Trouble shooting 20
INDOOR UNIT Error Method:
Indoor Unit Fan Motor1 Error
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
OK
Indoor unit Controller PCB
Indoor unit fan motor
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Controller PCB failure 5. Indoor unit fan motor failure
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace It.
Check excessively high temperature around the motor.
(if there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
When the fan motor speed is less than 1/3 of the target fan speed
for 56 seconds.
When detect the 0 rpm for 56 seconds after fan motor started.
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>if Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
Outdoor unit :
POWER
MODE
ERROR
2
5
(L1)
(L2)
(L6)
(L5)
(L4)
(L3)
15
PUMP
DOWN
LOW
NOISE
PEAK
CUT
Indicate or Display:
Economy lamp : Continuous flash.
ERROR CODE : [E : 51]
Indoor Unit : Operation lamp: 5 time Flash,
Timer lamp: 1 time Flash