En-8

5.4.2  Removing the pinch pipe

 WARNING

Remove the pinch pipe only when the internal gas is completely drained as shown on 
the below instructions.
If gas still remains inside, the piping may crack if you melt the brazing filler metal of the 
junction area with a burner.

Before connecting the piping, remove the pinch pipe in accordance with the following 
instructions:

1)  Verify that the liquid 

side and gas side 3-way 
valves are closed.

2)  Cut the end of the liquid 

side and gas side pinch 
pipe and vent the gas 
inside the pinch pipe.

3)  After all the gas is vented, 

melt the brazing filler 
metal on connecting part 
using a torch and remove 
the pinch pipe.

3-way valves

Pinch pipes

End of pinch pipes

5.4.3  Pipe connection

 CAUTION

Seal the pipe route hole with putty (locally purchased) such that there are no gaps. 
Small insects or animals that are trapped in the outdoor unit may cause a short circuit in 
the electrical component box.

To prevent pipe damage; do not make sharp bends.
Bend the pipe at a radius of 2-3/4 in (70 mm) or greater.

Do not bent pipe many times at same part to prevent break.

After completing all the pipe connection by brazing, perform the indoor unit pipe connec-
tion with a flare joint.

When removing the pinch pipe or brazing the joint pipe, carry out the work while cooling 
down the 3-way valve sufficiently.

• Braze the joint pipe onto the 3-way valves at the liquid and gas side. Install the joint pipe 

appropriately so that it can be connected easily with the main pipe.

• Braze the joint pipe at the liquid and gas side with the main pipe.
*  Be sure to supply nitrogen when brazing.

Connection example

Front connection

Bottom connection

Liquid pipe
(locally 
purchased)

Gas pipe
(locally purchased)

(accessory)

(accessory)

Liquid pipe
(locally purchased)

Gas pipe
(locally 
purchased)

(accessory)

(accessory)

A:

Joint pipe A (72, 96 model), Joint pipe A-L (120 model)

B:

Joint pipe B (72, 96 model), Joint pipe B-L (120 model)

C:

Joint pipe C (72, 96 model)

5.4.4  Handling precautions for the valves

• Mounted part of Blank cap is sealed for protection.
• Fasten blank cap tightly after opening valves.

Operating the valves

• Use a hexagon wrench. 

Liquid valve: size 4 mm, Gas valve: size 8 mm.

Opening:

(1)  Insert the hexagon wrench into the 

valve shaft, and turn it counterclock-
wise.

(2)  Stop turning when the valve shaft can 

no longer be turned. (Open position)

Closing:

(1)  Insert the hexagon wrench into the 

valve shaft, and turn it clockwise.

(2)  Stop turning when the valve shaft can 

no longer be turned. (Closed position)

Opening 
direction

Hexagon wrench

Seal
  (blank cap 

installation 
portion)

Liquid 
pipe

Gas pipe

Opening 
direction

6.  ELECTRICAL WIRING

6.1.  The precautions of electrical wiring

 WARNING

Wiring connections must be performed by a qualified person in accordance with speci-
fications.
The rated supply of this product is 60 Hz, 208/230 V of 3-phase. Use a voltage within 
the range of 187 to 253 V.

Make sure to perform earthing (grounding) work. Improper earthing (grounding) work 
can cause electric shocks.

Before connecting the cables, make sure the power supply is OFF.

We suggest installing GFEB breakers or follow local electrical code. When installing 
this system, install using ground fault equipment breakers (GFEB) to reduce the risk of 
leaking current which may result in electric shock or potential fire.

Be sure to install a breaker of the specified capacity. When selecting breaker, please 
comply with the laws and the regulations of each country. One breaker must be installed 
on the power supply of the outdoor unit. Wrong selection and setup of the breaker will 
cause electric shock or fire.

Do not connect AC power supply to the transmission line terminal board.
Improper wiring can damage the entire system.

Connect the connector cord securely to the terminal.
Faulty installation can cause a fire.

Make sure to secure the insulation portion of the connector cable with the cord clamp. A 
damaged insulation can cause a short circuit.

Never install a power factor improvement condenser. Instead of improving the power 
factor, the condenser may overheat.

CAUTION - Risk of Electric Shock
Before servicing the unit, turn the power supply switch OFF. Then, do not touch electric 
parts for 10 minutes due to the risk of electric shock.

Always use a separate power supply line protected by a circuit breaker operating on all 
cables with a distance between contact of 1/8 in (3 mm) for this unit.

Do not modify power cable, use extension cable or branch wiring. Improper use may 
cause electric shock or fire by poor connection, insufficient insulation or over current.

Use ring terminals and tighten the terminal screws to the specified torques, otherwise, 
abnormal overheating may be produced and possibly cause serious damage inside the 
unit.

Securely install the electrical box cover on the unit. An improperly installed service 
panel can cause serious accidents such as electric shock or fire through exposure to 
dust or water.

If the supply cable is damaged, it must be replaced by the manufacturer, its service 
agent or similarly qualified persons in order to avoid a hazard.

 CAUTION

The primary power supply capacity is for the air conditioner itself, and does not include 
the concurrent use of other devices.

Connect the power cables in positive phase sequence. If there is a missing phase con-
nection, the unit will not operate normally.

Do not use crossover power supply wiring for the outdoor unit.

If the electrical power is inadequate, contact your electric power company.

Install a breaker in a location that is not exposed to high temperatures.
If the temperature surrounding the breaker is too high, the amperage at which the 
breaker cuts out may decrease.

This system uses an inverter, which means that when used with a ground fault breaker 
you must use breakers that can handle harmonics such as a (GFEB) Ground Fault 
Equipment Breaker (100 mA or greater) in order to prevent malfunctioning of ground 
fault device.

When the electrical switchboard is installed outdoors, place it under lock and key so that 
it is not easily accessible.

Never bundle the power supply cable and transmission cable, remote control cable to-
gether. Separate these cables by 2 in (50 mm) or more. Bundling these cables together 
will cause miss operation or breakdown.

Always keep to the maximum length of the transmission cable. Exceeding the maximum 
length may lead to erroneous operation.

The static electricity that is charged to the human body can damage the control PC 
board when handling the control PC board for address setting, etc.
Please keep caution to the following points.
Provide the grounding of Indoor unit, Outdoor unit and Option equipment.
Cut off the power supply (breaker).
Touch the metal section (such as the unpainted control box section) of the indoor or 
outdoor unit for more than 10 seconds. Discharge the static electricity in your body.
Never touch the component terminal or pattern on the PC board.

9380545309-02.indb   8

9380545309-02.indb   8

2018/12/27   8:39:01

2018/12/27   8:39:01

Содержание Airstage AOU120RLAVL

Страница 1: ...T UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado PART No 9380545309 02 AOU72RLAVL AOU96RLAVL AOU120RLAVL 9380545309 02 indb i 9380545309 02 indb i 2018 12 27 8 38 58 2018 12 27 8 38 58 ...

Страница 2: ...to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be neces sary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip pi...

Страница 3: ...rical Code by authorized personnel only Cancer and Reproductive Harm www P65Warnings ca gov CAUTION This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instruc...

Страница 4: ...CN135 UTY XWZXZ9 For External output Base heater CN115 2 6 About unit of the length All Fujitsu General products are manufactured to metric units and tolerances United States customary units are provided for reference only In cases where exact dimensions and tolerances are required always refer to metric units 3 INSTALLATION WORK Please obtain the approval of the customer when selecting the locati...

Страница 5: ...space If you are installing more outdoor units than indicated here please ensure sufficient space or consult your distributing agent as it may affect the performance due to short circuit and other problems Consider the transportation route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Keep the space shown in the ...

Страница 6: ...snow hoods and drift prevention fencing is recommended when blowing and drifting snow is common to the region 3 3 3 Outdoor units installation in multi row The following settings are not recommended in case of cooling by a low outside tem perature Unit in mm 1 Single parallel unit arrangement 2 Multiple parallel unit arrangement 4 100 or more 24 600 or more 40 1000 or more 79 2000 or more 20 500 o...

Страница 7: ...or equivalent Please select the pipe size in accordance with local rules 1 Allowable tensile stress 33 N mm 2 Allowable tensile stress 61 N mm 3 Endurance pressure of the pipes 609 psi 4 2 MPa Table B Diameter of piping used between outdoor unit and first separation tube or header For the following installation conditions it is necessary to increase the piping size Condition 1 Total indoor unit ca...

Страница 8: ...t bend or stretch the pipes more than 3 times 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters the refrigera tion cycle the internal pressure in the refrigeration cycle will become abnormally high and prevent the unit from exerting its full performance Pressure regulating valve Cap Nitrogen gas Brazing area Apply nitrogen gas while brazing the pipes Nitrogen gas...

Страница 9: ...ase comply with the laws and the regulations of each country One breaker must be installed on the power supply of the outdoor unit Wrong selection and setup of the breaker will cause electric shock or fire Do not connect AC power supply to the transmission line terminal board Improper wiring can damage the entire system Connect the connector cord securely to the terminal Faulty installation can ca...

Страница 10: ...he exclusive tool such as a wire stripper If there is no exclusive tool available necessarily carefully strip the coat ing by a cutter etc so that the conductive wire is not damaged If it is damaged it may lead to an open circuit and a communication error Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cr...

Страница 11: ...n the figure below Tightening torque lbf ft N m M3 screw 4 4 to 5 3 0 5 to 0 6 M5 screw 17 7 to 26 5 2 0 to 3 0 Power supply terminal Ring terminal M5 Transmission terminal M3 Power supply cable Conduit Power supply cable Transmission cable Transmission cable Push mount cable tie accessories Push mount cable tie accessories Earth ground cable 5 16 to 3 8 in 8 to 10 mm 1 to 1 9 16 in 25 to 40 mm Ho...

Страница 12: ... priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SETTING 3 The emergency stop function mounted in this model does not guarantee the regula tions of each country For this reason sufficient checking is necessary regarding use Especially s...

Страница 13: ...the wired remote controller 22 Forbidden Factory default 2 2 0 0 z 23 Forbidden Factory default 2 3 0 0 z 24 Forbidden Factory default 2 4 0 0 z 25 Forbidden Factory default 2 5 0 0 z 26 Forbidden Factory default 2 6 0 0 z 27 Forbidden Factory default 2 7 0 0 z 28 Change of unit Temperature Celsius C 2 8 0 0 z Fahrenheit F 0 1 7 FIELD SETTING CAUTION Discharge the static electricity from your body...

Страница 14: ...l automatically return to the low noise mode 41 Low noise mode setting 1 Off Normal 4 1 0 0 z On Low noise mode 0 1 42 Low noise mode level setting Level 1 4 2 0 0 z Level 2 0 1 Forbidden 0 2 50 Forbidden Factory default 5 0 0 0 z 51 Forbidden Factory default 5 1 0 0 z 52 Forbidden Factory default 5 2 0 0 z 60 Forbidden Factory default 6 0 0 0 z 61 Forbidden Factory default 6 1 0 0 z 64 Forbidden ...

Страница 15: ...plifiers can be set automatically from 1 outdoor unit master unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address setting for signal amplifiers When setting the address of the signal amplifier please use the factory setting See the ins...

Страница 16: ...valve Blank cap 72 96 120 6 0 to 7 3 8 1 to 9 9 13 3 to 16 2 18 0 to 22 0 19 9 to 24 4 27 0 to 33 0 16 6 to 20 3 22 5 to 27 5 8 4 to 10 3 11 4 to 14 0 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen in flammable gas or poisonous gas to pressurize the system If oxygen is used there is the danger of an explosion Do not apply shock during sealing test It can rupture th...

Страница 17: ...lated from the length of the liquid pipe Round up the value to 2 decimal places Model B Factory charged amount lbs kg AOU72RLAVL 24 25 11 0 AOU96RLAVL 24 25 11 0 AOU120RLAVL 24 25 11 0 Diameter of liquid pipe in mm a Additional amount for pipe length lbs ft kg m Ø 1 4 6 35 0 014 0 021 Ø 3 8 9 52 0 039 0 058 Ø 1 2 12 70 0 077 0 114 Ø 5 8 15 88 0 120 0 178 Ø 3 4 19 05 0 180 0 268 1 Calculation of ad...

Страница 18: ... temperature control will not activate during test opera tion continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the crank case heater for a sufficient length of time before restarting the operation Perform test operation for each refrigerant system You can set cooling test operation or heating test operatio...

Страница 19: ... 4 2 Outdoor unit network communication 2 error E 1 4 5 The number of indoor unit shortage Function setting error E 2 2 1 Indoor unit capacity error E 2 4 2 Connection unit number error Indoor unit E 2 6 1 Indoor unit duplicate address error E 2 8 1 Auto address setting error E 2 8 4 Signal amplifier auto address error Indoor unit actuator error E 5 U 1 Indoor unit miscellaneous error Outdoor unit...

Отзывы: