5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,
while the indoor fan only runs.
When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
01-04
1. Fan speed
2. FAN OPERATION
( Table4 : Indoor Fan Speed )
Operation mode
Air flow mode
Speed (rpm)
1330
1290
1160
980
Cooling/ Fan
Hi
Hi
710
600
480
1330
Me+
Me
Me
Heating
Lo
Lo
1160
930
Quiet
Quiet
680
Dry
S-Lo
X zone: 680
J zone: 660
1500
1360
1230
1050
770
600
480
1440
1230
1000
750
X zone: 750
J zone: 730
Cool air prevention
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure3.
On the other hand, if switched in [HIGH]
[QUIET], the indoor motor will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH,as shown in Table4.
( Fig.3 : Airflow change - over ( Cooling : AUTO ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 4°F
(2°C)
2°F > TR-Ts
(1°C)
4°F > TR-Ts > 2°F
(2°C)
(1°C)
=
TR-Ts > 5°F
(2.5°C)
=
3°F > TR-Ts
(1.5°C)
5°F > TR-Ts > 3°F
(2.5°C)
(1.5°C)
=
HIGH mode
MED mode
LOW mode
ASU9RLF
ASU12RLF
ASU15RLS
4. DRY OPERATION
Refer to the Table4.
During the dry mode operation, the fan speed setting can not be changed.
Содержание 9RLF