Operation Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit Forced thermostat off function Edge input only Connector Input signal Command Ch3 of CNA03 or CNA04...

Страница 12: ...ibed 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing...

Страница 13: ...rt Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error report target 47 00 All Change the target for reporting er rors Errors can either be reported in all locations or only on the central remote controller 01 Display only on central remote con troller Fan set ting when cooling thermostat OFF 49 00 Follow the setting on the remote controller When set to 01 the fan stop...

Страница 14: ... FILTER indicator lamp Red Setting number 0 to 9 0 5s ON 0 5s OFF Example Function 31 Setting number 2 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 11 sec 10 sec 9 sec 1 cycle 12 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF 8 CASSETTE GRILLE INSTALLATION 8 1 Remove the intake grille 1 Slide the 2 grille hook Grille hoo...

Страница 15: ...stallation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns See the lamp blinking patterns and error codes in the table below Erro...

Отзывы: