SPECIAL INSTALLATION
SETTING
PUMP DOWN (Refrigerant collecting operation)
ERROR CONTENTS
(outdoor unit)
1. Make a TEST RUN in accordance with the in-
stallation instruction sheet for the indoor unit.
2. OUTDOOR UNIT LEDS
Error contents
Communication error
(Indoor unit - Outdoor unit)
Discharg pipe temperature sensor
Outdoor heat exchanger temperature sensor
Outdoor temperature sensor
Compressor temperature sensor
Heat sink temperature sensor
Pressure switch abnormal
IPM error
Compressor rotor position cannot detect
Compressor cannot operate
Outdoor fan abnormal (upper fan)
Outdoor fan abnormal (lower fan)
No error
LED
1 flash
2 flash
3 flash
4 flash
7 flash
8 flash
9 flash
12 flash
13 flash
14 flash
15 flash
16 flash
lighting
1. When the product is stopped:
When a malfunction occurs in the outdoor unit, the LED on
the circuit board lights to indicate the error. Refer to the fol-
lowing table for the description of each error according to the
LED.
Perform the following procedures to collect the refrigerant
when moving the indoor unit or the outdoor unit.
*When the pump down operation is repeated, temporarily disconnect
the power supply after opening the closed valves (both liquid and gas).
Reconnect the power supply after 2 - 3 minutes and perform the pump
down operation.
*When the start of the operation after pump down operation has been
completed, temporarily disconnect the power supply after opening the
closed valves (both liquid and gas).
Reconnect the power supply after 2-3 minutes and be sure to perform
a test operation for cooling.
1
2
3
4
2. When the product is operating:
1
2
3
4
Press the PUMP DOWN switch on the outdoor unit.
(The LED on the outdoor unit circuit board lights.)
Press the PUMP DOWN switch on the outdoor unit.
The LED on the outdoor unit circuit board lights, and
operation stops. At this point, recovery has not been
completed, so do not close the two- and three-way
valves.
The pump down operation (cooling operation) be-
gins right away. After oparation starts, close the
three-way valve (liquid).
The pump down operation (cooling operation) be-
gins after three minutes. Close the three-way valve
(liquid) after operation starts.
After 2 - 3 minutes, operation stops. Close the three-
way valve (gas) within one minute after operations
stops.
After 2 - 3 minutes, operation stops. Close the three-
way valve (gas) within one minute after operations
stops.
The LED will go out three minutes after it stops.Dis-
connect the power supply after confirming that the
LED has gone out.
The LED will go out three minutes after it stops. Dis-
connect the power supply after confirming that the
LED has gone out.
3-way valve
(Liquid)
3-way valve
(Gas)
2005.12.28
12
Содержание ABU36RSLX
Страница 10: ...600 450V x 4 Model AOU36RLX CONTROLLER PCB ASSEMBLY MAIN PCB K04AW 0504HUE C1 2005 12 28 9 ...
Страница 15: ...407 434 435 408 505 506 69 876 1 387 160 91 91 91 321 386 361 Model ABU36RSLX 2005 12 28 14 ...
Страница 16: ...63 868 385 763 227 321 387 436 424 684 438 876 2 Model ABU36RSLX 2005 12 28 15 ...
Страница 18: ...1 6 7 3 4 5 2 Model AOU36RLX 2005 12 28 17 ...
Страница 19: ...17 18 10 13 11 9 15 14 8 Model AOU36RLX 2005 12 28 18 ...
Страница 20: ...22 23 31 20 29 12 28 12 19 24 26 27 25 30 Model AOU36RLX 2005 12 28 19 ...
Страница 21: ...37 38 33 34 36 35 Model AOU36RLX 2005 12 28 20 ...
Страница 25: ...0512G2981 ...