2-23. E: 77. Heat sink thermistor error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 77
Detective actuator
Heat sink temperature thermistor
Heat sink temperature thermistor short or open detected
Forecast of cause
Connector failure
Thermistor failure
Inverter PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the outdoor temperature thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of inverter PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-17.
If the voltage does not appear, replace inverter PCB.
↓
End
2-23. E: 77. Heat sink thermistor error (Outdoor unit)
- (03-28) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABYG36KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Страница 40: ......
Страница 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Страница 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Страница 106: ......
Страница 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...