4.4.1 Application Parameters for Terminal Control with
Fire Mode Fixed Speed
Code
Name
Data setting range
Set
F 01
Frequency Command 1
2
F 02
Operation Method
Terminal command FWD
1
F 03
Maximum Frequency 1
50Hz
F 04
Base Frequency 1
50Hz
F 05
Rated Voltage at Base
Frequency 1
415V
F 06
Maximum Output Voltage 1
415V
F 07
Acceleration Time 1
30 sec
F 08
Deceleration Time 1
30 sec
F 11
Overload detection level
As per motor rating plate
Amps
F 37
Load Selection
Variable torque load
0
F 43
Current Limiter
Disabled
0
E 07
Terminal [X7] Function
Switch to fire mode (FMS)
134
P 01
Number of poles
As per motor rating plate
4
P 02
Rated capacity
As per motor rating plate
kW
P 03
Rated current
As per motor rating plate
Amps
P 99
Motor Selection
Other motors
4
H1 16
Fire Mode
FMS-on
0
H1 17
Confirmation time
3.0
H1 18
Reference frequency
Set frequency required for fire mode
Hz
H1 19
Rotation direction
Forward rotation
2
H1 20
Start method
Auto search
1
H1 21
Reset interval
5.0
Содержание FRENIC HVAC Series
Страница 4: ...Ph 1800 987 616 Email industrial cse uniserve com au Website www cse 1 2 Keypad Functions ...
Страница 5: ...Ph 1800 987 616 Email industrial cse uniserve com au Website www cse 1 3 Navigate Mode Menus ...
Страница 7: ...Ph 1800 987 616 Email industrial cse uniserve com au Website www cse 2 2 Programming Mode Menus ...
Страница 13: ...Ph 1800 987 616 Email industrial cse uniserve com au Website www cse 4 3 Terminal Control with 4 20mA ...