External heater output
Control
Primary heater
Auxiliary heater
Function setting
Indoor unit
Control switching
external heaters No. 61
Auxiliary heater control 1
Heat pump
External device*
1
61-00
Auxiliary heater control 2
Heat pump
External device
61-01
Heat pump prohibition
control
External device
None
61-02
Auxiliary heater control by
outdoor temperature 1
Heat pump
External device
61-03
Auxiliary heater control by
outdoor temperature 2
Heat Pump
External device
61-04
Auxiliary heater control by
outdoor temperature 3
Heat Pump
External device
61-05
Auxiliary heat pump
control
External device
Heat pump
61-06
Auxiliary heat pump
control by outdoor
temperature 1
External device
Heat pump
61-07
Auxiliary heat pump
control by outdoor
temperature 2
External device
Heat pump
61-08
Auxiliary heat pump
control by outdoor
temperature 3
External device
Heat pump
61-09
NOTES:
• After turning off the heater, 3 minutes of standby time is required by next power-on of the
heater.
• For items marked “—” in the table, any of validate or invalidate of the setting are acceptable.
• *1: External device means Hot water, Electrical heater, etc.
- 37 -
8-4. Details of function
8. External input and output
CASSETTE TYPE
ADUH09-18LUAS1
CASSETTE TYPE
ADUH09-18LUAS1