background image

En-13

A

Check if [L] is flared uniformly
and is not cracked or scratched.

Die

Pipe

Pipe outside  

diameter  

[mm (in.)]

Dimension A  

[mm (in.)]

Dimension B

-

0
0.4 

[mm (in.)]

Flare tool for R410A,  

clutch type

6.35 (1/4)

0 to 0.5  

(0 to 0.020)

9.1 (11/32)

9.52 (3/8)

13.2 (17/32)

12.70 (1/2)

16.6 (21/32)

15.88 (5/8)

19.7 (25/32)

19.05 (3/4)

24.0 (15/16)

When using conventional flare tools to flare R410A pipes, 
the dimension A should be approximately 0.5 mm (0.020 in.)  
more than indicated in the table (for flaring with R410A flare 
tools) to achieve the specified flaring. Use a thickness gauge 
to measure the dimension A.

Width across 

flats

Width across 

flats

Pipe outside 

diameter [mm (in.)]

Width across flats 

of Flare nut [mm (in.)]

6.35 (1/4)

17 (21/32)

9.52 (3/8)

22 (7/8)

12.70 (1/2)

26 (1-1/32)

15.88 (5/8)

29 (1-5/32)

19.05 (3/4)

36 (1-13/32)

7.3.2. Bending pipes

• 

If pipes are shaped by hand, be careful not to collapse 
them.

• 

Do not bend the pipes in an angle more than 90°.

• 

When pipes are repeatedly bend or stretched, the material 
will harden, making it difficult to bend or stretch them any 
more. 

• 

Do not bend or stretch the pipes more than 3 times.

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. 

If the pipe is bent repeatedly at the same place, it will break.

7.3.3. Pipe connection

 

CAUTION

Be sure to install the pipe against the port on the indoor unit 
correctly. If the centering is improper, the flare nut cannot 
tighten smoothly. If the flare nut is forced to turn, the threads 
will be damaged.

Do not remove the flare nut from the indoor unit pipe until 
immediately before connecting the connection pipe.

Hold the torque wrench at its grip, keeping it at a right angle 
with the pipe, in order to tighten the flare nut correctly.

Tighten the flare nuts with a torque wrench using the specified 
tightening method. Otherwise, the flare nuts could break after 
a prolonged period, causing refrigerant to leak and generate 
a hazardous gas if the refrigerant comes into contact with a 
flame.

 

CAUTION

Connect the piping so that the control box cover can easily be 
removed for servicing when necessary.

In order to prevent water from leaking into the control box, 
make sure that the piping is well insulated.

When the flare nut is tightened properly by your hand, hold 
the body side coupling with wrench, then tighten with a torque 
wrench. (See the table below for the flare nut tightening 
torques.)

Tighten with 2 wrenches.

Holding wrench

Flare nut 

Connection pipe

Torque wrench

Indoor unit pipe 
(Body side)

Flare nut [mm (in.)]

Tightening torque [N·m (lbf·ft)]

6.35 (1/4) dia.

16 to 18 (11.8 to 13.3)

9.52 (3/8) dia.

32 to 42 (23.6 to 31.0)

12.70 (1/2) dia.

49 to 61 (36.1 to 45.0)

15.88 (5/8) dia.

63 to 75 (46.5 to 55.3)

19.05 (3/4) dia.

90 to 110 (66.4 to 81.1)

7.4. Installing heat insulation

Install the heat insulation material after performing a 
refrigerant leak check (see the Installation Manual for the 
outdoor unit for details).

7.4.1. COUPLER HEAT INSULATION

• Insulate with the coupler heat insulation (Accessories) 

around the gas pipe and liquid pipe at indoor unit.

• After installing the coupler heat insulation, wrap both ends 

with vinyl tape so that there is no gap.

• After affixing the coupler heat insulation, secure it with 2 

binders (large), one on each end of the insulation.

• Make sure that the binders overlap the heat insulation 

pipe.

Coupler heat
insulation 
(Accessories)

Cover this portion with 
heat insulation.

Binder (Large)
(Accessories)

Heat insulation

 

CAUTION

After checking for gas leaks (refer to the Installation Manual of 
the outdoor unit), perform this section.

Install heat insulation around both the large (gas) and small 
(liquid) pipes. Failure to do so may cause water leaks.

Содержание AirStage AR12

Страница 1: ...ype Floor standing concealed type 7 6 2A Installation the unit Ceiling concealed type 7 6 2B Install the unit Wall mounted type Floor standing concealed type 10 7 PIPE INSTALLATION 12 7 1 Selecting the pipe material 12 7 2 Pipe requirement 12 7 3 Flare connection Pipe connection 12 7 4 Installing heat insulation 13 8 INSTALLING DRAIN PIPES 14 8 1A Installing drain pipes Ceiling concealed type 14 8...

Страница 2: ...nect all wiring tightly Loose wiring may cause overheat ing at connection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and out door units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin alu minum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sur...

Страница 3: ...pipes It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 0 0014 oz 10 m 33 ft Do not use copper pipes having a collapsed deformed or discolored portion especially on the interior surface Otherwise the expansion value or capillary tube may become blocked with contaminants As an air conditioner using R410A incurs pressure higher than when us...

Страница 4: ...ication Operating Manual 1 Installation Manual 1 This book Installation template 1 For positioning the indoor unit Washer 8 For installing indoor unit Coupler heat insulation Large 1 For indoor side pipe joint Large pipe Coupler heat insulation Small 1 For indoor side pipe joint Small pipe Binder Medium 3 For power supply and remote control cable binding Large 4 For fixing the coupler heat insulat...

Страница 5: ...eter Liquid pipe Gas pipe AR9 12 model 6 35 mm 1 4 in 9 52 mm 3 8 in AR18 model 6 35 mm 1 4 in 12 70 mm 1 2 in AR24 model 6 35 mm 1 4 in 15 88 mm 5 8 in Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F Reverse cycle model only In addition if ...

Страница 6: ...nd receptacle Do not extend the power cable WARNING Refer to local codes for acceptable cable type Cable Cable size Remarks Connection cable 14 AWG 3 cable Ground 1Φ 208 230 V Max Cable Length Limit voltage drop to less than 2 In crease cable gauge if voltage drop is 2 or more 5 SELECTING THE MOUNTING POSITION Correct initial installation location is important because it is difficult to move unit a...

Страница 7: ...32 or more 300 11 13 16 or more 300 11 13 16 or more Inlet air Inlet air Strong and durable floor Strong and durable floor 10 13 32 or less Right side PIPE side Right side PIPE side Grill Duct Grill Strong and durable floor unit mm in 6 2A Installation the unit Ceiling concealed type WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the mai...

Страница 8: ...n WG AR24 Model Set the static pressure outside the unit to 0 2 in WG or less the allowable range is between 0 and 0 2 in WG Replace the cover as follows Remove the screws and then remove cover and fan guard Install the cover with the screws as shown in the illustration below Model Screw M5 AR9 12 9 AR18 11 AR24 13 screw M5 Cover Fan guard Side Inlet Side Outlet Insulation material Field supply Al...

Страница 9: ...7 32 unit mm in AR9 12 AR18 AR24 A 734 28 29 32 934 36 25 32 1134 44 21 32 6 2A 4 FIX THE UNIT 1 Hang the unit Hanger bolt Nut A Field supply Nut B Field supply Washer Accessories Hanger Hanger bolt Nut A Field supply Washer Accessories Nut B Field supply Unit Hanger 20 mm 25 32 in length Cover It might become difficult to open and shut the Cover control box cover when the length exceeds 20 mm 25 3...

Страница 10: ...r in return duct 2 Outlet side Connect the duct to outlet flange Wind the outlet flange connecting to the duct with aluminum tape etc to avoid the air discharge Insulate the duct to avoid condensation CAUTION Check that duct work does not exceed the range of external static pressure of equipment Make sure to insulate ducts to avoid condensation Make sure to insulate between ducts and walls if metal...

Страница 11: ...is installed in wall mounted type floor standing concealed type 6 2B 3 INSTALLING THE UNIT To prevent overturning attach the unit to the floor or the wall To avoid vibration of the unit install vibration isolation pad between the unit and the floor or the wall Leveling Level unit before attaching to floor or wall Level 10 mm or less 13 32 in NO GOOD OK Level NO GOOD OK 10 mm or less 13 32 in CAUTION F...

Страница 12: ...f connecting pipe or for difference of its elevation Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 i...

Страница 13: ... with a torque wrench using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a flame CAUTION Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make ...

Страница 14: ...M1 Be sure to connect the pipes for drainage without leakage To avoid condensation and dripping always insulate the indoor drain pipe Install the drain pipe with downward gradient 1 50 to 1 100 and so there are no rises or traps in the pipe Use general hard polyvinyl chloride pipe 19 mm 3 4 in O D 27 mm 1 1 16 in and connect it with adhesive polyvinyl chloride so that there is no leakage When the ...

Страница 15: ...ten the Hose band 2 at the position where vertical against ground The Hose band 2 must be positioned at the right side of the Drain hose 1 as in the figure CAUTION Do not connect to the Drain hole with adhesive Using adhesive may cause damage and water leaks 3 After installing the Drain hose 1 check if the drainage is smooth When drain pump is not used Natural drainage Downward gradient 2 5 5 0 mm ...

Страница 16: ...h box Erroneous wiring may cause burning of the electric parts Connect the connection cords firmly to the terminal board Imperfect installation may cause a fire Always fasten the outside covering of the connection cord with the cable clip If the insulator is chafed electric leakage may occur Always connect the ground wire 1 Use ring terminals with insulating sleeves as shown in the figure below to co...

Страница 17: ... correct capacity of disconnect switch according to the load CAUTION Tighten the indoor unit connection cable and power supply indoor and outdoor unit branch box terminal board connections firmly with the terminal board screws Faulty connection may cause a fire If the indoor unit connection cable and power supply are wired incorrectly the air conditioner may be damaged Connect the indoor unit connec...

Страница 18: ...ntroller Open the operation panel on the front of the remote control ler remove the 2 screws indicated in the following figure and then remove the front case of the remote controller When installing the remote controller remove the connector from the front case The wires may break if the connector is not removed and the front case hangs down When installing the front case connect the connector to t...

Страница 19: ...tion setting This procedure changes the function settings used to control the indoor unit according to the installation conditions Incorrect settings can cause the indoor unit to malfunction This proce dure should be performed by authorized installation or service personnel only Perform the FUNCTION SETTING according to the installation conditions using the remote controller Refer to the indoor un...

Страница 20: ...ing to the amount of dust or debris in the room If you do not wish the filter sign to be displayed select the setting value for No indication Factory setting Setting description Function number Setting value Standard 400 hours 11 00 Long interval 1000 hours 01 Short interval 200 hours 02 No indication 03 2 Static pressure Select appropriate static pressure according to the installation conditions F...

Страница 21: ...he room temperature sensor may require a correction The settings may be changed as shown in the table below Factory setting Setting description Function number Setting value Standard 31 00 Lower control 01 Slightly warmer control 02 Warmer control 03 When using floor console installation change the setting value to 01 5 Auto restart Enable or disable automatic system restart after a power outage F...

Страница 22: ...pressor protection CHECK ITEMS 1 Is operation of each button on the remote control unit normal 2 Does each lamp light normally 3 Do not air flow direction louvers operate normally 4 Is the drain normal 5 Is there any abnormal noise and vibration during operation Do not operate the air conditioner in test run for a long time OPERATION METHOD For the operation method refer to the operating manual 1 S...

Страница 23: ... off the main power DUAL REMOTE CONTROLLERS 2 separate remote controllers can be used to operate the indoor units The timer and self diagnosis functions cannot be used on the slave units 1 Wiring method indoor unit to remote controller Remote controller cable Indoor unit Remote controller Slave unit Master unit 2 Remote controller DIP switch 1 setting Set the remote controller DIP switch 1 No 2 ac...

Страница 24: ...1 12 2 Remote sensor Optional parts Connection method Connection terminals Remote sensor terminal CN8 Wiring arrangement Binder Remove the existing connector and replace it with the remote sensor connector ensure that the correct connector is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Setting for room temperature cor...

Страница 25: ... Active filter error PFC circuit error Voltage error stoppage permanently Voltage error can restore Over current protected operation stoppage permanently PFC hardware error 6 5 Outdoor unit IPM error Trip terminal L error 6 10 Outdoor unit Display panel error Microcomputers communication error 7 1 Outdoor unit Discharge thermistor error Discharge thermistor 1 error 7 2 Outdoor unit Compressor therm...

Страница 26: ...cordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote control unit operations 2 Air filter removal and cleaning and how to use the air louvers 3 Give the operating manual to the customer 4 If the wireless remote control signal code is changed from A to B C or D it will change back to A when the batteries...

Отзывы: