6.2. How to the install the indoor unit wire harness

1. Remove the screws, then remove the conduit holder.
2. Fasten the indoor unit wire harness to the conduit holder using the lock nut.

IMPORTANT: Refer to 

fi

 gure of indoor unit wire length about the length of indoor unit 

wire harness. 

3. Use the screws to install the conduit holder provide with the indoor unit.
4. Remove the screws, then remove the cable clamp.
5. Connect indoor unit wire harness to the terminal.

Refer to the wiring diagram.

6. Use the screws to install the cable clamp.

lock nut

CONDUIT 

HOLDER

SCREW CONDUIT CON-

NECTOR

Connection cable

Screw

Cable 

clamp 

Connection 

cable

Cable clamp

Screw

Square hole

Insert the tab into the square hole of the indoor unit and fas-

ten with a screw.

Tab

6.3.  How to connect wiring to the terminals

Caution when wiring cable

When stripping off the insulation of a lead wire, always use a special tool such as a wire 
stripper. If there is no special tool available, carefully strip the insulation with a knife etc.
(1) Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to connect to 

the terminal block.

(2) Securely clamp the ring terminals to the wires using an appropriate tool so that the 

wires do not come loose.

Strip : 3/8 in. (10 mm)

Ring terminal

Sleeve

(3) Use the speci

fi

 ed wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-

driver that is too small, otherwise, the screw heads may be damaged and prevent the 
screws from being properly tightened.

(5) Do not tighten the terminal screws too much, otherwise, the screws may break.

Screw with special washer

Wire

Ring terminal

Terminal blocks

Wire

Screw with special washer

Ring terminal

(6) See the table below for the terminal screw tightening torques.

Tightening torque [lbf·in (N·m)]

M4 screw

11 to 16 (1.2 to 1.8)

 CAUTION

•  Attach the cable clamp 

fi

 rmly by holding the connection cable, and make sure that the 

clamp is 

fi

 xed securely. 

Incomplete attachment of the cable clamp might cause a malfunction of the open 
panel.

•  Match the terminal block numbers and connection cable colors with those of the 

outdoor unit.

Erroneous wiring may cause burning of the electric parts.

•  Connect the connection cables 

fi

 rmly to the terminal block. Imperfect installation may 

cause a 

fi

 re.

•  Always fasten the outside covering of the connection cable with the cable clamp. 

(If the insulator is chafed, electric discharge may occur.)

•  Always connect the ground wire.
•  Do not use the earth screw of the indoor unit for the connection other than a speci

fi

 ed 

outdoor unit.

7. FINISHING 

 (1)  Insulate between pipes.

• Insulate suction and discharge pipes separately.
• For rear, right, and bottom piping, overlap the connection pipe heat insulation and 

indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.

• For left and left rear piping, butt the connection pipe heat insulation and indoor unit pipe 

heat insulation together and bind them with and vinyl tape so that there is no gap.

• For left and left rear piping, wrap the area which accommodates the rear piping 

housing section with cloth tape.

• For left and left rear piping, bind the connection cable to the top of the pipe with 

vinyl tape.

• For left and left rear piping, bundle the piping and drain hose together by wrapping 

them with cloth tape over the range within which they 

fi

 t into the rear piping housing 

section.

 (2)  Temporarily fasten the connection cable along the connection pipe with vinyl tape. 

(Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water 
does not enter.)

 (3)  Fasten the connection pipe to the outside wall with a saddle, etc.
 (4)  Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain 

water and wind cannot blow in.

 (5)  Fasten the drain hose to the outside wall, etc.

*Locally purchased

Pipe

Saddle*

Outside wall cap*

Sealer putty*

(Outdoors)

Wall

9318739183_IM.indb   6

9318739183_IM.indb   6

11/19/2014   6:04:31 PM

11/19/2014   6:04:31 PM

Содержание 9318739183

Страница 1: ... strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised plat...

Страница 2: ...gerant R410A have a different charging port thread diameter to pre vent erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching...

Страница 3: ...s or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or s...

Страница 4: ...ping cut off the piping outlet cutting groove with a hacksaw CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur Attach the Drain hose insulation to the drain hose Drain hose insulation Drain hose For left piping and left rear piping alig...

Страница 5: ...ct with a flame CAUTION Connect the piping so that the control box cover can easily be removed for servic ing when necessary In order to prevent water from leaking into the control box make sure that the pip ing is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a wrench then tighten with a torque wrench See the table below for the flare nut ti...

Страница 6: ... m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Connect the conne...

Страница 7: ...or simple remote controller Recommended cable length of wired remote controller is 32 ft 10 m Make sure to do insulate of connecting part when extended the cable 10 2 Remote controller cable modification 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable 2 Connect the remote controller cable and connecting cab...

Страница 8: ...onnecting cable to control board connector 1 Pass the cable from the hole in the back of indoor unit 2 Connect the cable to the control board connector 3 Hook the cable to the rib connect the cable rib CN6 CN16 CN14 PCB hole Option type Connector No Wired remote controller Simple remote controller CN6 External input CN14 External output CN16 4 Use cable clamper and screw to fasten the cable of wir...

Страница 9: ...do not know the air conditioner custom code setting try each of the custom codes A B C D until you find the code which operates the air conditioner STEP 2 Selecting the Function Number and Setting Value 1 Press the SET TEMP buttons to select the function number Press the MODE button to switch between the left and right digits 2 Press the FAN button to proceed to setting the value Press the FAN but...

Страница 10: ...nges When High insulation 01 is selected Overheating overcooling is prevented at the start up All room temp control settings Function 30 31 92 93 will reset to No correction 0 0 F 0 0 C Factory setting Function Number Setting Value Setting Description 95 00 Standard insulation 01 High insulation Room temperature control for indoor unit sensor Depending on the installed environment correction of th...

Страница 11: ...ress the test run button with the tip of a ballpoint pen etc Transmitter section TEST RUN button To end test operation press the remote controller START STOP button When the air conditioner is running by pressing the TEST RUN button the OPERA TION Lamp and TIMER Lamp will simultaneously flash slowly Using the wired remote control Option For the operation method refer to the operating manual 1 Stop...

Страница 12: ... temp sensor error 8 4 Current sensor error 8 6 Discharge pressure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection 9 5 Compressor rotor position detection error 9 7 Outdoor unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Di...

Отзывы: