SERVICE PARTS INFORMATION 2
Check Point 1 : Check Connection
Check Point 2 : Check Winding Resistance
Check Point 3 : Replace Main PCB
C
S
R
Inverter Compressor
Check terminal connection of Compressor
(loose or incorrect wiring)
Check winding resistance of each terminal
If the resistance value is 0
or infinite, replace Compressor.
If the symptom does not change with above Check 1, 2, replace Main PCB.
Resistance Value :
2.7
at 20°C
02-30
R
S(W)
(WHITE)
C(T)
(BLACK)
Terminal cover opened
(RED)
S(V)
R(U)
R(U)
(RED)
(WHITE)
S(V)
C(W)
(BLACK)
C(W)
(BLACK)
Terminal cover opened
(WHITE)
(RED)
AOU15RLS
AOU12RLFW
AOU9RLFW
Terminal cover opened
AOU9RLFW
Resistance Value :
0.7
at 20°C
AOU12RLFW
Resistance Value :
1.4
at 25°C
AOU15RLS