1-1. COOLING OPERATION
1-1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
The maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode
and the outdoor temperature.
* If the room temperature is 2 degC higher than a set temperature,
the compressor operation frequency will attain to maximum frequency.
* If the room temperature is 2.5 degC lower than a set temperature, the compressor will be stopped.
* When the room temperature is b2 degC to -2.5 degC of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
minimum
frequency
maximum
frequency
18rps
113rps
18rps
80rps
Outdoor air
temperature
A zone
B zone
C zone
D zone
E zone
F zone
Hi
Me
Lo
Quiet
A zone
113rps
113rps
80rps
54rps
66rps
66rps
54rps
45rps
54rps
54rps
45rps
38rps
34rps
34rps
34rps
24rps
80rps
80rps
80rps
49rps
49rps
49rps
49rps
38rps
42rps
42rps
42rps
30rps
34rps
34rps
34rps
22rps
B zone
C zone
D-F zone
A zone
B zone
C zone
D-F zone
( Table 1 : Compressor Frequency Range )
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
01-01
Fan speed mode
When the room
temperature rises
When the room
temperature drops
36°C
32°C
21°C
12°C
2°C
34°C
30°C
19°C
10°C
0°C
AB*G18LVTB
AR*G14/18LLTB
AU*G14/18LVLB
AR*G12LLTB
AU*G12LVLB
AB*G18LVTB
AR*G14/18LLTB
AU*G14/18LVLB
AR*G12LLTB
AU*G12LVLB